York GM9S*DH Vent System, Horizontal Vent Applications and Termination, Downflow Vent Assembly

Page 18

268890-UIM-B-0607

VENT SYSTEM

This furnace is certified to be installed with one of two possible vent configurations.

1.Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.

2.Vertical vent system. This vent system can be installed completely vertical or a combination of horizontal, vertical, or offset using elbows.

HORIZONTAL VENT APPLICATIONS AND TERMINATION

When selecting the location for a horizontal combustion air / vent termi- nation, the following should be considered:

1.Observe all clearances listed in vent clearances in these instruc- tions.

2.Termination should be positioned where vent vapors will not dam- age plants or shrubs or air conditioning equipment.

3.Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue gases.

4.Termination should be located where it will not be damaged or exposed to flying stones, balls, etc.

5.Termination should be positioned where vent vapors are not objec- tionable.

6.Horizontal portions of the vent system must slope upwards and be supported to prevent sagging. The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft. (1.22 m).

7.Sealed combustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone. Refer to Figures 19, 20, & 21.

DOWNFLOW VENT ASSEMBLY

1.Place the 2” (5.08 cm) 45° PVC street elbow on the vent connec- tion shown in Figure 18.

2.Place the 2” (5.08 cm) PVC WYE (“Y”) assembly on the 2” (5.08 cm) 45° PVC street elbow as shown in Figure 18.

3.Locate the rubber condensate hose in front of the blower access panel.

4.Slide the hose through the hole in the top cover, and insert the hose on to the barbed fitting on the bottom of the 2” (5.08 cm) PVC WYE (“Y”) assembly as shown in Figure 18.

RETURN

 

2” (5.08 cm)

 

AIR

 

VENT PIPE

 

 

 

 

RETURN

2” PVC

 

2” PVC

AIR

 

WYE

 

45°

 

 

 

 

 

STELL

 

FURNACE

HORIZONTAL LEFT

 

 

 

 

 

 

VENT PIPE

 

 

 

DOWNFLOW RETURN

AIR

BARBED

FITTING

HORIZONTAL RIGHT

FIGURE 18: Downflow/Horizontal Vent Assembly

HORIZONTAL VENT ASSEMBLY

Horizontal Left Vent Assembly

1.Place the 2” (5.08 cm) 45° PVC street elbow on the vent connec- tion shown in Figure 18.

2.Place the 2” (5.08 cm) PVC WYE (“Y”) assembly on the 2” (5.08 cm) 45° PVC street elbow as shown in Figure 18.

3.Refer to the “DOWNFLOW/HORIZONTAL CONDENSATE INTER- NAL DRAIN CONFIGURATIONS” for futher details.

Horizontal Right Vent Assembly

1.Place the 2” (5.08 cm) 45° PVC street elbow on the vent connec- tion shown in Figure 18.

2.Place the 2” (5.08 cm) PVC WYE (“Y”) assembly on the 2” (5.08 cm) 45° PVC street elbow as shown in Figure 18.

3.Refer to the “DOWNFLOW/HORIZONTAL CONDENSATE INTER- NAL DRAIN CONFIGURATIONS” for futher details.

MAINTAIN 12” MINIMUM CLEARANCE

ABOVE HIGHEST ANTICIPATED SNOW

LEVEL. MAXIMUM 24” ABOVE ROOF.

12” MIN.

12” MIN.

FIGURE 19: Termination Configuration - 1 Pipe

12” VERTICAL SEPARATION

 

BETWEEN COMBUSTION AIR

12” MINIMUM

AND VENT

BELOW

MAINTAIN 12”

OVERHANG

MINIMUM

12” MINIMUM

CLEARANCE

ABOVE HIGHEST

SEPARATION

ANTICIPATED

 

BETWEEN BOTTOM

SNOW LEVEL.

 

OF COMBUSTION

 

 

AIR PIPE AND

 

 

BOTTOM OF VENT

 

 

MAINTAIN 12”

 

 

MINIMUM CLEARANCE

 

 

ABOVE HIGHEST

 

 

ANTICIPATED SNOW

 

 

LEVEL OR GRADE,

 

 

WHICHEVER IS

 

 

HIGHER

FIGURE 20: Termination Configuration - 2 Pipe

12” MINIMUM SEPARATION BETWEEN BOTTOMOF COMBUSTION AIR PIPE AND TOP OF VENT. MAINTAIN 12” MIN. CLEARANCE ABOVE

HIGHEST ANTICIPATED SNOW LEVEL.

12” MIN.

12” MIN.

