York BQ 060 BQ 6 Point Loads Weight Distribution, Center of Gravity, Operating Weights LBS

Page 39

036-21508-005-A-0305

 

A

BACK OF UNIT

A

447/8

447/8

BACK OF UNIT

821/4

 

821/4

D

F

B

X

X

 

B

E

C

APPROXIMATE

 

APPROXIMATE

 

CENTER OF GRAVITY

 

CENTER OF GRAVITY

 

 

C

CONDENSER COIL

D

 

END OF UNIT

FRONT OF UNIT

Y

Y

FRONT OF UNIT

CONDENSER COIL

END OF UNIT

FIGURE 9 - FOUR AND SIX POINT LOADING

TABLE 27: BQ 4 POINT LOADS WEIGHT DISTRIBUTION

UNIT

TOTAL

A

B

C

D

BQ036

628

139

137

174

177

 

 

 

 

 

 

BQ048

668

148

146

185

189

BQ060

693

154

151

192

196

TABLE 28: BQ 6 POINT LOADS WEIGHT DISTRIBUTION

UNIT

TOTAL

A

B

C

D

E

F

BQ036

628

93

92

91

116

117

119

 

 

 

 

 

 

 

 

BQ048

668

99

98

97

123

125

126

BQ060

693

103

102

100

128

129

131

TABLE 29: CENTER OF GRAVITY

DIMENSION

3 - 5 TON

 

 

X

40-¾”

 

 

Y

19-¾”

 

 

TABLE 30: OPERATING WEIGHTS (LBS.)

 

MODEL SIZE

 

 

3 TON

4 TON

5 TON

BASIC UNIT

BQ

 

 

628

668

693

 

Economizer

 

 

 

50

 

 

 

 

 

 

 

 

 

Motorized Damper

 

 

 

26

 

OPTIONS

 

 

 

 

 

 

 

 

 

5

- 7 kW

 

18

 

 

Electric Heater

 

 

 

 

 

 

 

 

10

- 15 kW

 

23

 

 

 

 

 

 

 

 

 

 

 

 

20

- 30 kW

 

28

 

 

 

 

 

 

 

 

 

 

Roof Curb

 

 

 

 

92

 

ACCY.

 

 

 

 

 

Barometric Relief / Fixed Air Damper

 

 

10

 

 

 

 

 

 

 

 

 

Belt-Drive Blower

 

 

 

5

 

Unitary Products Group

39

Image 39
Contents Description Technical Guide Single Package Heat Pump UnitsTable of Contents 718 Product Nomenclature Johnson UNT Controller, DFS, APS, SS Drain Pan Technicoat Condenser Coil & Dirty Filter Switch Hinged Filter Door & Toolless Access Cabinet 036-21508-005-A-0305 Novar ETC-3 Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Cabinet Features Unit Cutaway FACTORY-INSTALLED OptionsFIELD-INSTALLED Accessories 036-21508-005-A-0305 Capacity Ratings Sound Power RATING1BQ036 Cooling Capacities 3 TON BQ048 Cooling Capacities 4 TON BQ060 Cooling Capacities 5 TON BQ Heating Capacities CFM RET. AIR F CAP Outdoor AIR TEMPERATURE, F 72% RH036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 MED Belt Drive Blower Motor and Drive DataElectric Heater CFM Limitations Static ResistancesRLA LRA Voltage Motor Outlet Brkr 036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 Physical Data Electric Heat Correction FactorsVoltage LIMITATIONS1 Typical Control Wiring Typical Power WiringUnit Dimensions 3 5 TON Heat Pump Front View Unit with Fixed Outdoor AIR/MOTORIZED Damper Rainhood Minimum Clearances DISCONNECT/BLOWER Access Location Utilities EntryTypical Applications BQ 6 Point Loads Weight Distribution Operating Weights LBSCenter of Gravity Guide Specifications GeneralDescription Indoor Evaporator FAN Assembly Manual Outdoor AIR Damper BAS Controls SImplicity INTELLI-Comfort 036-21508-005-A-0305