York GY9S*DH, GM9S*DH, GF9S*DH Vertical Vent Applications Termination, Venting Multiple Units

Page 19

268890-UIM-B-0607

12” MINIMUM BELOW OVERHANG

12” MINIMUM

SEPARATION

BETWEEN BOTTOM

OF COMBUSTION

AIR PIPE AND

BOTTOM OF VENT

 

 

MAINTAIN 12”

 

 

MINIMUM CLEARANCE

 

 

ABOVE HIGHEST

 

 

ANTICIPATED SNOW

 

 

LEVEL OR GRADE,

VENT DRAIN

 

WHICHEVER IS

 

HIGHER

 

 

FIGURE 22: Crawl Space Termination Configuration - 2Pipe

VERTICAL VENT APPLICATIONS AND

TERMINATION

Roof mounted vertical terminals may be field fabricated. Standard PVC/ SRD fittings may be used. If installing a vertical venting system through any unconditioned space such as an attic or crawl space it must be insulated.

1.Observe all clearances listed in vent clearances in these instruc- tions.

2.Termination should be positioned where vent vapors are not objec- tionable.

3.Termination should be located where it will not be affected by wind gusts, light snow, or allow recirculation of flue gases.

4.Termination should be located where it cannot be damaged, plugged or restricted by tree limbs, leaves and branches.

5.Horizontal portions of the vent system must slope upwards and be supported to prevent sagging. The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft. (1.22 m).

VENTING MULTIPLE UNITS

Only the sealed combustion system can be used for installations requir- ing more than one furnace in a structure. A separate sealed combustion air pipe and a separate vent pipe must be installed for each furnace. Do not connect more than one furnace to a combustion air pipe or a vent pipe. The combustion air and vent termination must be located as shown in Figures 23 or 24.

VENT

COMBUSTION AIR

2”

MIN.

FIGURE 23: Double Horizontal Sealed Combustion Air and Vent Termination

MIN. 6”

FIGURE 24: Double Vertical Sealed Combustion Air and Vent Termination

COMBUSTION AIR SUPPLY

All installations must comply with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest edi- tions.

This furnace is certified to be installed with one of three possible com- bustion air intake configurations.

1.OUTDOOR COMBUSTION AIR: This is a sealed combustion air configuration where the combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in the same atmospheric zone as the vent. This type of installation is approved on all models. Refer to Figures 25 & 27.

2.AMBIENT COMBUSTION AIR: Combustion air is supplied from the area surrounding the furnace through the combustion air pipe in the furnace casing. The combustion air and the vent pipes are not terminated in the same atmospheric zone. Refer to Figures 19 & 26 for vent terminations. Refer to “AMBIENT COMBUSTION AIR SUPPLY” and “VENT AND SUPPLY OUTSIDE AIR SAFETY CHECK PROCEDURE” for proper installation.

3.VENTILATED COMBUSTION AIR: Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated attic or crawl space. The combustion air and the vent pipes are not termi- nated in the same atmospheric zone. Refer to Figure 28 for crawl space and attic termination. Only the combustion air intake may terminate in the attic. The vent must terminate outside.

Outdoor Combustion Air

Combustion Air Intake/Vent Connections

This installation requires combustion air to be brought in from outdoors. This requires a properly sized pipe (shown in Figures 31, 33, or 35) that will bring air in from the outdoors to the furnace combustion air intake collar on the burner box. The second pipe (shown in Figures 31, 33 or 35) is the furnace vent pipe.

2” (5.08 cm)

