GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of aluminized steel and shall be designed with induced draft com- bustion with post purge logic, energy saving direct spark igni- tion, and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 ºF. Burners shall be of the in-shot type, con- structed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through either the side or bot- tom, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol- lowing minimum protection:
a.Primary and auxiliary high-temperature limit switches.
b.Induced draft pressure sensor.
c.Flame roll out switch (manual reset).
d.Flame proving controls.
e.All two stage units shall have two independent stages of capacity (60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements, shall be provided in a range of 9 thru 54 KW, offering two states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heat- ing Section assembly shall slide out of the unit for easy mainte- nance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years, Parts – 1 Year
intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed- air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief or power exhaust.
•MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and return air dampers that are interlocked and positioned by a 2-position,spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
•ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.
•Variable Air Volume (VAV) – The VAV option using a varible frequency drive (VFD) shall be available on 6-1/2 through 12-1/2 ton, models for applications requiring a constant supply-duct static pressure. Unts equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. The VAV control board shall operate using factory-installed Supply Air, Return Air and Outside Air Temperature Sensors with a nominal resistance of 10,000 Ohms. Units equipped with VFD’s shall have factory-installed manual bypass as an option.