Lochinvar TNR-I&S-02 Rated, Determining required vent length, Power Vent Installation

Page 9

TNR-I&S-02

Figure 12

Typical Vertical Direct Vent System Installation

Through The Wall Venting with Low Ground Clearance:

When venting cannot exit through the wall at a height greater than or equal to 12" (30.5 cm) (and above expected snow level) from the ground, then the installation must be modified as shown below (see Figure 13).

Figure 13

Vent Terminal (Low Ground Clearance)

Table 2

Direct Vent Maximum Vent Length

Storage

Rated

Max Vent Length (ft)

Max Vent Length (ft)

Capacity

Input

3" PVC or CPVC

4" PVC or CPVC

(Gallons)

(BTU/HR)

 

 

 

 

 

 

6 0

125,000

1 2 0

1 7 0

6 0

150,000

1 0 0

1 5 0

6 0

199,000

8 0

1 3 0

 

 

 

 

1 0 0

150,000

1 2 0

1 7 0

1 0 0

199,999

1 0 0

1 5 0

1 0 0

250,000

8 0

1 3 0

1 0 0

300,000

6 0

1 1 0

1 0 0

399,999

5 0

1 0 0

Determining required vent length:

1.Determine the total length of straight vent pipe (in feet) required for both the intake and the exhaust.

2.Add 5 feet of venting for every 90° elbow.

3.Add 2 ½ feet of venting for every 45° elbow.

4.Total vent length can not exceed “Max Vent Length” in Table 2.

5.Air intake can not exceed exhaust by more than 30 feet in any venting situation.

NOTICE

DO NOT include the 3" exhaust elbow or vent terminals in determining maximum vent length.

POWER VENT INSTALLATION

Power venting is where the indoor air is used and the exhaust is vented to the outside. Venting may be run horizontally through an outside wall or vertically through a roof through using either 3 inch (7.6 cm) or 4 inch (10.2 cm) diameter PVC or CPVC. This water heater is supplied with a screened intake and exhaust 90° elbow referred to as the exhaust vent terminal and the air intake terminal.

Power Vent Terminal Location

Refer to the “Direct Vent Terminal Location” (see page 7) section previously mentioned to determine the proper exhaust vent location. Plan the vent system layout so that proper clearances are maintained from plumbing and wiring. Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES, and with National Fuel Gas Code and local codes.

9

Image 9
Contents General Information Table of ContentsLocation Installation InstructionsMechanical Exhausting of Room AIR AIR RequirementsUnconfined Space Confined SpaceWater Connections Result from excessive temperature and pressuresInstructions for Connections Injury. The water is under pressure and may splashApproximate Time/Temperature Scald Chart Approximate TIME/TEMPERATURE Relationships in ScaldsScalding Venting Direct Vent InstallationDirect Vent Terminal Location Exceptions for InstallationsVent terminal must not terminate Vent Terminal LocationVertical Installation Horizontal InstallationFollow the following procedure to vent through the roof Follow the following procedure to vent through the wallPower Vent Terminal Location Power Vent InstallationRated Determining required vent lengthTypical Vertical Power Vent System Installation Total vent length can not exceed Max. Vent ength in Table Maximum Vent Length DeterminationRain Cap to Small Vent Pipe Ass’y Vent Pipe Preparation Initial PreparationSelection of Materials Electrical Connections GAS ConnectionsGAS Meter Size Natural GAS only GAS Pressure RegulationOperating Instructions General Instructions Wiring Diagram and SchematicTo Fill the Water Heater Sequence of OperationLighting Instructions Maintenance Schedule MaintenanceGeneral Burner Flame CheckDraining Water Heater Flushing Water HeaterFilling Water Heater Sediment and Lime Scale RemovalDrain Valve and Tank Access Panel Anode Inspection and ReplacementRelief Valve Vent and AIR Intake SystemMake sure that the temperature of the tank is cool Replace the switchTimes, call service Check Collector Limit Switch as previously mentioned