| | 262292-YTG-B-0107 |
| | |
| FACTORY-INSTALLED OPTIONS | A ‘VFD-ready’ option provides the provisions for a cus- |
| • SINGLE INPUT ELECTRONIC ENTHALPY | tomer-installed drive. The unit comes with a mounting |
| bracket installed in the Blower Access compartment which |
| ECONOMIZERS - Includes a slide-in / plug-in damper | may accommodate other vendor’s drives depending on |
| assembly with fully modulating spring-return motor | their size. In order to utilize the unit’s mounting bracket, |
| actuator capable of introducing up to 100% outdoor air | the maximum recommended drive dimensions are as fol- |
| with nominal 1% leakage type dampers. | lows: |
| The enthalpy system contains one sensor that monitors | For 5-hp motor applications ........................13” H x 6” W x 7” D |
| the outdoor air and determines when the air is cool |
| For 7.5 thru 15-hp motor applications .........13” H x 8” W x 8” D |
| enough and dry enough to provide free cooling. |
| The rainhood is painted to match the basic unit and must | If the customer-installed drive will not fit in the allotted |
| be field-assembled before installing. | space, then it will have to be mounted within a NEMA-4 |
| • POWER EXHAUST - Our single economizer options are | enclosure for outside installation or inside the building on |
| a perpendicular wall not subjected to excessive tempera- |
| available with power exhaust. Whenever the outdoor air |
| ture, vibration, humidity, dust, corrosive gas, explosive |
| intake dampers are opened for free cooling, the exhaust |
| gas, etc. |
| fan will be energized to prevent the conditioned space |
| |
| from being over-pressurized during economizer operation. | A terminal block located in the control box is provided for |
| The exhaust fan, motor and controls are installed and | field connection of the VFD controls. |
| wired at the factory. The rain hood must be assembled | • HOT GAS BYPASS - To allow for low cooling load opera- |
| and installed in the field. |
| tion, a direct-acting pressure-modulating bypass control |
| • MOTORIZED OUTDOOR AIR INTAKE DAMPER - |
| valve installed on the system #1 discharge line is used to |
| Includes a slide-in / plug-in damper assembly with a 2- |
| divert high temperature, high pressure refrigerant around |
| position, spring return motor actuator which opens to a |
| the TXV in order to maintain a desired minimum evaporator |
| pre-set position whenever the supply air blower is |
| pressure. HGBP is standard on all units with VAV and |
| operating and will drive fully closed when the blower unit |
| optional with CV units. |
| shuts down. |
| • FILTER OPTIONS - Standard units are shipped with 2” |
| The rain hood is painted to match the basic unit and must |
| throw-away filters installed. 2” pleated and 4” pleated |
| be field assembled before installing. |
| filters are offered as a factory installed option. |
| • PHENOLIC COATED EVAPORATOR, REHEAT, AND |
| • CONVENIENCE OUTLET - This 110 volt outlet can be |
| CONDENSER COILS - Special coating process that |
| “powered” by the unit with a stepdown transformer or you |
| utilizes Technicoat 10-1" processes. Coating is applied by |
| may order the unit with a “non-powered” convenience |
| total immersion of the complete coil for maximum |
| outlet that can be wired in the field. |
| protection. |
| • DISCONNECT SWITCH - For gas heat units and cooling |
| • ELECTRIC HEATERS wired for single point power |
| units with electric heat, a HACR breaker sized to the unit |
| supply. These nickel chromium heater elements are |
| is provided. For cooling only units, a switch sized to the |
| provided with limit and automatic reset capability to |
| largest electric heat available for the particular unit is |
| prevent operation at excessive temperatures. |
| provided. Factory installed option only. |
| • VARIABLE AIR VOLUME (VAV) - A factory-installed |
| • DOUBLE WALL CONSTRUCTION - Optional double wall |
| variable frequency drive (VFD), mounted in the Blower |
| construction is available to provide smooth inner surfaces |
| Access compartment, is used to control the speed of the |
| for easy and effective cleaning to reduce risk of dirt and |
| indoor blower motor in order to maintain a constant static |
| bacterial accumulation. Fiberglass insulation is |
| pressure in the supply duct. A pressure transducer and |
| sandwiched between heavy gauge steel sheets to form a |
| VAV control board are mounted inside the control box. |
| durable, rigid casing to withstand higher working |
| The drive comes completely wired and pre-programmed |
| pressures and impact forces. The heavy-duty construction |
| from the factory. |
| provides excellent acoustic and thermal insulation and |
| An optional, factory-installed manual bypass switch avail- |
| eliminates erosion of insulation material and |
| able with factory-installed VFD can be found in the Blower | contamination of the air stream. |
| Motor Access compartment. The switch can be used to | • BAS - Building Automation System Controls |
| either route power to the VFD for modulating control of the |
| (available on two-system cooling product only). |
| blower motor, to bypass the drive and operate the motor |
| Simplicity® INTELLI-Comfort™ CONTROL - The York® |
| at full speed, or to power the drive (and not the motor) for |
| diagnostic purposes. | Simplicity® INTELLI-Comfort™ control is factory installed. |
| It includes a supply air sensor, a return air sensor, and an |
| Due to space limitations, VAV is not available with any of |
| outside air sensor. There are provisions for a field installed |
| the factory-installed BAS options described below, but is | dirty filter indicator switch, an air-proving switch, an Out- |
| available with ‘BAS-ready’ models. Terminal blocks are | side Air Humidity sensor, a Return Air Humidity sensor, an |
| provided in the control box for field wiring of the customer- | Inside IAQ sensor, and an Outside Air IAQ sensor. Con- |
| installed BAS. | |