matic reset to prevent the heating element system from oper- ating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

a.Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compres- sor, with standard controls, shall be capable of oper- ation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER- Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi- tioned space during normal operation. During econo- mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.

036-21508-005-A-0305

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position,spring-return damper actuator. The maximum leakage rate for the out- door air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pres- sure differential of 0.5 IWG. A unit-mounted potentiome- ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down).

BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.

POWER EXHAUST OPTION - To work in conjunction with economizers.

ELECTRIC HEATERS

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD - Contains all hood panels and the hardware for assem- bling.

MANUAL OUTDOOR AIR DAMPER

COIL GUARD KIT - Guard for cooling coil.

HAIL GUARD

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION - To work in conjunction with economizers.

TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

DIRTY FILTER SWITCH

PHASE MONITOR

COIL GUARD

POWERED GFI CONVENIENCE OUTLET

NON-POWERED GFI CONVENIENCE OUTLET

42

Unitary Products Group

Image 42
Contents Technical Guide Single Package Heat Pump Units DescriptionTable of Contents 718 Product Nomenclature Johnson UNT Controller, DFS, APS, SS Drain Pan Technicoat Condenser Coil & Dirty Filter Switch Hinged Filter Door & Toolless Access Cabinet 036-21508-005-A-0305 Novar ETC-3 Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Cabinet Features FACTORY-INSTALLED Options Unit CutawayFIELD-INSTALLED Accessories 036-21508-005-A-0305 Sound Power RATING1 Capacity RatingsBQ036 Cooling Capacities 3 TON BQ048 Cooling Capacities 4 TON BQ060 Cooling Capacities 5 TON CFM RET. AIR F CAP Outdoor AIR TEMPERATURE, F 72% RH BQ Heating Capacities036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 Belt Drive Blower Motor and Drive Data MEDStatic Resistances Electric Heater CFM LimitationsRLA LRA Voltage Motor Outlet Brkr 036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 036-21508-005-A-0305 Physical Data Electric Heat Correction FactorsVoltage LIMITATIONS1 Typical Power Wiring Typical Control WiringUnit Dimensions 3 5 TON Heat Pump Front View Unit with Fixed Outdoor AIR/MOTORIZED Damper Rainhood DISCONNECT/BLOWER Access Location Utilities Entry Minimum ClearancesTypical Applications BQ 6 Point Loads Weight Distribution Operating Weights LBSCenter of Gravity Guide Specifications GeneralDescription Indoor Evaporator FAN Assembly Manual Outdoor AIR Damper BAS Controls SImplicity INTELLI-Comfort 036-21508-005-A-0305