York R-410A Unit Operating Characteristics, Electrical Requirements, Standard Limited Warranties

Page 11

251934-YTG-G-0708

Unit Operating Characteristics

Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0° F. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

Electrical Requirements

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

Standard Limited Warranties

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

Optional Outdoor Air (Shall be made available by either/or):

Electronic Enthalpy Automatic Economizer - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating,spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.

Motorized Outdoor Air Dampers - Outdoor and return air dampers that are interlocked and positioned by a 2- position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed

position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

Other Pre-engineered Accessories Available

Roof Curb - 14" high, full perimeter curb with wood nailer (shipped knocked-down).

100% Barometric Relief Damper - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.

Propane Conversion Kit - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.

High Altitude - Natural Gas - Contains orifices required for applications between 2000 and 6000 feet altitude.

High Altitude - Propane Gas - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.

Burglar Bars - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings.

Side Duct Flange - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust.

High Static Drive - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance.

Wood Skid - Allows unit to be handled with 90" forks.

Economizer/motorized Damper Rain Hood (ZJ/ZR/ZFN/E/C300 only) - Contains all hood panels and the hardware for assembling.

Anti-Recycle Timer - Assures 5-minute off time between compressor cycles.

Low Ambient Kit - Provides unit cooling operation down to 0 °F.

Coil Guard Kit - Guard for cooling coil.

OTHER FACTORY INSTALLED OPTIONS

Power Exhaust Option - To work in conjunction with economizers.

Stainless Steel Heat Exchanger

Stainless Steel Drain Pan

Technicoat Phenolic Coated Condenser And Evaporator Coil

Electronic Single Enthalpy Economizer

Dirty Filter Switch

Double Wall

Phase Monitor

Coil Guard

Powered GFI Convenience Outlet

Non-powered GFI Convenience Outlet

Bas Controls - Simplicity® Intelli-Comfort™, CPC,

JOHNSON, HONEYWELL, NOVAR, YORK COMMERCIAL COMFORT SYSTEM (YCCS)

