FIGURE 12, PART D
MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.
SHEET STEEL SUPPORTS
CHIMNEY SECTION
| CHIMNEY THIMBLE |
CHIMNEY | FLUE |
CONNECTOR | |
| |
2 IN. | CHIMNEY |
AIR SPACE |
|
MASONRY CHIMNEY CONSTRUCTED
TO NFPA 211
MINIMUM CLEARANCE 2 IN. ALL AROUND
1 IN. AIR SPACE TO CHIMNEY LENGTH
CHIMNEY CONNECTOR
TO HEATER
SOLID INSULATED, LISTED
LENGTH (12 IN. LONG MIN.)
SHEET STEEL SUPPORTS
(24 GAUGE MIN. THICKNESS)
4.Use an 8" inside diameter solid insulated listed
5.A listed
Additional requirements pertaining to Figure 8 and the above wall
1.Insulation material used as part of wall
2.All clearances and thicknesses are minimums: larger clearances and thickness are acceptable.
3.A chimney thimble, as shown for 3" and 4" above (Parts C and D) shall be for types "3" and 4" connections to facilitate removal of the chimney connector for cleaning. The chimney thimble shall be of ASTM C315 fireclay with 5/8" minimum wall thickness, or material or equivalent durability. The inside diameter of the thimble shall be sized for the proper snug fit of a 6" diameter chimney connector pipe. The thimble shall be installed without damage to the chimney flue. The thimble shall extend through the chimney wall to, but not beyond, the inner surface of the chimney flue and shall be permanently cemented in place with high temperature cement.
4.A chimney connector to a masonry chimney, except for 2" above (Part B), shall extend through the wall
5.Any material used to close up any opening for the connector shall be noncombustible.
PART E - (Figure 12)
In addition to the methods shown by A, B, C, and D of Figure 12, a listed
CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY WHEN CHIMNEY CONNECTOR
DOES NOT PASS THROUGH A COMBUSTIBLE WALL
If the chimney connector does not have to pass through a combustible wall to get to a masonry chimney, simply connect the chimney connector directly to the masonry chimney's chimney thimble as described and shown by parts C and D of Figure 12. Remember, the chimney connector should extend into the chimney thimble to the innerface of the chimney flue but not beyond; if the chimney connector is extended through the chimney thimble into the chimney flue, resistance to the flow of smoke and gases up the chimney will occur; that flow resistance will have an adverse affect on the opera- tion and performance of the heater and venting system.