This furnace may not be common vented with any other appliance, since it requires separate, properly sized air intake and vent lines. The furnace shall not be connected to any type of B, BW or L vent or vent connector, and not connected to any portion of a factory- built or masonry chimney
The furnace shall not be connected to a chimney flue serving a sep- arate appliance designed to burn solid fuel.
When combustion air pipe is installed above a suspended ceiling or when it passes through a warm and humid space, the pipe must be insulated with 1/2” Armaflex or other heat resistant type insulation.
Vent piping must be insulated with 1/2” insulation if it will be sub- jected to freezing temperatures such as routing through unheated areas or through an unused chimney.
COMBUSTION AIR/VENT PIPE SIZING
The size of pipe required will be determined by the furnace model, the total length of pipe required and the number of elbows required.
Table 8 lists the maximum equivalent length of pipe allowed for each model of furnace. The equivalent length of elbows is shown in Table 9. The equivalent length of the vent system is the total length of straight pipe PLUS the equivalent length of all of the elbows.
The following rules must also be followed:
1.Long radius (sweep) elbows are recommended. Standard elbows may be used, but since they have a longer equivalent length, they will reduce the total length of pipe that will be allowed. Short radius (plumbing vent) elbows are not allowed. The standard dimensions of the acceptable elbows are shown below.
2.The maximum equivalent length listed in Table 8 is for the vent pip- ing and the air intake piping separately. For example, if the table allows 65 equivalent feet for a particular model, then the vent can have 65 equivalent feet of pipe, AND the combustion air intake can have another 65 equivalent feet of pipe.
3.Three vent terminal elbows (two for the vent and one for the com- bustion air intake) are already accounted for and need not be included in the equivalent length calculation.
4.All combustion air and vent pipe must conform to American National Standards Institute (ANSI) and American Society for Test- ing and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core), D2261 (ABS-DWV) or F628 (Schedule 40 ABS). Pipe cement and primer must conform to ASTM Standard D2546 (PVC) or D2235 (ABS). If ABS pipe is to be used, any joint where ABS pipe is joined to PVC pipe must be glued with cement that is approved for use with BOTH materials. Metallic materials must not be used for venting or air intake.
5.If a flexible connector is used in the vent system, it must be made of a material that is resistant to acidic exposure and to at least 225° F temperature. Flexible connectors are also allowed in the combustion air pipe.
6.All models are supplied with 2" vent connections. When the pipe must be increased to 3" diameter, the transition from 2" to 3" must be done as close to the furnace as possible. For upflow models, the transition from 2" to 3" should be done immediately above the furnace. For downflow or horizontal models, the transition from 2" to 3" pipe should be done immediately after the drain tee or drain elbow.
7.In Canada, vents shall be certified to ULC S636, Standard for Type BH Gas Venting Systems. IPEX System 636 PVC is certified to this standard.
8.In Canada, the first three feet (900 mm) of the vent must be readily accessible for inspection.
TABLE 8: Maximum Equivalent Pipe Length
Model Input | | | Pipe Size | | Maximum |
| | | Equivalent |
BTUH (kW) | | Inches (cm) | |
| | length feet (m) |
| | | | | |
| | | | | | |
40,000 (11.7) | | | 2 (5.1) | | 65 (19.8) |
40,000 (11.7) | | | 3 (7.6) | | 90 (27.4) |
60,000 (17.6) | | | 2 (5.1) | | 65 (19.8) |
60,000 (17.6) | | | 3 (7.6) | | 90 (27.4) |
80,000 (23.4) | | | 2 (5.1) | | 65 (19.8) |
80,000 (23.4) | | | 3 (7.6) | | 90 (27.4) |
100,000 (29.3) | | | 2 (5.1) | | 30 (9.2) |
100,000 (29.3) | | | 3 (7.6) | | 85 (25.9) |
120,000 (29.3) | | | 3 (7.6) | | 60 (18.3) |
TABLE 9: Equivalent Length of Fittings | | |
| | | | |
Fitting | | | | Equivalent Length |
| | | | |
2" 90º sweep elbow | | | | 5 feet of 2" pipe |
2" 45º sweep elbow | | | | 2-1/2 feet of 2" pipe |
2" 90º standard elbow | | | | 10 feet of 2" pipe |
2" 45º standard elbow | | | | 5 feet of 2" pipe |
3" 90º sweep elbow | | | | 5 feet of 3" pipe |
3" 45º sweep elbow | | | | 2-1/2 feet of 3" pipe |
3" 90º standard elbow | | | | 10 feet of 3" pipe |
3" 45º standard elbow | | | | 5 feet of 3" pipe |
2" corrugated connector | | | 10 feet of 2" pipe |
3" corrugated connector | | | 10 feet of 3" pipe |
Example:
An 80,000 BTUH furnace requires 32 feet of pipe and four 90º elbows. Using 2" pipe and standard elbows, the total equivalent length will be:
32 feet of 2" pipe = | 32 equivalent feet |
4 - 90º standard 2" elbows = (4x10) = | 40 equivalent feet |
Total = | 72 equivalent feet of 2" pipe |
This exceeds the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus not acceptable.
By using sweep elbows, the total equivalent length will be:
32 feet of 2" pipe = | 32 equivalent feet |
4 - 90º standard 2" elbows = (4x5) = | 20 equivalent feet |
Total = | 52 equivalent feet of 2" pipe |
This is less than the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus acceptable.
Alternatively, using 3" pipe and standard elbows, the total equivalent length will be:
32 feet of 3" pipe = | 32 equivalent feet |
4 - 90º standard 2" elbows = (4x5) = | 40 equivalent feet |
Total = | 72 equivalent feet of 3" pipe |
This is less than the 90 foot maximum equivalent length of 3" pipe allowed for that model and is thus acceptable.