York 2000 installation instructions Electric Heaters

Page 5

ELECTRIC HEATERS

Supplemental electric heaters may be ordered as a field-installed accessory. Refer to Form 530.18-N7.1V for installation instruction. These UL and C.G.A. approved heaters are located within the central compartment of the unit (see Figure 6 for access panel) with the heating elements extending into the supply air chamber.

Fuses are supplied, where required, by the factory. Some KW sizes require fuses and others do not. Refer to the electric heater accessory installation instruction for the heater electrical data.

The minimum air flow limitations across these heaters are listed in Table 2.

 

 

 

 

 

511.06-N5Y

TABLE 2 - AIR FLOW LIMITATIONS

 

 

NOMINAL

 

UNIT MODEL SIZE, NOMINAL TONS

HEATER

1

3

 

4

5

SIZE

VOLTAGE

 

 

 

 

MINIMUM SUPPLY AIR CFM

 

KW

 

 

 

 

 

 

5

 

1,100

 

1,300

1,600

7

 

1,100

 

1,300

1,600

10

208 /

1,200

 

1,300

1,600

15

230-1-60

1,200

 

1,300

1,600

20

 

1,3002

 

1,3002

1,600

30

 

 

1,600

5

 

1,100

 

1,300

1,600

7

 

1,100

 

1,300

1,600

10

208 /

1,200

 

1,300

1,600

15

230-3-60

1,200

 

1,300

1,600

20

 

1,3002

 

1,300

1,600

30

 

 

1,600

7

 

1,100

 

1,300

1,600

10

 

1,200

 

1,300

1,600

15

460-3-60

1,200

 

1,300

1,600

20

 

1,300

 

1,300

1,600

30

 

 

1,600

10

 

1,200

 

1,300

1,600

15

575-3-60

1,200

 

1,300

1,600

20

1,300

 

1,400

1,600

 

 

30

 

 

1,800

1208/230 and 460 volt heaters are UL approved. 208/230 and 575 volt heaters are CGA approved.

2CGA minimum is 1,400 CFM.

CONTROL WIRING

124-volt thermostat with subbase; -2TH11704024 for manual changeover. -2TH11704124 for automatic changeover.

2Only required on units with supplemental electric heat.

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DISCONNECT

SWITCH, THE WIRING AND THE

OVERCURRENT PROTECTION.

FIG. 3 - TYPICAL FIELD WIRING

TO REMOTE SENSOR

2TH04702224 IF USED

1Electronic progammable thermostat 2ET04700324 with subbase for either manual or automatic changeover.

2Only required on units with economizer. Remove jumper L2 from terminals

4 and 9 on jumper plug P7. The outdoor air intake dampers will return to their fully closed position when the thermostat switches to the “unoccupied” mode.

3Second stage cooling may be used on units with economizer. Remove jumper J1 from terminals 8 and 10 on jumper plug connector P7.

4Only required on units with supplemental electric heat.

POWER WIRING

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DISCONNECT

SWITCH, THE WIRING AND THE

OVERCURRENT PROTECTION.

Unitary Products Group

5

Image 5
Contents Approvals GeneralInspection ReferenceTable of Contents Rigging and Handling InstallationLocation ClearancesPower and Control Wiring Service AccessFilters Condensate DrainElectric Heaters Optional Economizer Rain Hood Economizer Rain Hood Assembly OptionOptions / Accessories Weights LBSModels BCH Supply AIRUtilities Entry Data DIA Control Wiring Side or Bottom Power WiringKnockout Hole Size Used for Return AIRBCH CFM RPM Model AIR FlowModel Motor BHN CFM RPMBCH Speed CFM MEDMIN MAX RLA LRA FLA Blower Circuit Size Breaker BCH Supply Motor AmpacityMIN MAX RLA LRA FLA Amps Operation Turns Blower Drive Range RPM Open TON Lockout ControlChecking Supply AIR CFM 1000 1500 2000 2500 3000 MaintenanceNormal Maintenance 511.06-N5Y Unitary Products Group Models only
Related manuals
Manual 24 pages 58.42 Kb