York R-410A manual Reheat Mode Sequence Of Operation, Normal Mode, Alternate Mode

Page 12

251934-YTG-G-0708

BAS Ready Economizer (2-10 V.D.C. Actuator Without a Controller)

Hinged Filter Door Access And Tool Free Access Panels

Hinged Tool Free Blower, Blower Motor, Filter And Electrical Access Panels

High Static Drive

Low Static Drive (ZJ/ZR/ZF300 only)

2" Pleated Filters

4" Throw Away Filters

Disconnect Switch

Supply Air Smoke Detector

Return Air Smoke Detector

Reheat Mode Sequence Of Operation

The reheat control board allows the user to select two different modes of operation via a jumper connection on the board. (See Reheat Control Board.) Each mode is described below. Refer to Reheat Controls - Part 1 and Part 2 when reading this section.

“Normal” Mode

When the reheat control board (RCB) detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2 and there is not a call for cooling, it energizes the hot gas relay (HGR), which energizes the 3-way valve (SOL 3), the condenser coil valve (SOL 2), and de-energizes the reheat coil bleed valve (SOL 1). The Y1 signal is passed to the unit control board (UCB), which engages circuit # 1, resulting in circuit #1 reheat mode operation.

When the room thermostat calls for first stage cooling, with or without a call for dehumidification, the RCB senses a signal through "Y1", de-energizing the HGR, which de-energizes SOL 3 and SOL 2, and energizes SOL 1, engaging circuit # 1, resulting in circuit #1 cooling mode operation.

When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and engages circuit #1 and circuit #2 in the cooling mode.

Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification.

Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is a call for dehumidification at "HUM".

The unit will not operate in the reheat mode if there is any call for heating.

On units with economizers, the unit will not operate in the reheat mode if there is a call for cooling and the economizer is operating as first stage of cooling.

All safety devices function as previously described.

"Alternate” Mode

When the RCB detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2, and there is not a call for cooling, it energizes the HGR, which energizes the SOL 3, SOL 2, and de-energizes SOL 1. The unit then operates with circuit #1 in reheat mode and circuit #2 in cooling mode.

When the room thermostat calls for first stage cooling while there is still a call for dehumidification, no operational change is made. The call for cooling is ignored and the unit continues to operate with circuit #1 in reheat mode and circuit #2 in cooling mode.

When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and de-energizes the HGR, which de-energizes SOL 3 and SOL 2, and energizes SOL 1. Both circuits operate in the cooling mode.

Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification.

Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is still a call for dehumidification at "HUM".

The unit will not operate in the reheat mode if there is any call for heating.

All safety devices function as previously described.

