York AHP18 THRU 60, SHP48 THRU 60 Electrical Data 208/230-3-60, 1st 2nd 3rd 208/240, W1 Only

Page 9

255029-YTG-J-1007

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

 

 

Min. Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Models

Heater

 

Circuit

 

 

Circuit

 

 

Circuit

 

Models

 

 

 

 

 

 

 

 

 

 

 

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

 

 

 

 

 

 

 

 

 

 

 

 

AHP24B**(N,H)21

4HK16501306

40.9 / 47.0

19.5 / 22.5

45 / 50

20 / 25

8 / 8

10

/ 10

AHP30B**(N,H)21

4HK16501306

41.6 / 47.9

19.5 / 22.5

45 / 50

20 / 25

8 / 8

10

/ 10

4HK165N1506

45.8 / 52.8

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

AHP36C**(N,H)21

4HK16501506

47.5 / 54.5

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

4HK16501806

43.9 / 50.3

39.8 / 45.8

45 / 60

40 / 50

8 / 6

8

/ 8

 

4HK16501506

47.6 / 54.8

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

AHP42C**(N,H)21

4HK16501806

44.0 / 50.6

39.8 / 45.8

45 / 60

40 / 50

8 / 6

8

/ 8

 

4HK16502006

47.6 / 54.8

43.4 / 50.0

50 / 60

40 / 50

8 / 6

8

/ 8

AHP48D**(N,H)21

4HK16501506

47.6 / 54.8

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

4HK16501806

44.0 / 50.6

39.8 / 45.8

45 / 60

40 / 50

8 / 6

8

/ 8

SHP48D**N21

 

 

 

 

 

 

 

 

 

 

 

4HK16502006

47.6 / 54.8

43.4 / 50.0

50 / 60

40 / 50

8 / 6

8

/ 8

 

 

4HK16501506

52.9 / 59.5

21.7 / 25.0

60 / 60

25 / 25

6 / 6

10

/ 10

AHP60D**(N,H)21

4HK16501806

49.3 / 55.3

39.8 / 45.8

50 / 60

45 / 60

6 / 6

8

/ 6

SHP60D**N21

 

 

 

 

 

 

 

 

 

 

 

4HK16502006

52.9 / 59.5

43.4 / 50.0

60 / 60

45 / 50

6 / 6

8

/ 8

 

4HK16502506

52.9 / 59.5

43.4 / 50.0

21.68 / 25.00

60 / 60

45 / 50

25 / 25

6 / 6

8

/ 8

10 / 10

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

ELECTRICAL DATA - 208/230-3-60

 

Heat Kit -

Max.

Min.

 

Total Heat1

 

 

 

KW Staging

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

Speed

KW

MBH

W1 Only

W2 Only

W1 + W2

Three Phase

Static

 

Tap

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

240V

208V

240V

208V

240V

208V

240V

208V

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AHP24B**(N,H)21

4HK06501025

0.5

Hi

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

AHP30B**(N,H)21

4HK06501025

0.5

Hi

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

4HK065N1525

0.5

Hi

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

 

AHP36C**(N,H)21

4HK06501025

0.5

Med

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

4HK06501525

0.5

Med

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

 

 

4HK06501025

0.5

Med

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

AHP42C**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

4HK06501525

0.5

Med

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

 

4HK06501825

0.5

Hi

12.9

17.2

44.7

58.7

12.9

17.2

12.9

17.2

12.9

17.2

AHP48D**(N,H)21

4HK06501025

0.5

Med

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

4HK06501525

0.5

Med

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

SHP48D**N21

4HK06501825

0.5

Hi

12.9

17.2

44.7

58.7

12.9

17.2

12.9

17.2

12.9

17.2

 

 

4HK06501025

0.5

#3

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

AHP60D**(N,H)21

4HK06501525

0.5

#4

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

SHP60D**N21

 

 

 

 

 

 

 

 

 

 

 

 

 

4HK16501825

0.5

#4

12.9

17.2

44.7

58.7

12.9

17.2

12.9

17.2

12.9

17.2

 

4HK16502525

0.5

#4

18.0

24.0

61.4

81.4

9.0

12.0

18.0

24.0

18.0

24.0

1. See conversion table on Page 7.

Unitary Products Group

9

Image 9
Contents Features Models AHP18 Thru 60 and SHP48 ThruDescription Dimensions DimensionsCoil Technical Data Cooling Capacity Models Rated CFM Entering Air FDry / Wet Bulb Limitations AccessoriesAIR Flow Data 60 Hz Models Air Handler Voltage 1Normal OperatingRated Airflow Application Factors Rated CFM VS. Actual CFMElectrical Data Cooling only 60 Hz Physical & Electrical DataElectrical Data 208/230-1-60 KW & MBH Conversions for Total Power Input RequirementHeater Max Min Total Heat1 KW Staging Models Speed W1 Only W2 Only W1 + W2Min. Circuit Ampacity 75C Wire Size AWG1st 2nd 3rd 208/240 Electrical Data 208/230-3-60Heat Kit Max Min Total Heat1 KW Staging Models Speed W1 OnlyAHP24B**N,H21 4HK06501025 23.1 Cooling Models with Electric Heat Wiring Cooling Models with Electric Heat WiringSINGLE-STAGE Cooling Wiring Unitary 5005 Norman Products York Group Drive 73069 Typical Applications