CGTH INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 8: OPERATION 8.1 Operating Instructions

1.Set the thermostat to the lowest setting.

2.Turn off all electric power to the heater.

3.Do not try to light the burner by hand.

4.Turn off the manual gas valve in the heater supply line.

5.Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! If you do not smell gas, go to the next step.

6.Open the manual gas valve in the heater supply line.

7.Turn on electric power to the heater.

8.Set the thermostat to the desired setting.

9.If the heater will not operate, See Section 8.2 and call your service technician or gas supplier.

8.2 To Turn Off Gas To Heater

1. Set the thermostat to the lowest setting.

2.Turn off all electric power to the heater if service is to be performed.

3.Turn off the manual gas valve in the heater supply line.

8.3 Sequence of Operation

1.When the thermostat calls for heat, the blower motor will energize.

2.When the motor approaches nominal running speed, the pressure switch closes and activates the ignition module which in turn initiates the purge.

3.The ignition module then energizes the spark igniter.

4.When sparking begins, the gas valve is energized.

5.If a flame is detected, the gas valve remains open. When the call for heat is satisfied, the system con- trol mechanism de-energizes and the gas valve is turned off.

6.If no flame is detected, the gas valve is closed, and a purge period begins. After the purge period, the ignition module energizes the spark igniter and the gas valve. If a flame is still not established, a third and final purge/ignition sequence is begun. After three failed attempts, the system control mecha-

nism will lock out for a period of one hour or until the unit is reset. Reset is accomplished by remov- ing power from the heater for at least five seconds.

7.With a three-try module, when the flame is estab- lished and then lost on the first or second trial, the gas valve will automatically turn off. A purge and trial for ignition will then occur.

8.4 Testing

Establish that a satisfactorily purged gas supply and an electrical supply is available to the heater.

With the gas supply turned off at the gas valve, and the electrical supply isolated by switching off at the local switch and removing the appliance electrical plug, open the control chamber secured by the four screws. Remove the sealing screw from the outlet pressure tap with a 3/16" Hex Key Allen Wrench and install a test tap and hose. Remove the cover cap from the regulator screw with a straight slot screw- driver through the top hole of the burner. (See Figure 33).

Turn on appliance gas valve and connect appliance electrical plug. Ensure that the timer or thermostat, if fitted, is set to call for heat. Switch on power at the local switch. If necessary, the sequence as described above, in the first and second paragraphs, should take place. If not, refer to detailed fault finding sequence. When flame is established, check the gas pressure reading and adjust if necessary. See data label or Page 8, Section 2, for required gas pressure setting.

Check the gas pressure at the outlet of the gas valve to ensure minimum pressure. See Page 8, Section 2.9, for required gas pressure settings.

Switch off the electrical supply (shutting down the heater), remove pressure gauge and refit plug at out- let pressure tap, ensuring a tight gas seal. Replace cap and regulator screw. Close burner side cover.

