ELECTRIC HEATERS
Supplemental electric heaters may be ordered as a
Fuses are supplied, where required, by the factory. Some KW sizes require fuses and others do not. Refer to the electric heater accessory installation instruction for the heater electrical data.
The minimum air flow limitations across these heaters are listed in Table 2.
|
|
|
|
| ||
TABLE 2 - AIR FLOW LIMITATIONS |
|
| ||||
NOMINAL |
| UNIT MODEL SIZE, NOMINAL TONS | ||||
HEATER | 1 | 3 |
| 4 | 5 | |
SIZE | VOLTAGE |
|
|
|
| |
MINIMUM SUPPLY AIR CFM | ||||||
| ||||||
KW |
| |||||
|
|
|
|
| ||
5 |
| 1,100 |
| 1,300 | 1,600 | |
7 |
| 1,100 |
| 1,300 | 1,600 | |
10 | 208 / | 1,200 |
| 1,300 | 1,600 | |
15 | 1,200 |
| 1,300 | 1,600 | ||
20 |
| 1,3002 |
| 1,3002 | 1,600 | |
30 |
| – |
| – | 1,600 | |
5 |
| 1,100 |
| 1,300 | 1,600 | |
7 |
| 1,100 |
| 1,300 | 1,600 | |
10 | 208 / | 1,200 |
| 1,300 | 1,600 | |
15 | 1,200 |
| 1,300 | 1,600 | ||
20 |
| 1,3002 |
| 1,300 | 1,600 | |
30 |
| – |
| – | 1,600 | |
7 |
| 1,100 |
| 1,300 | 1,600 | |
10 |
| 1,200 |
| 1,300 | 1,600 | |
15 | 1,200 |
| 1,300 | 1,600 | ||
20 |
| 1,300 |
| 1,300 | 1,600 | |
30 |
| – |
| – | 1,600 | |
10 |
| 1,200 |
| 1,300 | 1,600 | |
15 | 1,200 |
| 1,300 | 1,600 | ||
20 | 1,300 |
| 1,400 | 1,600 | ||
|
| |||||
30 |
| – |
| – | 1,800 |
1208/230 and 460 volt heaters are UL approved. 208/230 and 575 volt heaters are CGA approved.
2CGA minimum is 1,400 CFM.
CONTROL WIRING
2Only required on units with supplemental electric heat.
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, THE WIRING AND THE
OVERCURRENT PROTECTION.
FIG. 3 - TYPICAL FIELD WIRING
TO REMOTE SENSOR
2TH04702224 IF USED
1Electronic progammable thermostat 2ET04700324 with subbase for either manual or automatic changeover.
2Only required on units with economizer. Remove jumper L2 from terminals
4 and 9 on jumper plug P7. The outdoor air intake dampers will return to their fully closed position when the thermostat switches to the “unoccupied” mode.
3Second stage cooling may be used on units with economizer. Remove jumper J1 from terminals 8 and 10 on jumper plug connector P7.
4Only required on units with supplemental electric heat.
POWER WIRING
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, THE WIRING AND THE
OVERCURRENT PROTECTION.
Unitary Products Group | 5 |