FIGURE 21: Termination Configuration - 2 Pipe Horizontal

18

Unitary Products Group

Image 18
Contents List of Figures Section I SafetyList of Sections List of TablesAnce to a 50 HZ Power Supply or a Voltage Above 130 Volts Specific Safety Rules and PrecautionsSafety Requirements Combustion AIR Quality List of ContaminantsInspection Furnace Location and ClearancesDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Section II Ductwork Floor Base and Ductwork InstallationDuctwork Installation Ductwork General InformationInput Return1 Rectangular2 Round2 Supply3Round Duct Size Downflow Air Conditioning Coil Cabinet Horizontal Installations With a Cooling Coil CabinetHorizontal Installations Without a Cooling Coil Cabinet Horizontal ModelsFilter Installation Section III FiltersCFM Downflow Filters Attic InstallationSuspended Furnace / Crawl Space Installation Horizontal ApplicationSection IV GAS Piping Section V Electrical Power Electrical Power ConnectionsAfue LOW Voltage Control Wiring Connections Supply Voltage ConnectionsAC1 Section VI Twinning and Staging Combustion AIR and Vent Safety Section VII Combustion AIR and Vent SystemStaging Combustion AIR/VENT Pipe Sizing Model Input Pipe Size MaximumCombustion AIR / Vent Clearances Combustion AIR and Vent Piping AssemblyElbow Dimension Furnace Vent Connection SizesVent Clearances Home LayoutVent System Downflow Vent AssemblyHorizontal Vent Assembly Horizontal Vent Applications and TerminationCombustion AIR Supply Vertical Vent Applications TerminationVenting Multiple Units Outdoor Combustion AirDampers, Louvers and Grilles Canada Only Ambient Combustion Air SupplyCombustion Air Source From Outdoors BtuhVent and Supply Outside Air Safety Check Procedure Ventilated Combustion AirVentilated Combustion Air Termination Condensate Drain Trap and Drain Freeze Protection Section Viii Condensate PipingCondensate Drain Condensate Drain Hose Part NumbersHose #5 Hose #1 Horizontal Left Air Flow Inducer Low Refer to Figures 31Hose #9 Hose #4 Hose #6 Horizontal Right Air Flow Inducer High Refer to Figures Unitary Products Group HOSE#1 Hose #2 Barbed TEE Hose #4 Hose #7 Hose #9 Section IX Safety Controls Section X START-UP AdjustmentsIgnition System Sequence Calculating the Furnace Input Natural GASUSA use the following formula to calculate the furnace input Nominal Manifold Pressure Adjustment of Manifold GAS PressureInlet GAS Pressure Range Reading the gas pressure with the burner box cover in placeWith Burner BOX Cover in Place Adjustment of Temperature RiseAdjustment of FAN Control Settings With Burner BOX Cover RemovedSlow Green Flash Normal operation Furnace Control DiagnosticsDiagnostic Fault Code Storage and Retrieval Ignition ControlAirflow Range Minimum Filter Type Opening Size Disposable Filter PerformanceModels PleatedField Installed Accessories NON-ELECTRICAL Applying Filter Pressure Drop to Determine System AirflowModel no Description Used with Section XI Wiring Diagram Unitary 5005 Norman Product York Group Drive 73069

GF9S*DH, GY9S*DH, GM9S*DH specifications

The York GM9S*DH, GF9S*DH, and GY9S*DH series air conditioning systems are known for their robust performance, reliability, and energy efficiency. These models are well-suited for both residential and light commercial applications, making them versatile options for a range of users.

One of the standout features of these systems is their high efficiency. The GM9S*DH is equipped with advanced heating and cooling technologies that allow it to achieve excellent SEER (Seasonal Energy Efficiency Ratio) ratings. This translates to lower energy consumption and reduced utility bills for homeowners and business operators alike. The GF9S*DH model further enhances this efficiency by incorporating variable-speed blowers that adjust airflow based on specific needs, ensuring that the system operates only as necessary.

Reliability is another key characteristic of the York GM9S*DH, GF9S*DH, and GY9S*DH series. These models are engineered with durable components and rigorous performance testing, which contributes to their long lifespan and minimizes the need for repairs. Moreover, they come with robust warranties that provide peace of mind for consumers.

In terms of technology, these units utilize a smart thermostat feature that allows for precise temperature control and programmable settings. This feature not only enhances comfort but also contributes to energy savings by allowing users to set optimal cooling or heating schedules. The systems are also designed with quiet operation in mind, employing sound-dampening features that minimize noise levels, which is particularly beneficial for residential installations.

The installation of the York GM9S*DH, GF9S*DH, and GY9S*DH systems is straightforward, offering flexibility in placement and integration with various home or office setups. Their compact design allows them to fit seamlessly into different environments without compromising on performance.

Additionally, the systems are equipped with advanced filtration options that improve indoor air quality by capturing allergens and pollutants. This is particularly beneficial for families with children or members who suffer from allergies.

Overall, the York GM9S*DH, GF9S*DH, and GY9S*DH series provide exceptional performance, energy efficiency, and reliability, making them an ideal choice for maintaining a comfortable indoor environment. With their cutting-edge technologies and user-friendly features, these systems represent an excellent investment for anyone looking to enhance their heating and cooling experience.