York GM9S*DH Vent and Supply Outside Air Safety Check Procedure, Ventilated Combustion Air

Page 21

268890-UIM-B-0607

GABLE

VENT

 

VENTILATED

OPTIONAL

ATTIC

INLET (a)

TOP ABOVE

INSULATION

 

SOFFIT

OUTLET

VENT

AIR (a)

 

GAS

 

WATER

 

HEATER

GAS VENT

FURNACE

AIR SUPPLY OPENINGS AND DUCTS

1.An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction. The opening shall be located within 12” (30.5 cm) horizontally from, the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK” in these instructions for

 

additional information and safety check procedure.

 

2.

The duct shall be either metal, or a material meeting the class 1

OUTLET

AIR (b)

 

requirements of CAN4-S110 Standard for Air Ducts.

 

3.

The duct shall be least the same cross-sectional area as the free

 

 

area of the air supply inlet opening to which it connects.

 

4.

The duct shall terminate within 12 in (30.5 cm) above, and

INLET

 

within 24 in (61 cm) horizontally from, the burner level of

 

 

the appliance having the largest input.

AIR (b)

 

GAS

VENT

 

 

OUTLET

 

 

AIR (a)

GAS

FURNACE

INLET

WATER

 

 

HEATER

 

 

 

 

AIR (a)

VENTILATED

CRAWL SPACE

5.A square or rectangular shaped duct shall only be used when the required free area of the supply opening is

9 in2 (58.06 cm2) or larger. When a square or rectangular duct is used, its small dimensionshall not be less than

3 in (7.6 cm).

6.An air inlet supply from outdoors shall be equipped with a means to prevent the direct entry of rain and wind. Such means shall not reduce the required free area of the air supply opening.

7.An air supply inlet opening from the outdoors shall be located not less than 12” (30.5 cm) above the outside grade level.

GABLE

VENT

SOFFIT

VENT

INLET

AIR (b)

GAS

VENT

VENTILATED

ATTIC

TOP ABOVE

INSULATION

GAS

FURNACE

WATER

 

HEATER

 

INLET AIR (a)

COMBUSTION AIR SOURCE FROM OUTDOORS

1.Two permanent openings, one within 12 in (30.5 mm) of the top and one within 12 in (30.5 mm) of bottom of the confined space, Two permanent openings, shall communicate directly or by means of ducts with the outdoors, crawl spaces or attic spaces.

2.One permanent openings, commencing within 12 in (30.5 mm)of the top of the enclosure shall be permitted where the equipment has clearances of at least 1 in (2.54 cm) from the sides and back and 6 in (15.24 cm) from the front of the appliance. The opening shall communicate directly with the outdoors and shall have a minimum free area of:

a.1 square in per 3000 Btu per hour (6.45 cm2 0.879 kW) of the total input rating of all equipment located in the enclosure.

b.Not less than the sum of all vent connectors in the confined space.

3.The duct shall be least the same cross-sectional area as the free area of the air supply inlet opening to which it connects.

4.The blocking effects of louvers, grilles and screens must be given consideration in calculating free area. If the free area of a specific louver aor grille is not known.

FIGURE 27: Outside and Ambient Combustion Air

Vent and Supply (Outside) Air Safety Check Procedure

Follow the procedure in ANSI Z223.1 National Fuel Gas Code. Refer to the section on the “Recommended Procedure for Safety Inspection of an Existing Appliance” or in Canada B149.1-00 Natural Gas and Pro- pane Installation Code section on “Venting Systems and Air Supply for Appliances” and all local codes. In addition to the procedure specified in ANSI Z223.1, it is recommended that you follow the venting safety pro- cedure below. This procedure is designed to detect an inadequate ven- tilation system that can cause the appliances in the area to operate improperly causing unsafe levels of Carbon Monoxide or an unsafe condition to occur.

1.Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other deficiencies, which could cause an unsafe condition

2.Close all building doors and windows and all doors.

3.Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Open the fireplace dampers. Do not operate a summer exhaust fan.

4.Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continuously.

5.Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening after 5 minutes of main burner operation. Appliances that do not have draft hoods need to be checked at the vent pipe as close to the appliance as possible. Use a combustion analyzer to check the CO2 and CO levels of each appliance. Use a draft gauge to check for a downdraft or inadequate draft condition.

6.After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their normal condition.

7.If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can function safely.

NOTE: An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1 in. W.C. (-25 kPa) with all of the appliance(s) operating at the same time.

8.Any corrections to the venting system and / or to the supply (out- side) air system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1-00 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the appropriate tables in Appendix G of the above codes or for this appliance, refer to Table 8 of these instructions.

Ventilated Combustion Air

The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in “COMBUS- TION AIR SOURCE FROM OUTDOORS” in this instruction or in Sec- tion 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (latest edition). This type installation requires two properly sized pipes. One brings combustion air from a properly venti- lated attic space or crawl space and a second pipe that extends from the furnace vent connection (top right of unit) to the exterior of the build- ing. Refer to Table 8 for intake pipe sizing, allowable length and elbow usage. Follow all notes, procedures and required materials in the SEALED COMBUSTION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a venti- lated attic space or crawl space. DO NOT terminate vent pipe in an Attic or Crawl Space.

Ventilated Combustion Air Termination

Refer to Figure 28 for required attic termination for the combustion air intake pipe. For attic termination, use two 90 elbows with the open end in a downward position. Be sure to maintain 12” (30.5 cm) clearance above any insulation, flooring or other material.

