036-21508-005-A-0305
| A | BACK OF UNIT | A |
447/8 | 447/8 |
BACK OF UNIT
821/4 |
| 821/4 |
D | F | B |
X | X |
|
B | E | C |
APPROXIMATE |
| APPROXIMATE |
| |
CENTER OF GRAVITY |
| CENTER OF GRAVITY |
| |
| C | CONDENSER COIL | D | |
| END OF UNIT | |||
FRONT OF UNIT | Y | Y | ||
FRONT OF UNIT |
CONDENSER COIL
END OF UNIT
FIGURE 9 - FOUR AND SIX POINT LOADING
TABLE 27: BQ 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT | TOTAL | A | B | C | D |
BQ036 | 628 | 139 | 137 | 174 | 177 |
|
|
|
|
|
|
BQ048 | 668 | 148 | 146 | 185 | 189 |
BQ060 | 693 | 154 | 151 | 192 | 196 |
TABLE 28: BQ 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT | TOTAL | A | B | C | D | E | F |
BQ036 | 628 | 93 | 92 | 91 | 116 | 117 | 119 |
|
|
|
|
|
|
|
|
BQ048 | 668 | 99 | 98 | 97 | 123 | 125 | 126 |
BQ060 | 693 | 103 | 102 | 100 | 128 | 129 | 131 |
TABLE 29: CENTER OF GRAVITY
DIMENSION | 3 - 5 TON |
|
|
X | |
|
|
Y | |
|
|
TABLE 30: OPERATING WEIGHTS (LBS.)
| MODEL SIZE |
|
| 3 TON | 4 TON | 5 TON | |
BASIC UNIT | BQ |
|
| 628 | 668 | 693 | |
| Economizer |
|
|
| 50 |
| |
|
|
|
|
|
|
| |
| Motorized Damper |
|
|
| 26 |
| |
OPTIONS |
|
|
|
|
|
|
|
|
| 5 | - 7 kW |
| 18 |
| |
| Electric Heater |
|
|
|
|
|
|
|
| 10 | - 15 kW |
| 23 |
| |
|
|
|
|
|
|
|
|
|
|
| 20 | - 30 kW |
| 28 |
|
|
|
|
|
|
|
|
|
| Roof Curb |
|
|
|
| 92 |
|
ACCY. |
|
|
|
|
| ||
Barometric Relief / Fixed Air Damper |
|
| 10 |
| |||
|
|
|
|
|
|
| |
|
|
|
| 5 |
|
Unitary Products Group | 39 |