York AHP18 THRU 60, SHP48 THRU 60 Application Factors Rated CFM VS. Actual CFM, Rated Airflow

Page 5

255029-YTG-J-1007

AIR FLOW DATA - 60 Hz MODELS

 

Blower

 

 

 

 

 

230 Volt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

Motor

 

 

 

CFM1 @ External Static Pressure - IWC

 

 

 

 

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

0.20

0.30

 

0.40

0.50

0.60

0.70

 

0.80

0.90

1.00

 

 

 

 

 

High

1054

989

923

 

862

791

665

581

 

202

N/A

N/A

AHP18B**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium

782

762

716

 

670

613

536

315

 

121

N/A

N/A

 

Low

541

519

479

 

445

397

298

168

 

N/A

N/A

N/A

 

High

1232

1167

1098

 

1025

940

826

731

 

622

486

345

AHP24B**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium

966

915

868

 

799

724

641

540

 

452

347

224

 

Low

785

740

684

 

618

532

446

364

 

296

192

131

 

High

1434

1359

1297

 

1220

1138

1050

916

 

782

640

519

AHP30B**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium

1112

1076

1031

 

970

907

802

629

 

507

394

380

 

Low

885

854

821

 

751

686

625

547

 

459

350

N/A

 

High

1760

1681

1607

 

1538

1456

1360

1322

 

1260

966

770

AHP36C**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium

1320

1284

1255

 

1207

1146

1075

988

 

846

729

572

 

Low

1146

1119

1090

 

1038

992

972

841

 

725

617

496

 

High

1883

1764

1657

 

1543

1435

1327

1210

 

902

714

527

AHP42C**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium

1625

1510

1429

 

1339

1256

1172

1038

 

765

609

412

 

Low

1260

1225

1179

 

1110

1047

973

785

 

638

500

340

AHP48D**(N,H)21

High

2029

1944

1837

 

1743

1643

1537

1435

 

1320

1064

789

Medium

1805

1730

1649

 

1566

1479

1385

1286

 

1147

851

683

SHP48D**N21

 

 

Low

1491

1441

1388

 

1328

1253

1174

1076

 

867

726

555

 

 

 

 

High / #1

2256

2226

2198

 

2159

2095

1959

1914

 

1776

1519

1380

AHP60D**(N,H)21

Medium High / #2

1990

1963

1935

 

1893

1857

1820

1783

 

1698

1486

1353

Medium / #3

1774

1748

1704

 

1670

1635

1593

1534

 

1480

1384

1325

SHP60D**N21

 

 

Medium Low / #4

1557

1523

1483

 

1432

1389

1329

1265

 

1235

1198

1167

 

 

 

 

Low / #5

1340

1300

1253

 

1198

1126

1079

1037

 

1007

954

912

1. Includes return air filter and coil.

All air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater, unless otherwise noted.

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow

80%

90%

Rated CFM

110%

120%

 

 

 

 

 

 

Capacity Factor

0.96

0.98

1.00

1.02

1.03

 

 

 

 

 

 

Unitary Products Group

5

Image 5
Contents Description FeaturesModels AHP18 Thru 60 and SHP48 Thru Coil Technical Data DimensionsDimensions Dry / Wet Bulb Cooling CapacityModels Rated CFM Entering Air F Limitations AccessoriesAIR Flow Data 60 Hz Models Air Handler Voltage 1Normal OperatingRated Airflow Application Factors Rated CFM VS. Actual CFMElectrical Data Cooling only 60 Hz Physical & Electrical DataElectrical Data 208/230-1-60 KW & MBH Conversions for Total Power Input RequirementHeater Max Min Total Heat1 KW Staging Models Speed W1 Only W2 Only W1 + W2Min. Circuit Ampacity 75C Wire Size AWG1st 2nd 3rd 208/240 Electrical Data 208/230-3-60Heat Kit Max Min Total Heat1 KW Staging Models Speed W1 OnlyAHP24B**N,H21 4HK06501025 23.1 SINGLE-STAGE Cooling Wiring Cooling Models with Electric Heat WiringCooling Models with Electric Heat Wiring Unitary 5005 Norman Products York Group Drive 73069 Typical Applications