York 2000 installation instructions Model AIR Flow, Bch Cfm Rpm

Page 9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

511.06-N5Y

TABLE 4 - SUPPLY AIR PERFORMANCE - 3 & 4 Ton Units w/Belt-Drive Blower

 

 

 

 

 

 

3 TON - SIDE DUCT CONNECTIONS @230/460/575 Volts

 

 

 

 

 

 

 

 

 

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

0.20

0.30

0.40

0.50

0.60

0.70

0.80

 

BCH

CFM

 

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

843

860

880

925

919

1005

956

1065

993

1145

1030

1195

1067

1235

 

 

1900

817

775

854

850

893

920

930

995

970

1065

1008

1125

1046

1170

 

 

1800

790

700

828

760

867

840

906

905

944

980

985

1040

1025

1100

 

 

1700

-

-

802

670

840

745

881

815

920

900

961

970

1001

1030

 

036

1600

-

-

-

-

818

665

858

740

898

820

940

890

980

950

 

 

1500

-

-

-

-

-

-

842

695

882

755

922

835

962

895

 

 

1400

-

-

-

-

-

-

833

650

867

705

904

765

942

820

 

 

1300

-

-

-

-

-

-

-

-

858

665

893

725

932

785

 

 

1200

-

-

-

-

-

-

-

-

847

640

880

680

916

730

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

0.90

1.00

1.10

1.20

1.30

1.40

1.50

 

BCH

CFM

 

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

1103

1270

-

-

-

-

-

-

-

-

-

-

-

-

 

 

1900

1085

1210

-

-

-

-

-

-

-

-

-

-

-

-

 

 

1800

1064

1145

1102

1180

-

-

-

-

-

-

-

-

-

-

 

 

1700

1040

1075

1081

1115

1121

1140

-

-

-

-

-

-

-

-

 

036

1600

1020

1005

1060

1050

1100

1085

-

-

-

-

-

-

-

-

 

 

1500

1003

945

1044

995

1086

1035

-

-

-

-

-

-

-

-

 

 

1400

982

880

1024

920

1067

965

1107

1000

-

-

-

-

-

-

 

 

1300

970

835

1010

870

1053

920

1099

960

-

-

-

-

-

-

 

 

1200

953

780

992

815

1034

855

1080

905

-

-

-

-

-

-

 

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO TABLE 7 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

4 TON - SIDE DUCT CONNECTIONS @ 230/460/575 Volts

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

 

 

 

0.20

0.30

0.40

0.50

 

0.60

 

0.70

 

0.80

 

BCH

CFM

 

 

 

 

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

843

860

880

925

919

1005

956

1065

 

993

 

1145

 

1030

 

1195

 

1067

 

1235

 

 

1900

817

775

854

850

893

920

930

995

 

970

 

1065

 

1008

 

1125

 

1046

 

1170

 

 

1800

790

700

828

760

867

840

906

905

 

944

 

980

 

985

 

1040

 

1025

 

1100

 

 

1700

-

-

802

670

840

745

881

815

 

920

 

900

 

961

 

970

 

1001

 

1030

 

048

1600

-

-

-

-

818

665

858

740

 

898

 

820

 

940

 

890

 

980

 

950

 

 

1500

-

-

-

-

-

-

842

695

 

882

 

755

 

922

 

835

 

962

 

895

 

 

1400

-

-

-

-

-

-

833

650

 

867

 

705

 

904

 

765

 

942

 

820

 

 

1300

-

-

-

-

-

-

-

-

 

858

 

665

 

893

 

725

 

932

 

785

 

 

1200

-

-

-

-

-

-

-

-

 

847

 

640

 

880

 

680

 

916

 

730

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

 

 

 

 

0.90

1.00

1.10

1.20

 

1.30

 

1.40

 

1.50

 

BCH

CFM

 

 

 

 

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

RPM

 

Watts

 

 

 

 

 

 

 

 

 

2000

1103

1270

-

-

-

-

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1900

1085

1210

-

-

-

-

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1800

1064

1145

1102

1180

-

-

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1700

1040

1075

1081

1115

1121

1140

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

048

1600

1020

1005

1060

1050

1100

1085

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1500

1003

945

1044

995

1086

1035

-

-

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1400

982

880

1024

920

1067

965

1107

1000

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1300

970

835

1010

870

1053

920

1099

960

 

-

 

-

 

-

 

-

 

-

 

-

 

 

1200

953

780

992

815

1034

855

1080

905

 

-

 

-

 

-

 

-

 

-

 

-

 

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO TABLE 7 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

Unitary Products Group

9

Image 9
Contents Approvals GeneralInspection ReferenceTable of Contents Rigging and Handling InstallationLocation ClearancesPower and Control Wiring Service AccessFilters Condensate DrainElectric Heaters Optional Economizer Rain Hood Economizer Rain Hood Assembly OptionOptions / Accessories Weights LBSModels BCH Supply AIRUtilities Entry Data DIA Control Wiring Side or Bottom Power WiringKnockout Hole Size Used for Return AIRBCH CFM RPM Model AIR FlowModel Motor BHN CFM RPMBCH Speed CFM MEDBlower Circuit Size Breaker BCH Supply Motor Ampacity MIN MAX RLA LRA FLA AmpsMIN MAX RLA LRA FLA Operation Lockout Control Checking Supply AIR CFMTurns Blower Drive Range RPM Open TON Maintenance Normal Maintenance1000 1500 2000 2500 3000 511.06-N5Y Unitary Products Group Models only