34

Image 40
Contents Gas-Fired, Low-Intensity Page 2005 Page Table of Figures Page Questions, Comments or Suggestions Before YOU Begin 1.1 Read This ManualRoberts-Gordon, LLC Safety Unpacking the Heater 2.3.1 Manpower RequirementsAbout the Heater Carton Contents of Heaters with Galvanized Venting Carton Contents of Heaters with Cox Geelen Venting Heater AssemblyAvailable as an accessory under kit part numbers Manual Gas Shut-off ValveAvailable Accessories for Galvanized Vent Wall Venting Kit P/N 08032200 includes Components Identification Components Identification CGTH-Series byHeater Specifications Venting SpecificationsWhere Can the Heater Be Installed? Where Cant the Heater Be Installed?Gas Service Requirements 3.2.1 Gas Type Meter and ServiceElectrical Service Requirements Planning 3.1 GeneralVenting Requirements 3.4.1 System Requirements Venting CodesBalanced Flue Construction Public GaragesHazardous Locations Installation Safety EquipmentInstallation Tools Installation MaterialsGeneral Venting Guidelines Required Safe Distances from Combustibles Model Inches Metric cmHang the Heater Remove Shipping Screw from Control Housing DoorNon-residential applications Typical Installation Dimension Model Minimum MaximumHorizontal Installation Heater Orientation13 45 Tilted Installation 45 Tilted InstallationGrille Installation for Select Models Only Silicone Cap InstallationVenting Installation Install Galvanized CollarGeneral Venting Requirements United States RequirementsGalvanized Horizontal Venting Bird Screen Installation Galvanized Horizontal Venting with an ElbowHorizontal Installation Top View Elbow Assembly Vent Assembly Overview Assembly OverviewHorizontal Installation Side View Cox Geelen Venting Cox Geelen Horizontal VentingFlue Collar and Adapter Part Number DescriptionVertical Venting Configurations Cox Geelen Vertical VentingVent Clamp Electrical Service Installation Heater Rating 120V, 60 Hz, Single Phase, 1AThermostat Placement System RequirementsThermostat Installation Rear View GAS Service Installation 7.1 Install Gas Supply Lines Testing Operation 8.1 Operating InstructionsTo Turn Off Gas To Heater Sequence of OperationCover Cap Regulator Screw Outlet Pressure Tap Possible Cause Try this Blower does not Come onIgniter does not Spark LP Gas Burner does not LightNatural Gas Manometer Reading Burner Cycles on and OFF TOO Quickly Housing door. See Page 17, Section Burner Makes Vibrating Noises While RunningMaintenance 10.1 Pre-Season Maintenance Wiring Diagrams 11.1 Connection Diagram Connection DiagramLadder Diagram Ladder Diagram Replacement Parts Illustrated Parts List for Burner Illustrated Parts ListReplacement Parts List for Burner Part Number Description CGTH-30 CGTH-40 CGTH-50 ROBERTS-GORDON will not PAY for Warranty is Void ifLimitations on Authority Representatives Page Owner Warranty Registration Card Page
Related manuals
Manual 30 pages 54.92 Kb

CGTH-40, CGTH-50, CGTH-30 specifications

Roberts Gordon is a renowned manufacturer known for its innovative heating solutions, particularly in the realm of infrared heaters. Among their product lineup, the CGTH series, which includes the CGTH-50, CGTH-40, and CGTH-30 models, exemplifies high-performance technology tailored specifically for industrial and commercial applications.

The CGTH series is designed for versatility and efficiency, offering advanced features that enhance the heating experience in various environments. One of the standout features of these heaters is their infrared technology, which provides targeted warmth, making them ideal for large, open spaces such as warehouses, factories, and sporting facilities. Infrared heaters work by directly heating objects and people in their path rather than the air, ensuring quicker warmth and greater energy efficiency.

Each model offers different heating capacities, with the CGTH-50 boasting a maximum output of 50,000 BTUs, the CGTH-40 providing up to 40,000 BTUs, and the CGTH-30 generating 30,000 BTUs. This variety allows users to choose a model that best fits their heating needs based on the size and requirements of their space.

The units are designed for easy installation, featuring a modular design that allows for both indoor and outdoor applications. Moreover, the heaters can be integrated with various control systems, including programmable thermostats and remote management, enhancing user convenience and optimizing energy usage.

A critical aspect of the CGTH series is its emphasis on durability and safety. Each model is crafted using high-quality materials that can withstand harsh conditions typically found in industrial settings. Additionally, they incorporate safety features such as over-temperature protection and robust mounting brackets, ensuring peace of mind during operation.

Another important characteristic of the CGTH series is their efficiency. By minimizing energy waste and targeting heat output precisely, these heaters can significantly lower energy costs, making them not only environmentally friendly but also economically advantageous for businesses.

In summary, the Roberts Gordon CGTH-50, CGTH-40, and CGTH-30 infrared heaters stand out for their innovative technology, energy efficiency, and reliability. Whether for large commercial spaces or industrial environments, these heating solutions are designed to provide the comfort and performance required for any operation. With their robust features and customizable options, they remain a top choice for effective heating solutions in diverse settings.