Johnson Controls Unitary Products

11

Image 11
Contents Description ZJ/ZR ShownTable of Contents ZJ shown Component LocationTon Sunline Magnum Model Number Nomenclature NomenclatureBalanced Heating Features and BenefitsStandard Features Factory Installed Options Control Options General Guide SpecificationsField Installed Accessories Unit Cabinet Indoor Evaporator Fan AssemblyDescription Gas Heating Section ZJ/ZR/ZF***N Models Outdoor Condenser Fan AssemblyRefrigerant Components Unit ControlsStandard Limited Warranties Unit Operating CharacteristicsOther Pre-engineered Accessories Available Electrical RequirementsAlternate Mode Reheat Mode Sequence Of OperationNormal Mode Reheat Controls Part Reheat Control BoardRHB ZJ180-300 Physical Data Physical DataFilters ZR180-300 Physical Data No. speeds Number of motors Motor HP each AFUE% ZF180-300 Physical DataMin ZJ/ZR/ZF180-300 Unit LimitationsZJ180 15 Ton Capacity PerformanceZJ180-300 Cooling Capacities 115F 125F ZJ210 17.5 Ton ZJ210 17.5 Ton ZJ240 20 Ton ZJ240 20 Ton ZJ300 25 Ton ZJ300 25 Ton ZR180 15 Ton ZR180-300 Cooling and Reheat CapacitiesZR180 15 Ton 35F 45F ZR180 15 Ton Alternate Reheat ModeSensible Capacity MBh ZR240 20 Ton 115F 125F ZR240 20 Ton Alternate Reheat Mode 75F 85F ZR300 25 Ton 115F 125F ZR300 25 Ton Alternate Reheat Mode 75F 85F ZF180 15 Ton ZF180-300 Cooling Capacities115F 125F ZF210 17.5 Ton ZF210 17.5 Ton ZF240 20 Ton ZF240 20 Ton ZF300 25 Ton ZF300 25 Ton ZJ210 17.5 Ton Side Duct Airflow PerformanceZJ180-300 Side Duct Application ZJ180 15 Ton Side DuctZJ240 20 Ton Side Duct ZJ300 25 Ton Side Duct ZJ210 17.5 Ton Bottom Duct ZJ180-300 Bottom Duct ApplicationZJ180 15 Ton Bottom Duct ZJ240 20 Ton Bottom Duct ZJ300 25 Ton Bottom Duct ZR240 20 Ton Side Duct ZR180-300 Side Duct ApplicationZR180 15 Ton Side Duct ZR300 25 Ton Side Duct ZR240 20 Ton Bottom Duct ZR180-300 Bottom Duct ApplicationZR180 15 Ton Bottom Duct ZR300 25 Ton Bottom Duct ZF210 17.5 Ton Side Duct ZF180-300 Side Duct ApplicationZF180 15 Ton Side Duct ZF240 20 Ton Side Duct ZF300 25 Ton Side Duct ZF210 17.5 Ton Bottom Duct ZF180-300 Bottom Duct ApplicationZF180 15 Ton Bottom Duct ZF240 20 Ton Bottom Duct ZF300 25 Ton Bottom Duct Additional Static Resistance RPM SelectionDrive Selection Correction Altitude/Temperature Correction FactorsAir Temperature ºF Gas Heat Minimum Supply Air FactorElectric Heat Minimum Supply Air Indoor Blower SpecificationsPower Exhaust Specifications Electric Heat Multipliers ZJ/ZR/ZF Indoor Sound Power LevelsSound Performance ZJ180 ZJ180-300 Standard Drive Without Powered Convenience OutletElectrical Data MCA Model Stages Amps ZJ180-300 Standard Drive With Powered Convenience OutletZJ180-300 Standard Drive With Powered Convenience Outlet Conv YTG-G-0708 ZJ180-300 High Static Drive With Powered Convenience Outlet ZJ180-300 High Static Drive With Powered Convenience Outlet ZJ300 Low Static Drive With Powered Convenience Outlet ZJ300 Low Static Drive Without Powered Convenience OutletZR180 ZR180-300 Standard Drive Without Powered Convenience OutletZR180-300 Standard Drive With Powered Convenience Outlet YTG-G-0708 ZR180-300 High Static Drive With Powered Convenience Outlet ZR300 Low Static Drive With Powered Convenience Outlet ZR300 Low Static Drive Without Powered Convenience OutletZF180 ZF180-300 Standard Drive Without Powered Convenience OutletPwr Max Fuse Motors ZF180-300 Standard Drive With Powered Convenience Outlet ZF180-300 Standard Drive With Powered Convenience Outlet ZF180-300 Hi Static Drive Without Powered Convenience Outlet ZF180-300 Hi Static Drive Without Powered Convenience Outlet ZF180-300 Hi Static Drive With Powered Convenience Outlet ZF180-300 Hi Static Drive With Powered Convenience Outlet ZF180-300 Low Static Drive With Powered Convenience Outlet ZJ180-300 Typical Control Diagram ZJ/ZR/ZF180-300 Wiring DiagramsOCC Terminal Block ZR180-300 Typical Control DiagramOCC ZF180-300 Typical Control DiagramZF Unit 4 Point Load Weight ZF Unit 6 Point Load Weight Weights and DimensionsZJ/ZR/ZF180-300 Unit Weights Supply Fan VFD Weights, in Lbs ZJ/ZR/ZF180-300 Unit Accessory WeightsUtilities Entry ZJ/ZR/ZF180-300 Unit DimensionsZJ/ZR Unit Dimensions Front View 48-5/8 15 Ton 52-5/8 17.5 thru 25 Ton ZF Unit Dimensions Front ViewFor side duct applications ZJ/ZR/ZF Unit Dimensions Rear ViewFor bottom duct applications ZJ/ZR/ZF180-300 Unit Clearances ZJ/ZR/ZF Unit Dimensions Rain HoodZJ/ZR/ZF180-300 Roof Curb ZJ/ZR/ZF180-300 Unit Accessory DimensionsZJ/ZR/ZF180-300 Typical Installation Johnson Controls Unitary Products York Drive Norman, OK
Related manuals
Manual 24 pages 22.74 Kb Manual 68 pages 3.65 Kb Manual 128 pages 30.42 Kb Manual 36 pages 24.83 Kb

R-410A specifications

York R-410A is a widely recognized and highly efficient refrigerant used in modern air conditioning systems. Developed as an environmentally friendly alternative to R-22, R-410A has gained popularity in the HVAC industry due to its numerous advantageous features and characteristics.

One of the main features of York R-410A is its ability to provide superior cooling performance. This refrigerant operates efficiently at both high and low temperatures, allowing systems using it to maintain optimal indoor climates even during extreme weather conditions. Its high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER) ratings make it a preferred choice for energy-conscious consumers, resulting in lower energy bills and a reduced carbon footprint.

Technologically, York R-410A systems feature advanced compressor designs that enhance their overall reliability and performance. These compressors are often equipped with variable-speed technology, enabling them to adjust their output to match the cooling demands of the space. This not only improves comfort levels but also leads to efficient energy consumption, reducing wear and tear on the equipment over time.

Another significant characteristic of York R-410A is its non-ozone-depleting properties. Unlike its predecessor R-22, which is being phased out due to its damaging effects on the ozone layer, R-410A is designed to minimize environmental impact. Its lower global warming potential (GWP) further underscores its role in promoting sustainability within the HVAC sector.

Furthermore, York R-410A systems are engineered with enhanced safety features. The refrigerant is non-toxic and non-flammable, which makes it safer for use in both residential and commercial applications. Additionally, its high thermal stability reduces the risk of breakdown or leakage, contributing to longer system lifespans and lower maintenance costs.

In conclusion, York R-410A stands out as a cutting-edge refrigerant that combines efficiency, safety, and environmental responsibility. With its advanced technologies and remarkable characteristics, it meets the demands of modern air conditioning requirements while paving the way for a sustainable future in HVAC systems. Adopting York R-410A not only benefits individual users through improved comfort and lower energy bills but also plays a vital role in protecting our planet's ozone layer and mitigating climate change.