FIGURE 12, PART A
MINIMUM 12 IN.
TO COMBUSTIBLES
CHIMNEY FLUE
MASONRY CHIMNEY CONSTRUCTED TO NFPA 211
MINIMUM CHIMNEY CLEARANCE TO BRICK AND COMBUSTIBLES IS 2 IN.
MINIMUM CLEARANCES 12 IN. OF BRICK ALL AROUND
CHIMNEY CONNECTOR TO HEATER
FIRE CLAY LINER
(5/8" MIN. WALL THICKNESS)
MIN.
MASONRY WALL
1.Use a minimum
FIGURE 12, PART B
MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.
|
|
| FLUE |
|
| CHIMNEY | |
|
|
| |
CHIMNEY LENGTH |
|
|
|
| NONSOLUBLE |
|
|
|
|
| |
| REFACTORY |
|
|
| CEMENT |
|
|
CHIMNEY LENGTH
FLUSH WITH INSIDE
AIR SPACEOF FLUE 9 IN. MINIMUM
MASONRY CHIMNEY CONSTRUCTED
TO NFPA 211
AIR SPACE
MINIMUM CLEARANCE 9 IN. ALL AROUND
CHIMNEY CONNECTOR TO HEATER
USE CHIMNEY MFRS. PARTS TO
ATTACH CONNECTOR SECURELY
SOLID INSULATED, LISTED
SHEET STEEL SUPPORTS
(24 GAUGE MIN. THICKNESS)
2.Use a solid insulated listed
FIGURE 12, PART C
MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.
TWO VENTILATED AIR CHANNELS EACH 1 INCH. CONSTRUCTED OF SHEET STEEL.
CHIMNEY THIMBLE
CHIMNEY FLUE
MASONRY CHIMNEY CONSTRUCTED TO NFPA 211
24 GAUGE
VENTILATED THIMBLE WITH TWO 1 INCH AIR CHANNELS
CHIMNEY CONNECTOR
TO HEATER
MINIMUM 6 IN. GLASS
FIBER INSULATION ALL AROUND
SHEET STEEL SUPPORTS (24 GAUGE MIN. THICKNESS)
3.Use a 10" diameter ventilated thimble made of at least 24 gauge (0.024") steel having two 1" air channels. The ventilated thimble must be separated from combustible materials by a minimum of 6" glass fiber insulation. The opening in the combustible wall shall be covered and the thimble supported with sheet steel supports which are at least 24 gauge (0.024") in thickness. The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section. Fasteners used to secure chimney sections shall not penetrate chimney flue liner. See Part C.
11