12

Johnson Controls Unitary Products

Image 12
Contents ZJ/ZR Shown DescriptionTable of Contents Component Location ZJ shownNomenclature Ton Sunline Magnum Model Number NomenclatureFeatures and Benefits Standard FeaturesBalanced Heating Factory Installed Options Control Options Guide Specifications Field Installed AccessoriesGeneral Indoor Evaporator Fan Assembly DescriptionUnit Cabinet Outdoor Condenser Fan Assembly Refrigerant ComponentsUnit Controls Gas Heating Section ZJ/ZR/ZF***N ModelsUnit Operating Characteristics Other Pre-engineered Accessories AvailableElectrical Requirements Standard Limited WarrantiesReheat Mode Sequence Of Operation Normal ModeAlternate Mode Reheat Control Board Reheat Controls PartRHB Physical Data ZJ180-300 Physical DataFilters ZR180-300 Physical Data No. speeds Number of motors Motor HP each ZF180-300 Physical Data AFUE%ZJ/ZR/ZF180-300 Unit Limitations MinCapacity Performance ZJ180-300 Cooling CapacitiesZJ180 15 Ton 115F 125F ZJ210 17.5 Ton ZJ210 17.5 Ton ZJ240 20 Ton ZJ240 20 Ton ZJ300 25 Ton ZJ300 25 Ton ZR180-300 Cooling and Reheat Capacities ZR180 15 TonZR180 15 Ton ZR180 15 Ton Alternate Reheat Mode 35F 45FSensible Capacity MBh ZR240 20 Ton 115F 125F ZR240 20 Ton Alternate Reheat Mode 75F 85F ZR300 25 Ton 115F 125F ZR300 25 Ton Alternate Reheat Mode 75F 85F ZF180-300 Cooling Capacities ZF180 15 Ton115F 125F ZF210 17.5 Ton ZF210 17.5 Ton ZF240 20 Ton ZF240 20 Ton ZF300 25 Ton ZF300 25 Ton Airflow Performance ZJ180-300 Side Duct ApplicationZJ180 15 Ton Side Duct ZJ210 17.5 Ton Side DuctZJ240 20 Ton Side Duct ZJ300 25 Ton Side Duct ZJ180-300 Bottom Duct Application ZJ180 15 Ton Bottom DuctZJ210 17.5 Ton Bottom Duct ZJ240 20 Ton Bottom Duct ZJ300 25 Ton Bottom Duct ZR180-300 Side Duct Application ZR180 15 Ton Side DuctZR240 20 Ton Side Duct ZR300 25 Ton Side Duct ZR180-300 Bottom Duct Application ZR180 15 Ton Bottom DuctZR240 20 Ton Bottom Duct ZR300 25 Ton Bottom Duct ZF180-300 Side Duct Application ZF180 15 Ton Side DuctZF210 17.5 Ton Side Duct ZF240 20 Ton Side Duct ZF300 25 Ton Side Duct ZF180-300 Bottom Duct Application ZF180 15 Ton Bottom DuctZF210 17.5 Ton Bottom Duct ZF240 20 Ton Bottom Duct ZF300 25 Ton Bottom Duct RPM Selection Additional Static ResistanceDrive Selection Altitude/Temperature Correction Factors Air Temperature ºF Gas Heat Minimum Supply AirFactor CorrectionIndoor Blower Specifications Power Exhaust SpecificationsElectric Heat Minimum Supply Air ZJ/ZR/ZF Indoor Sound Power Levels Sound PerformanceElectric Heat Multipliers ZJ180-300 Standard Drive Without Powered Convenience Outlet Electrical DataZJ180 MCA ZJ180-300 Standard Drive With Powered Convenience Outlet Model Stages AmpsZJ180-300 Standard Drive With Powered Convenience Outlet Conv YTG-G-0708 ZJ180-300 High Static Drive With Powered Convenience Outlet ZJ180-300 High Static Drive With Powered Convenience Outlet ZJ300 Low Static Drive Without Powered Convenience Outlet ZJ300 Low Static Drive With Powered Convenience OutletZR180-300 Standard Drive Without Powered Convenience Outlet ZR180ZR180-300 Standard Drive With Powered Convenience Outlet YTG-G-0708 ZR180-300 High Static Drive With Powered Convenience Outlet ZR300 Low Static Drive Without Powered Convenience Outlet ZR300 Low Static Drive With Powered Convenience OutletZF180-300 Standard Drive Without Powered Convenience Outlet ZF180Pwr Max Fuse Motors ZF180-300 Standard Drive With Powered Convenience Outlet ZF180-300 Standard Drive With Powered Convenience Outlet ZF180-300 Hi Static Drive Without Powered Convenience Outlet ZF180-300 Hi Static Drive Without Powered Convenience Outlet ZF180-300 Hi Static Drive With Powered Convenience Outlet ZF180-300 Hi Static Drive With Powered Convenience Outlet ZF180-300 Low Static Drive With Powered Convenience Outlet ZJ/ZR/ZF180-300 Wiring Diagrams ZJ180-300 Typical Control DiagramZR180-300 Typical Control Diagram OCC Terminal BlockZF180-300 Typical Control Diagram OCCWeights and Dimensions ZJ/ZR/ZF180-300 Unit WeightsZF Unit 4 Point Load Weight ZF Unit 6 Point Load Weight ZJ/ZR/ZF180-300 Unit Accessory Weights Supply Fan VFD Weights, in LbsZJ/ZR/ZF180-300 Unit Dimensions ZJ/ZR Unit Dimensions Front ViewUtilities Entry ZF Unit Dimensions Front View 48-5/8 15 Ton 52-5/8 17.5 thru 25 TonZJ/ZR/ZF Unit Dimensions Rear View For bottom duct applicationsFor side duct applications ZJ/ZR/ZF Unit Dimensions Rain Hood ZJ/ZR/ZF180-300 Unit ClearancesZJ/ZR/ZF180-300 Unit Accessory Dimensions ZJ/ZR/ZF180-300 Roof CurbZJ/ZR/ZF180-300 Typical Installation Johnson Controls Unitary Products York Drive Norman, OK
Related manuals
Manual 24 pages 22.74 Kb Manual 68 pages 3.65 Kb Manual 128 pages 30.42 Kb Manual 36 pages 24.83 Kb

R-410A specifications

York R-410A is a widely recognized and highly efficient refrigerant used in modern air conditioning systems. Developed as an environmentally friendly alternative to R-22, R-410A has gained popularity in the HVAC industry due to its numerous advantageous features and characteristics.

One of the main features of York R-410A is its ability to provide superior cooling performance. This refrigerant operates efficiently at both high and low temperatures, allowing systems using it to maintain optimal indoor climates even during extreme weather conditions. Its high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER) ratings make it a preferred choice for energy-conscious consumers, resulting in lower energy bills and a reduced carbon footprint.

Technologically, York R-410A systems feature advanced compressor designs that enhance their overall reliability and performance. These compressors are often equipped with variable-speed technology, enabling them to adjust their output to match the cooling demands of the space. This not only improves comfort levels but also leads to efficient energy consumption, reducing wear and tear on the equipment over time.

Another significant characteristic of York R-410A is its non-ozone-depleting properties. Unlike its predecessor R-22, which is being phased out due to its damaging effects on the ozone layer, R-410A is designed to minimize environmental impact. Its lower global warming potential (GWP) further underscores its role in promoting sustainability within the HVAC sector.

Furthermore, York R-410A systems are engineered with enhanced safety features. The refrigerant is non-toxic and non-flammable, which makes it safer for use in both residential and commercial applications. Additionally, its high thermal stability reduces the risk of breakdown or leakage, contributing to longer system lifespans and lower maintenance costs.

In conclusion, York R-410A stands out as a cutting-edge refrigerant that combines efficiency, safety, and environmental responsibility. With its advanced technologies and remarkable characteristics, it meets the demands of modern air conditioning requirements while paving the way for a sustainable future in HVAC systems. Adopting York R-410A not only benefits individual users through improved comfort and lower energy bills but also plays a vital role in protecting our planet's ozone layer and mitigating climate change.