A crawl space combustion air installation consists of a straight pipe from the PVC coupling on the burner box that extends into the crawl space and terminates with a 1/4” (0.63 cm) mesh screen and no elbows.

Unitary Products Group

21

Image 21
Contents List of Sections Section I SafetyList of Figures List of TablesSafety Requirements Specific Safety Rules and PrecautionsAnce to a 50 HZ Power Supply or a Voltage Above 130 Volts Combustion AIR Quality List of ContaminantsInspection Furnace Location and ClearancesDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Ductwork Installation Floor Base and Ductwork InstallationSection II Ductwork Ductwork General InformationInput Return1 Rectangular2 Round2 Supply3Round Duct Size Horizontal Installations Without a Cooling Coil Cabinet Horizontal Installations With a Cooling Coil CabinetDownflow Air Conditioning Coil Cabinet Horizontal ModelsFilter Installation Section III FiltersCFM Suspended Furnace / Crawl Space Installation Attic InstallationDownflow Filters Horizontal ApplicationSection IV GAS Piping Section V Electrical Power Electrical Power ConnectionsAfue Supply Voltage Connections LOW Voltage Control Wiring ConnectionsAC1 Section VI Twinning and Staging Combustion AIR and Vent Safety Section VII Combustion AIR and Vent SystemStaging Model Input Pipe Size Maximum Combustion AIR/VENT Pipe SizingElbow Dimension Combustion AIR and Vent Piping AssemblyCombustion AIR / Vent Clearances Furnace Vent Connection SizesHome Layout Vent ClearancesHorizontal Vent Assembly Downflow Vent AssemblyVent System Horizontal Vent Applications and TerminationVenting Multiple Units Vertical Vent Applications TerminationCombustion AIR Supply Outdoor Combustion AirCombustion Air Source From Outdoors Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only BtuhVent and Supply Outside Air Safety Check Procedure Ventilated Combustion AirVentilated Combustion Air Termination Condensate Drain Section Viii Condensate PipingCondensate Drain Trap and Drain Freeze Protection Condensate Drain Hose Part NumbersHorizontal Left Air Flow Inducer Low Refer to Figures 31 Hose #5 Hose #1Hose #9 Hose #4 Hose #6 Horizontal Right Air Flow Inducer High Refer to Figures Unitary Products Group HOSE#1 Hose #2 Barbed TEE Hose #4 Hose #7 Hose #9 Section X START-UP Adjustments Section IX Safety ControlsCalculating the Furnace Input Natural GAS Ignition System SequenceUSA use the following formula to calculate the furnace input Inlet GAS Pressure Range Adjustment of Manifold GAS PressureNominal Manifold Pressure Reading the gas pressure with the burner box cover in placeAdjustment of FAN Control Settings Adjustment of Temperature RiseWith Burner BOX Cover in Place With Burner BOX Cover RemovedDiagnostic Fault Code Storage and Retrieval Furnace Control DiagnosticsSlow Green Flash Normal operation Ignition ControlModels Filter PerformanceAirflow Range Minimum Filter Type Opening Size Disposable PleatedField Installed Accessories NON-ELECTRICAL Applying Filter Pressure Drop to Determine System AirflowModel no Description Used with Section XI Wiring Diagram Unitary 5005 Norman Product York Group Drive 73069

GF9S*DH, GY9S*DH, GM9S*DH specifications

The York GM9S*DH, GF9S*DH, and GY9S*DH series air conditioning systems are known for their robust performance, reliability, and energy efficiency. These models are well-suited for both residential and light commercial applications, making them versatile options for a range of users.

One of the standout features of these systems is their high efficiency. The GM9S*DH is equipped with advanced heating and cooling technologies that allow it to achieve excellent SEER (Seasonal Energy Efficiency Ratio) ratings. This translates to lower energy consumption and reduced utility bills for homeowners and business operators alike. The GF9S*DH model further enhances this efficiency by incorporating variable-speed blowers that adjust airflow based on specific needs, ensuring that the system operates only as necessary.

Reliability is another key characteristic of the York GM9S*DH, GF9S*DH, and GY9S*DH series. These models are engineered with durable components and rigorous performance testing, which contributes to their long lifespan and minimizes the need for repairs. Moreover, they come with robust warranties that provide peace of mind for consumers.

In terms of technology, these units utilize a smart thermostat feature that allows for precise temperature control and programmable settings. This feature not only enhances comfort but also contributes to energy savings by allowing users to set optimal cooling or heating schedules. The systems are also designed with quiet operation in mind, employing sound-dampening features that minimize noise levels, which is particularly beneficial for residential installations.

The installation of the York GM9S*DH, GF9S*DH, and GY9S*DH systems is straightforward, offering flexibility in placement and integration with various home or office setups. Their compact design allows them to fit seamlessly into different environments without compromising on performance.

Additionally, the systems are equipped with advanced filtration options that improve indoor air quality by capturing allergens and pollutants. This is particularly beneficial for families with children or members who suffer from allergies.

Overall, the York GM9S*DH, GF9S*DH, and GY9S*DH series provide exceptional performance, energy efficiency, and reliability, making them an ideal choice for maintaining a comfortable indoor environment. With their cutting-edge technologies and user-friendly features, these systems represent an excellent investment for anyone looking to enhance their heating and cooling experience.