Toshiba RAV-SP1100UT-E, RAV-SP560AT-E Projection margin in flaring B Unit mm, Rigid Clutch type

Page 24

3 SELECTION OF INSTALLATION

How to remove the front panel

1.Remove screws of the front panel.

2.Pull the front panel downward.

Removing the front panel, the electric parts appear at the front side.

The metal pipes are attachable to the piping holes. If the size of the used power pipe does not match with the hole, adjust the hole size to match with pipe size.

Be sure to fix the power cable and indoor/outdoor connecting cable with bundling band sold on the market so that they do not make contact with the compressor and discharge pipe.

(Temperature of the compressor and discharge pipe becomes high.)

In order to avoid the force applied to on the connect- ing section, be sure to fix the cables to the cord clamps provided on the pipe valve fixing plate and the electric parts box.

Electric parts box

Front panel

Terminal plate

Piping hole

Cord clamp

4 REFRIGERANT PIPING

Pipe Forming/End Positioning

Flaring

1. Cut the pipe with a pipe cutter.

*In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that of R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin

size.

A

90˚

Obliquity Roughness

Warp

2. Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.

However, the conventionalB tools can be used by adjusting

projection margin of the copper pipe.

• Flaring size : A (Unit : mm)

 

A

+0

Outer dia. of copper pipe

 

- 0.4

R410A

R22

 

 

 

 

6.4

9.1

9.0

 

 

 

9.5

13.2

13.0

 

 

 

12.7

16.6

16.2

 

 

 

15.9

19.7

19.4

 

 

 

• Projection margin in flaring : B (Unit : mm)

Rigid (Clutch type)

Outer dia.

R410A tool used

Conventional tool used

of copper

 

 

 

 

R410A

R22

R410A

R22

pipe

 

 

 

 

 

6.4

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

9.5

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

12.7

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

15.9

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

Imperial (Wing nut type)

Outer dia. of copper pipe

R410A

R22

 

 

 

6.4

1.5 to 2.0

1.0 to 1.5

 

 

 

9.5

1.5 to 2.0

1.0 to 1.5

 

 

 

12.7

2.0 to 2.5

1.5 to 2.0

 

 

 

15.9

2.0 to 2.5

1.5 to 2.0

 

 

 

56

Image 24
Contents Split Type Adoption of NEW Refrigerant Indoor Unit 4-Way Air Discharge Cassette Type Precautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Accessory and Refrigerant Accessory and Installation Parts Refrigerant PipingSelection of Installation Before installationInstallation Place Necessary Space for InstallationObstacle at rear side Upper side is free Obstacle at front side Upper side is freeInstallation of Outdoor Unit Optional Installation Parts Local Procure Refrigerant Piping ConnectionFor Reference Piping connectionKnockout procedure How to remove the front panelKnockout of Pipe Cover Refrigerant Piping Pipe Forming/End PositioningFlaring size a Unit mm Projection margin in flaring B Unit mm FlaringTightening of Connecting Part Do not apply refrigerating machine oil to the flared surfaceEvacuating Air PurgeVacuum pump How to open the valve EvacuatingSM560AT-E How to remove the valve cover How to wireStripping length power cord and connecting cable Electrical WorkFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410APrecautions for Safety Accessory and Installation Parts SP1100AT-E, SP1400AT-E only SP1100AT-E, SP1400AT-ELength of refrigerant pipe SM1100AT-E, SM1400AT-E Single unitIn installation Moreor Liquid side Gas side Outer diameter Thickness Ø9.5 Ø15.9 Projection margin in flaring B Unit mm Rigid Clutch typeValve at gas side Evacuating How to open the valve Model RAV SM1400AT-E Useful Functions Final Installation Checks

RAV-SP1100UT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400UT-E, RAV-SP560AT-E specifications

Toshiba has consistently been at the forefront of advancing air conditioning technologies, and its line of products, including the RAV-SP1100AT-E, RAV-SP1100UT-E, RAV-SP1400UT-E, RAV-SP800AT-E, and RAV-SP560AT-E, exemplifies this commitment to quality and innovation. These models reflect Toshiba’s dedication to energy efficiency, user comfort, and technological sophistication.

The RAV-SP1100AT-E and RAV-SP1100UT-E are notable for their robust cooling capacities, making them ideal for medium to large spaces. With energy efficiency ratings that comply with global standards, these units help reduce electricity costs while maintaining optimal indoor temperatures. Both models feature advanced inverter technology, which allows for precise cooling and heating control. This technology not only ensures energy savings but also supports quieter operation, enhancing the overall comfort of the environment.

The RAV-SP1400UT-E stands out for its high-performance capabilities, designed to provide efficient climate control even under extreme conditions. This model integrates cutting-edge refrigerant technology, which minimizes environmental impact without compromising on performance. The RAV-SP1400UT-E offers advanced air purification systems that help eliminate dust and allergens, contributing to improved indoor air quality.

For those seeking compact yet powerful solutions, the RAV-SP800AT-E and RAV-SP560AT-E models are excellent choices. They are designed for smaller spaces without sacrificing efficiency. These units are equipped with compact designs that make installation straightforward, while still incorporating Toshiba’s inverter technology, allowing for both heating and cooling functions that adapt seamlessly to changing weather patterns.

All these models support advanced connectivity options, enabling users to monitor and control their units remotely through smart devices. This feature adds convenience and flexibility, allowing for greater energy management and comfort personalization.

In conclusion, Toshiba’s RAV-SP series embodies a blend of energy efficiency, advanced technology, and user-friendly features. These models not only cater to various cooling and heating needs but also prioritize environmental responsibility. With their ability to provide reliable performance across a range of conditions, Toshiba’s RAV-SP1100AT-E, RAV-SP1100UT-E, RAV-SP1400UT-E, RAV-SP800AT-E, and RAV-SP560AT-E stand out as exemplary choices for residential and commercial climate control solutions.