VENT

CONNECTION

AIR INTAKE

FIGURE 25: Sealed Combustion Air Intake Connection and Vent Connection

Unitary Products Group

19

Image 19
Contents List of Tables Section I SafetyList of Sections List of FiguresCombustion AIR Quality List of Contaminants Specific Safety Rules and PrecautionsSafety Requirements Ance to a 50 HZ Power Supply or a Voltage Above 130 VoltsFurnace Location and Clearances InspectionDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Ductwork General Information Floor Base and Ductwork InstallationDuctwork Installation Section II DuctworkReturn1 Rectangular2 Round2 Supply3 InputRound Duct Size Horizontal Models Horizontal Installations With a Cooling Coil CabinetHorizontal Installations Without a Cooling Coil Cabinet Downflow Air Conditioning Coil CabinetSection III Filters Filter InstallationCFM Horizontal Application Attic InstallationSuspended Furnace / Crawl Space Installation Downflow FiltersSection IV GAS Piping Electrical Power Connections Section V Electrical PowerAfue Supply Voltage Connections LOW Voltage Control Wiring ConnectionsAC1 Section VI Twinning and Staging Section VII Combustion AIR and Vent System Combustion AIR and Vent SafetyStaging Model Input Pipe Size Maximum Combustion AIR/VENT Pipe SizingFurnace Vent Connection Sizes Combustion AIR and Vent Piping AssemblyElbow Dimension Combustion AIR / Vent ClearancesHome Layout Vent ClearancesHorizontal Vent Applications and Termination Downflow Vent AssemblyHorizontal Vent Assembly Vent SystemOutdoor Combustion Air Vertical Vent Applications TerminationVenting Multiple Units Combustion AIR SupplyBtuh Ambient Combustion Air SupplyCombustion Air Source From Outdoors Dampers, Louvers and Grilles Canada OnlyVentilated Combustion Air Vent and Supply Outside Air Safety Check ProcedureVentilated Combustion Air Termination Condensate Drain Hose Part Numbers Section Viii Condensate PipingCondensate Drain Condensate Drain Trap and Drain Freeze ProtectionHorizontal Left Air Flow Inducer Low Refer to Figures 31 Hose #5 Hose #1Hose #9 Hose #4 Hose #6 Horizontal Right Air Flow Inducer High Refer to Figures Unitary Products Group HOSE#1 Hose #2 Barbed TEE Hose #4 Hose #7 Hose #9 Section X START-UP Adjustments Section IX Safety ControlsCalculating the Furnace Input Natural GAS Ignition System SequenceUSA use the following formula to calculate the furnace input Reading the gas pressure with the burner box cover in place Adjustment of Manifold GAS PressureInlet GAS Pressure Range Nominal Manifold PressureWith Burner BOX Cover Removed Adjustment of Temperature RiseAdjustment of FAN Control Settings With Burner BOX Cover in PlaceIgnition Control Furnace Control DiagnosticsDiagnostic Fault Code Storage and Retrieval Slow Green Flash Normal operationPleated Filter PerformanceModels Airflow Range Minimum Filter Type Opening Size DisposableApplying Filter Pressure Drop to Determine System Airflow Field Installed Accessories NON-ELECTRICALModel no Description Used with Section XI Wiring Diagram Unitary 5005 Norman Product York Group Drive 73069

GF9S*DH, GY9S*DH, GM9S*DH specifications

The York GM9S*DH, GF9S*DH, and GY9S*DH series air conditioning systems are known for their robust performance, reliability, and energy efficiency. These models are well-suited for both residential and light commercial applications, making them versatile options for a range of users.

One of the standout features of these systems is their high efficiency. The GM9S*DH is equipped with advanced heating and cooling technologies that allow it to achieve excellent SEER (Seasonal Energy Efficiency Ratio) ratings. This translates to lower energy consumption and reduced utility bills for homeowners and business operators alike. The GF9S*DH model further enhances this efficiency by incorporating variable-speed blowers that adjust airflow based on specific needs, ensuring that the system operates only as necessary.

Reliability is another key characteristic of the York GM9S*DH, GF9S*DH, and GY9S*DH series. These models are engineered with durable components and rigorous performance testing, which contributes to their long lifespan and minimizes the need for repairs. Moreover, they come with robust warranties that provide peace of mind for consumers.

In terms of technology, these units utilize a smart thermostat feature that allows for precise temperature control and programmable settings. This feature not only enhances comfort but also contributes to energy savings by allowing users to set optimal cooling or heating schedules. The systems are also designed with quiet operation in mind, employing sound-dampening features that minimize noise levels, which is particularly beneficial for residential installations.

The installation of the York GM9S*DH, GF9S*DH, and GY9S*DH systems is straightforward, offering flexibility in placement and integration with various home or office setups. Their compact design allows them to fit seamlessly into different environments without compromising on performance.

Additionally, the systems are equipped with advanced filtration options that improve indoor air quality by capturing allergens and pollutants. This is particularly beneficial for families with children or members who suffer from allergies.

Overall, the York GM9S*DH, GF9S*DH, and GY9S*DH series provide exceptional performance, energy efficiency, and reliability, making them an ideal choice for maintaining a comfortable indoor environment. With their cutting-edge technologies and user-friendly features, these systems represent an excellent investment for anyone looking to enhance their heating and cooling experience.