matic reset to prevent the heating element system from oper- ating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
a.Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compres- sor, with standard controls, shall be capable of oper- ation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
•Compressor 5 Years
•Electric Heat Element 5 Years
•Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
•ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER- Outdoor and return air dampers that are inter- locked and positioned by a
036-21508-005-A-0305
•MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped
•BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.
•POWER EXHAUST OPTION - To work in conjunction with economizers.
•ELECTRIC HEATERS
•ECONOMIZER/MOTORIZED DAMPER RAIN HOOD - Contains all hood panels and the hardware for assem- bling.
•MANUAL OUTDOOR AIR DAMPER
•COIL GUARD KIT - Guard for cooling coil.
•HAIL GUARD
OTHER FACTORY INSTALLED OPTIONS
•POWER EXHAUST OPTION - To work in conjunction with economizers.
•TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL
•ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•DIRTY FILTER SWITCH
•PHASE MONITOR
•COIL GUARD
•POWERED GFI CONVENIENCE OUTLET
•
42 | Unitary Products Group |