TABLE 12: STATIC RESISTANCES
|
|
|
|
|
| RESISTANCE, IWG |
|
|
|
| ||
DESCRIPTION |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| CFM |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1000 | 1200 | 1400 | 1600 |
| 1800 |
| 2000 | 2200 | 2400 | 2600 |
|
|
|
|
|
|
|
|
|
|
|
| |
ECONOMIZER1, 2 | 0.07 | 0.08 | 0.09 | 0.11 |
| 0.13 |
| 0.15 | 0.17 | 0.20 | 0.23 | |
ELECTRIC | 0.04 | 0.05 | 0.06 | 0.07 |
| 0.08 |
| 0.10 | 0.12 | 0.14 | 0.16 | |
HEATERS1 |
|
|
|
|
|
|
|
|
|
|
|
|
0.06 | 0.07 | 0.08 | 0.09 |
| 0.11 |
| 0.13 | 0.15 | 0.17 | 0.20 | ||
BOTTOM DUCT CONNECTIONS1 | 0.06 | 0.07 | 0.08 | 0.09 |
| 0.10 |
| 0.11 | 0.12 | 0.14 | 0.16 |
1.Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 13: ELECTRIC HEATER CFM LIMITATIONS
UNIT MODEL SIZE NOMINAL |
|
|
| MINIMUM SUPPLY AIR CFM |
|
| ||
VOLTAGE |
|
|
|
|
|
| ||
|
| HEATER SIZE NOMINAL KW |
|
| ||||
TONS |
|
|
|
| ||||
|
|
|
|
|
|
| ||
|
| 5 | 7 | 10 | 15 | 20 | 30 | |
| 1100 | 1100 | 1200 | 1200 | 1300 | - | ||
3 | 1100 | 1100 | 1200 | 1200 | 1300 | - | ||
|
|
|
|
|
|
| ||
- | 1100 | 1200 | 1200 | 1300 | - | |||
| ||||||||
|
|
|
|
|
|
|
| |
| - | - | 1200 | 1200 | 1300 | - | ||
| 1300 | 1300 | 1300 | 1300 | 1300 | - | ||
|
|
|
|
|
|
|
| |
4 | 1300 | 1300 | 1300 | 1300 | 1300 | - | ||
|
|
|
|
|
|
| ||
- | 1300 | 1300 | 1300 | 1300 | - | |||
| ||||||||
| - | - | 1300 | 1300 | 1400 | - | ||
| 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | ||
|
|
|
|
|
|
|
| |
5 | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | ||
- | 1600 | 1600 | 1600 | 1600 | 1600 | |||
| ||||||||
|
|
|
|
|
|
|
| |
| - | - | 1600 | 1600 | 1600 | 1800 |