York 2000 installation instructions Bhn Cfm Rpm, Model Motor, BCH Speed CFM, Med

Page 10

511.06-N5Y

TABLE 5 - SUPPLY AIR PERFORMANCE - 5 Ton w/Belt-Drive Blower 5 TON - SIDE DUCT CONNECTIONS @ 230/460/575 Volts

MODEL

AIR FLOW

 

 

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

 

 

 

 

0.20

0.30

0.40

0.50

0.60

0.70

0.80

 

BHN

CFM

 

RPM

Watts

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

1059

1560

1077

1590

1095

1630

1114

1650

1134

1660

1158

1685

1181

1720

 

 

2400

1032

1405

1054

1470

1074

1525

1094

1560

1116

1595

1140

1620

1167

1640

 

 

2300

1005

1260

1024

1275

1049

1370

1069

1440

1090

1475

1116

1505

1142

1535

 

 

2200

980

1160

1002

1170

1022

1190

1044

1250

1066

1350

1090

1410

1117

1440

 

 

2100

930

1060

957

1070

983

1080

1010

1100

1039

1160

1064

1260

1092

1340

 

060

2000

877

950

908

975

941

1000

976

1020

1009

1050

1040

1100

1070

1225

 

 

1900

-

-

-

-

894

885

940

940

980

980

1014

1020

1047

1095

 

 

1800

-

-

-

-

855

815

903

860

950

905

988

940

1022

970

 

 

1700

-

-

-

-

-

-

884

815

925

850

964

880

1001

910

 

 

1600

-

-

-

-

-

-

864

770

908

805

948

835

987

870

 

 

1500

-

-

-

-

-

-

-

-

882

740

926

780

965

830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

AIR FLOW

 

 

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

 

 

 

 

0.90

1.00

 

1.10

 

1.20

 

1.30

 

1.40

 

1.50

 

BCH

CFM

 

 

 

 

 

 

RPM

Watts

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

-

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

2400

1193

1665

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

2300

1170

1580

1202

 

1620

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

2200

1148

1480

1180

 

1530

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

2100

1121

1385

1155

 

1425

 

1190

 

1475

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

060

2000

1100

1285

1133

 

1340

 

1169

 

1385

 

1205

 

1445

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1900

1079

1180

1110

 

1240

 

1143

 

1280

 

1178

 

1330

 

1222

 

1375

 

-

 

-

 

-

 

-

 

 

1800

1058

1060

1090

 

1135

 

1122

 

1190

 

1158

 

1240

 

1196

 

1295

 

-

 

-

 

-

 

-

 

 

1700

1035

960

1071

 

1030

 

1103

 

1100

 

1134

 

1140

 

1164

 

1175

 

1197

 

1205

 

-

 

-

 

 

1600

1020

900

1056

 

965

 

1088

 

1035

 

1118

 

1065

 

1145

 

1105

 

1170

 

1130

 

1198

 

1150

 

 

1500

1004

860

1038

 

880

 

1070

 

925

 

1101

 

980

 

1130

 

1045

 

1158

 

1075

 

1184

 

1110

 

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO TABLE 7 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

TABLE 6 - SUPPLY AIR PERFORMANCE - 3, 4 & 5 Ton w/Direct-Drive Blower 230 / 460 / 575 VOLTS - SIDE DUCT APPLICATIONS

MODEL

MOTOR

 

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

 

0.20

0.30

0.40

0.50

0.60

0.70

 

0.80

0.90

1.00

BCH

SPEED

 

CFM

Watts

CFM

Watts

CFM

Watts

CFM

Watts

CFM

Watts

CFM

Watts

CFM

Watts

CFM

Watts

CFM

Watts

 

 

 

HI

-

-

-

-

-

-

1720

825

1665

795

1600

765

 

1540

735

1490

700

1380

670

036

MED

1660

850

1630

820

1590

780

1550

750

1500

720

1450

690

 

1400

665

1360

650

1270

610

 

LOW

1470

750

1440

725

1410

700

1370

675

1330

650

1290

625

 

1250

610

1220

600

1130

560

 

HI

-

-

-

-

2000

1010

1950

975

1905

945

1840

910

 

1770

825

1660

825

1530

775

048

MED

1810

910

1780

880

1740

850

1700

825

1665

800

1620

775

 

1560

740

1480

700

1390

660

 

LOW

1635

810

1610

780

1580

760

1555

740

1540

730

1510

715

 

1460

690

1400

660

1300

615

 

HI

-

-

-

-

2500

1400

2420

1350

2340

1300

2260

1250

 

2160

1190

2060

1135

1925

1065

060

MED

2390

1350

2350

1300

2300

1255

2245

1210

2190

1165

2130

1120

 

2065

1075

1990

1030

1900

970

 

LOW

2270

1320

2230

1270

2190

1220

2145

1170

2090

1110

2030

1070

 

1960

1020

1890

970

1810

920

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO TABLE 7 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

TABLE 7 - STATIC RESISTANCES*

EXTERNAL STATIC PRESSURE DROP

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

CFM

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

Economizer1, 2

 

 

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

Electric Heaters1

 

5 - 15 KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

 

20 - 30 KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

 

 

Bottom Duct Connections1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

10

Unitary Products Group

Image 10
Contents Inspection GeneralApprovals ReferenceTable of Contents Location InstallationRigging and Handling ClearancesFilters Service AccessPower and Control Wiring Condensate DrainElectric Heaters Economizer Rain Hood Assembly Option Optional Economizer Rain HoodModels BCH Weights LBSOptions / Accessories Supply AIRKnockout Hole Size Used for DIA Control Wiring Side or Bottom Power WiringUtilities Entry Data Return AIRModel AIR Flow BCH CFM RPMBCH Speed CFM BHN CFM RPMModel Motor MEDMIN MAX RLA LRA FLA Amps Blower Circuit Size Breaker BCH Supply Motor AmpacityMIN MAX RLA LRA FLA Operation Checking Supply AIR CFM Lockout ControlTurns Blower Drive Range RPM Open TON Normal Maintenance Maintenance1000 1500 2000 2500 3000 511.06-N5Y Unitary Products Group Models only
Related manuals
Manual 24 pages 58.42 Kb