York 2000 Blower Circuit Size Breaker BCH Supply Motor Ampacity, MIN MAX RLA LRA FLA Amps

Page 11

 

 

 

 

 

 

 

 

 

 

 

 

511.06-N5Y

TABLE 8 - MOTOR AND DRIVE DATA w/Belt-Drive Blower

 

 

 

 

 

 

 

 

 

 

 

MOTOR*

 

ADJUSTABLE

 

FIXED

BELT

 

BLOWER

 

 

MOTOR PULLEY

BLOWER PULLEY

 

 

 

 

 

 

 

 

MODEL

RANGE

 

 

FRAME

SERVICE

PITCH

BORE

PITCH

BORE

PITCH

 

DESIG-

 

(RPM)

HP

RPM

DIA.

DIA.

 

LENGTH

 

SIZE

FACTOR

(in.)

 

(in.)

NATION

 

 

 

 

(in.)

(in.)

 

(in.)

 

 

 

 

 

 

 

 

 

 

 

 

BCH 036

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

 

A36

BCH 048

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

 

A36

BCH 060

850 - 1220

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.2

 

1

37.3

 

A36

*All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 9 - ELECTRICAL DATA w/Direct-Drive Blower Motor

 

 

 

VOLTAGE

 

 

 

OUTDOOR

SUPPLY

 

MAX.

MAX.

 

 

 

LIMITATIONS

COMPRESSOR

AIR

MINIMUM

FUSE

HACR

MODEL

POWER

FAN

(SEE NOTE 1)

 

 

 

BLOWER

CIRCUIT

SIZE,

BREAKER

BCH

 

SUPPLY

 

 

 

MOTOR,

 

 

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

 

MIN.

MAX.

RLA

 

LRA

FLA

 

 

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

19.0

 

105

1.7

4.4

29.9

45

45

036

 

208/230-3-60

187

253

11.9

 

85

1.7

4.4

21.0

30

30

 

460-3-60

414

504

5.9

 

42

1.0

2.2

10.6

15

15

 

 

 

 

 

575-3-60

518

630

4.8

 

34

1.0

2.2

10.2

15

15

 

 

208/230-1-60

187

253

23.1

 

105

2.3

5.0

36.1

50

50

048

 

208/230-3-60

187

253

14.7

 

130

2.3

5.0

25.7

40

40

 

460-3-60

414

504

7.7

 

64

1.4

2.2

13.2

20

20

 

 

 

 

 

575-3-60

518

630

6.4

 

52

1.4

2.2

11.6

15

15

 

 

208/230-1-60

187

253

32.1

 

169

2.3

6.6

49.0

80

80

060

 

208/230-3-60

187

253

19.3

 

137

2.3

6.6

33.0

50

50

 

460-3-60

414

504

10.0

 

62

1.4

3.3

17.2

25

25

 

 

 

 

 

575-3-60

518

630

7.9

 

50

1.4

3.3

14.6

20

20

NOTES:

1. Rated in accordance wtih ARI Standard 110, utilizatin range "A".

 

 

 

 

 

 

 

2. Dual element, time delay type.

 

 

 

 

 

 

 

 

 

TABLE 10 - ELECTRICAL DATA w/Belt-Drive Blower Motor

 

 

 

VOLTAGE

 

 

OUTDOOR

SUPPLY

 

MAX.

MAX.

 

 

 

LIMITATIONS

COMPRESSOR

AIR

MINIMUM

FUSE

HACR

MODEL

POWER

FAN

(SEE NOTE 1)

 

 

BLOWER

CIRCUIT

SIZE,

BREAKER

BCH

 

SUPPLY

 

 

MOTOR,

 

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

 

MIN.

MAX.

RLA

LRA

FLA

 

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

19.0

105

1.7

5.3

34.8

45

45

036

 

208/230-3-60

187

253

11.9

85

1.7

5.3

21.9

30

30

 

460-3-60

414

504

5.9

42

1.0

3.1

11.5

15

15

 

 

 

 

575-3-60

518

630

4.8

34

1.0

3.1

11.1

15

15

 

 

208/230-1-60

187

253

23.1

105

2.3

8.6

39.7

50

50

048

 

208/230-3-60

187

253

14.7

130

2.3

5.2

25.9

40

40

 

460-3-60

414

504

7.7

64

1.4

2.6

13.6

20

20

 

 

 

 

575-3-60

518

630

6.4

52

1.4

2.0

11.4

15

15

 

 

208/230-1-60

187

253

32.1

169

2.3

8.6

51.0

80

80

060

 

208/230-3-60

187

253

19.3

137

2.3

6.0

32.4

50

50

 

460-3-60

414

504

10.0

62

1.4

3.0

16.9

25

25

 

 

 

 

575-3-60

518

630

7.9

50

1.4

2.4

13.7

20

20

NOTES:

1. Utilization Range “A” in accordance with ARI Standard 110.

 

 

 

 

 

 

 

2. Dual element, time delay type.

 

 

 

 

 

 

 

 

Unitary Products Group

11

Image 11
Contents Reference GeneralApprovals InspectionTable of Contents Clearances InstallationRigging and Handling LocationCondensate Drain Service AccessPower and Control Wiring FiltersElectric Heaters Optional Economizer Rain Hood Economizer Rain Hood Assembly OptionSupply AIR Weights LBSOptions / Accessories Models BCHReturn AIR DIA Control Wiring Side or Bottom Power WiringUtilities Entry Data Knockout Hole Size Used forBCH CFM RPM Model AIR FlowMED BHN CFM RPMModel Motor BCH Speed CFMMIN MAX RLA LRA FLA Blower Circuit Size Breaker BCH Supply Motor AmpacityMIN MAX RLA LRA FLA Amps Operation Turns Blower Drive Range RPM Open TON Lockout ControlChecking Supply AIR CFM 1000 1500 2000 2500 3000 MaintenanceNormal Maintenance 511.06-N5Y Unitary Products Group Models only