York R-410A manual Factory Installed Options

Page 5

528194-YTG-F-1210

sure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

Reliable – From the beginning – All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term – All Predator® units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.

Flexible Placement – All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the correct tonnage size and heating option after the internal loads have been determined.

To further simplify planning and installation, Predator® ZF cabinets are designed to fit your roof. With the optional roof curb, the unit ductwork is designed to fit around 24” on-center joists or between 48” on-center joists.

The drain pan can be rotated to drain to either the front or the rear of the unit. Additionally, the drain pan can be fitted to drain through the roof curb. As it is sometimes difficult to have a level installation, the drain pan features a generous slope to ensure proper drainage.

Full Perimeter Base Rails – The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer forklift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.

Easy Installation – Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor. All units are shipped with 2” throw-away filters installed.

Wide Range of Indoor Airflows – All indoor fan motors are belt-drive type providing maximum flexibility to handle most airflow requirements. For high static applications, factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at a minimum of 1.5” ESP.

A variable air volume (VAV) option using a variable frequency drive is available on 6-1/2 through 12-1/2 ton, ZF models for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure while a VAV control board provides a speed reference signal to the VFD to control the output of the indoor blower motor.

Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel and stainless steel tubular heat exchangers carry a 10- year warranty.

Factory Installed Options

YORK® offers several equipment options factory installed, for the Predator® line.

Optional Factory Installed Economizers - Predator units offer a variety of optional factory installed economizers with low leak dampers. The outdoor air enthalpy sensor enables economizer operation if the outdoor enthalpy is less than the setpoint of the economizer logic module. See economizer options section to determine the correct economizer for your application.

Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Provided). The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional CO2 input for demand ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.

Horizontal Economizer - (Without barometric relief) - All features of the downflow economizer exist except you must order the duct mount barometric relief separately.

You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.

BAS Ready Economizer -(With barometric relief) - The economizer is provided with an actuator that requires a 2-10V DC input from an external source (i.e., field installed building automation system controller). Power exhaust options are available. The economizer is 2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” pleated filters. BAS Ready actuators have an adjustable auxiliary end-switch for optional power exhaust control.

For units with optional VAV or Simplicity® Intelli- Comfort™ control, a factory-installed, dry bulb sensor determines if outdoor air temperature is low enough to provide free-cooling operation. (Field-installed humidity sensors for either outdoor air or outdoor & return air streams are available for single enthalpy and differential enthalpy configurations respectively).

