York SHP48 THRU 60, AHP18 THRU 60 specifications AHP24B**N,H21 4HK06501025 23.1

Page 10

 

 

 

 

 

 

 

255029-YTG-J-1007

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

 

 

 

 

 

 

 

 

 

 

 

 

Heat Kit -

Heater

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

Models

Amps

Min. Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Three Phase

 

240V

 

 

 

 

 

 

 

 

208V

240V

208V

240V

208V

240V

 

 

 

 

 

 

 

 

 

 

 

 

AHP24B**(N,H)21

4HK06501025

23.1

27.1

31.3

30

35

10

8

AHP30B**(N,H)21

4HK06501025

23.1

26.8

30.8

30

35

10

8

4HK065N1525

34.7

40.0

46.1

40

50

8

8

 

AHP36C**(N,H)21

4HK06501025

23.1

27.5

31.6

30

35

10

8

4HK06501525

34.7

40.0

46.1

40

50

8

8

 

 

4HK06501025

23.1

29.1

33.4

30

35

10

8

AHP42C**(N,H)21

4HK06501525

34.7

41.6

47.9

50

50

8

8

 

4HK06501825

41.4

48.9

56.3

50

60

8

6

AHP48D**(N,H)21

4HK06501025

23.1

29.3

33.6

30

35

10

8

4HK06501525

34.7

41.8

48.1

50

50

8

8

SHP48D**N21

4HK06501825

41.4

49.0

56.5

50

60

8

6

 

AHP60D**(N,H)21

4HK06501025

23.1

34.5

38.4

35

40

8

8

SHP60D**N21

4HK06501525

34.7

47.0

52.9

50

60

8

6

1.O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

2.Heaters are 3 Phase.

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

 

 

Minimum Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Models

Heater

 

 

 

Circuit

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

 

 

 

 

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

AHP60D**(N,H)21

4HK16501825

31.9 / 35.4

22.4 / 25.9

- / -

35 / 40

25 / 30

- / -

8 / 8

10

/ 10

- / -

SHP60D**N21

 

 

 

 

 

 

 

 

 

 

 

4HK16502525

40.8 / 45.6

31.3 / 36.1

- / -

45 / 50

35 / 40

- / -

8 / 8

8

/ 8

- / -

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

10

Unitary Products Group

Image 10
Contents Models AHP18 Thru 60 and SHP48 Thru FeaturesDescription Dimensions DimensionsCoil Technical Data Models Rated CFM Entering Air F Cooling CapacityDry / Wet Bulb AIR Flow Data 60 Hz Models AccessoriesLimitations Air Handler Voltage 1Normal OperatingApplication Factors Rated CFM VS. Actual CFM Rated AirflowPhysical & Electrical Data Electrical Data Cooling only 60 HzHeater Max Min Total Heat1 KW Staging Models Speed KW & MBH Conversions for Total Power Input RequirementElectrical Data 208/230-1-60 W1 Only W2 Only W1 + W275C Wire Size AWG Min. Circuit AmpacityHeat Kit Max Min Total Heat1 KW Staging Models Speed Electrical Data 208/230-3-601st 2nd 3rd 208/240 W1 OnlyAHP24B**N,H21 4HK06501025 23.1 Cooling Models with Electric Heat Wiring Cooling Models with Electric Heat WiringSINGLE-STAGE Cooling Wiring Typical Applications Unitary 5005 Norman Products York Group Drive 73069