Johnson Controls Unitary Products

5

Image 5
Contents Description Technical Guide R-410A ZF SeriesComponent Location Table of ContentsTon York Model Number Nomenclature NomenclatureStandard Features Features and BenefitsFactory Installed Options YTG-F-1210 Control Options Field Installed AccessoriesYTG-F-1210 Field Installed Acessories Non-Electrical AccessoriesField Installed Acessories Electric Heat Description Where UsedField Installed Acessories Fresh Air Guide SpecificationsField Installed Acessories Controls Field Installed Acessories ElectricalUnit Cabinet GAS Heating Section if Equipped Other PRE-ENGINEERED Accessories Available ZF078-150 Physical Data Physical DataCondenser FAN Data ZF078 ZF090 ZF102 ZF120 ZF150Belt Drive Evap FAN Data FiltersSize Unit Limitations ZF078-150 Unit LimitationsUnit Voltage Applied Voltage MinZF078 6.5 Ton Capacity PerformanceZF078-150 Cooling Capacities 115F ZF090 7.5 Ton ZF090 7.5 Ton ZF102 8.5 Ton ZF102 8.5 Ton ZF120 10 Ton ZF120 10 Ton ZF150 12.5 Ton 115F 125F ZF078-150 Side Duct Application Airflow PerformanceZF078 6.5 Ton Side Duct ZF090 7.5 Ton Side DuctAvailable External Static Pressure IWG1 ZF120 10 Ton Side DuctZF150 12.5 Ton Side Duct ZF078 6.5 Ton Bottom Duct ZF078-150 Bottom Duct ApplicationZF090 7.5 Ton Bottom Duct ZF102 8.5 Ton Bottom DuctZF150 12.5 Ton Bottom Duct ZF120 10 Ton Bottom DuctCFM RPM SelectionAdditional Static Resistance Airflow Performance Air Temperature ºF Altitude/Temperature Correction FactorsFactor CorrectionPower Exhaust Specifications Indoor Blower SpecificationsGas Heat Minimum Supply Air Electric Heat Minimum Supply AirOutdoor Sound Power Levels ZF078-150 Indoor Sound Power LevelsSound Performance Electric Heat MultipliersElectrical Data ZF078-150 Standard Motor Without Powered Convenience OutletZF078-150 Standard Motor Without Powered Convenience Outlet ZF078-150 Hi Static Motor Without Powered Convenience Outlet ZF078-150 Hi Static Motor Without Powered Convenience Outlet ZF078-150 Standard Motor With Powered Convenience Outlet ZF078-150 Standard Motor With Powered Convenience Outlet ZF078-150 Hi Static Motor With Powered Convenience Outlet ZF078-150 Hi Static Motor With Powered Convenience Outlet ZF078-150 Typical Wiring Diagrams Typical Wiring DiagramsYTG-F-1210 YTG-F-1210 YTG-F-1210 YTG-F-1210 YTG-F-1210 Typical ZF078-150 Factory Installed VFD Option YTG-F-1210 YTG-F-1210 YTG-F-1210 YTG-F-1210 YTG-F-1210 Typical ZF078-150 VFD Ready Unit Option Unit 4 Point Load Weight Unit 6 Point Load Weight Weights and DimensionsZF078-150 Unit Weights ZF078-150 Unit Accessory Weights ZF078-150 Unit DimensionsZF078 Shipping OperatingZF150 ZF078-150 Unit Physical DimensionsDimension ZF078-150 Unit Clearances Detail BDetail a ZF078-150 Unit Bottom Duct Openin TOP ViewFront ZF078-150 Unit Left Duct Opening ZF Side Duct DimensionsZF150 Unit Side Duct Openings ZF078-150 Transition Roof Curb ZF078-150 Unit Accessory DimensionsZF078-150 Roof Curb ZF078-150 Economizer Assembly Field Installed Downflow Economizer W/Power Exhaust Factory Installed Downflow EconomizerEconomizer Options Economizer UsageSlab Economizer Downflow W/Power Exhaust Field Installed Horizontal Economizer W/Power ExhaustJohnson Controls Unitary Products York Drive Norman, OK Slab Economizer End Return W/Power Exhaust
Related manuals
Manual 24 pages 22.74 Kb Manual 104 pages 7.39 Kb Manual 128 pages 30.42 Kb Manual 36 pages 24.83 Kb

R-410A specifications

York R-410A is a widely recognized and highly efficient refrigerant used in modern air conditioning systems. Developed as an environmentally friendly alternative to R-22, R-410A has gained popularity in the HVAC industry due to its numerous advantageous features and characteristics.

One of the main features of York R-410A is its ability to provide superior cooling performance. This refrigerant operates efficiently at both high and low temperatures, allowing systems using it to maintain optimal indoor climates even during extreme weather conditions. Its high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER) ratings make it a preferred choice for energy-conscious consumers, resulting in lower energy bills and a reduced carbon footprint.

Technologically, York R-410A systems feature advanced compressor designs that enhance their overall reliability and performance. These compressors are often equipped with variable-speed technology, enabling them to adjust their output to match the cooling demands of the space. This not only improves comfort levels but also leads to efficient energy consumption, reducing wear and tear on the equipment over time.

Another significant characteristic of York R-410A is its non-ozone-depleting properties. Unlike its predecessor R-22, which is being phased out due to its damaging effects on the ozone layer, R-410A is designed to minimize environmental impact. Its lower global warming potential (GWP) further underscores its role in promoting sustainability within the HVAC sector.

Furthermore, York R-410A systems are engineered with enhanced safety features. The refrigerant is non-toxic and non-flammable, which makes it safer for use in both residential and commercial applications. Additionally, its high thermal stability reduces the risk of breakdown or leakage, contributing to longer system lifespans and lower maintenance costs.

In conclusion, York R-410A stands out as a cutting-edge refrigerant that combines efficiency, safety, and environmental responsibility. With its advanced technologies and remarkable characteristics, it meets the demands of modern air conditioning requirements while paving the way for a sustainable future in HVAC systems. Adopting York R-410A not only benefits individual users through improved comfort and lower energy bills but also plays a vital role in protecting our planet's ozone layer and mitigating climate change.