1Service (continued)

Maximum Cascade Outlet Set Point

This parameter determines the set point used by the individual water heaters in a Cascade. When a water heater is commanded to fire by the Leader water heater, it will attempt to achieve this temperature at its outlet. The Leader water heater will limit the modulation of the water heater in order to hold the temperature at the tank sensor to the user set point. If any of the water heater outlet temperatures reach the maximum cascade outlet set point, the water heater will then modulate down on its own in order to keep its outlet temperature within the maximum cascade outlet set point. Therefore, this parameter can be used to limit the outlet temperatures of all the water heaters in a Cascade. This parameter is adjustable by the installer by accessing parameter F7. The default maximum cascade set point is 185°F (85°C).

Minimum On/Off Time

In order to prevent units in a Cascade from short cycling, this parameter defines the minimum ON and OFF time for each unit. The installer can adjust this time by accessing parameter F8. The minimum setting is 0 seconds and the maximum setting is 10 minutes. The default is 30 seconds.

Minimum Next On Time

In order to reduce the risk of temperature overshoot with a Cascade, this parameter defines the minimum time delay from starting one unit until the next unit may be started. The installer can adjust this time delay by accessing parameter F9. The minimum setting is 0 minutes and the maximum setting is 10 minutes. The default is 60 seconds.

Boiler Size

Not used.

G: Circulation pumps

DHW Pump Delay

The DHW pump delay parameter sets the length of time the pump (if connected) will run after a DHW demand has been satisfied. This parameter is adjustable by the installer by accessing parameter G1. The time range for this parameter is 0 minutes to 40 minutes. The default time is 30 seconds.

DHW Pump Anti-Seize Delay

If the water heater pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by parameter G2. The range of this setting is 0 seconds to 40 minutes. The default setting is 20 seconds.

Service Manual

H: BMS

BMS Type (Power / Set Point)

When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the 0 - 10V signal can be interpreted as either a modulation command or a set point. When parameter H1 is set to POWER, the 0 - 10V signal will control the modulation. When set to SETPOINT, the 0 - 10V signal will control the tank set point. The default setting is

SETPOINT.

Volts at Minimum

When programmed for BMS control through the 0 - 10V BMS input or through ModBus, parameter H2 should be set to the minimum voltage signal sent to the SMART SYSTEM control. The range of this parameter is 0.0V to the Volts at Minimum value (parameter H3). The default setting is 2.0V.

Volts at Maximum

When programmed for BMS control through the 0 - 10V BMS input or through ModBus, parameter H3 should be set to the maximum voltage signal sent to the SMART SYSTEM control. The range of this parameter is the Minimum value (parameter H2) to 10.0V. The default value is 10.0V.

Rate at Minimum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Minimum parameter (H2) is set by parameter H4. The minimum value is 0% and the maximum is the Power at Maximum Volts setting H5. The default value is 20%.

Rate at Maximum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Maximum parameter (H3) is set by parameter H5. The minimum value is the Power at Minimum Volts setting H4 and the maximum is 100%. The default value is 100%.

Set Point at Minimum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Minimum parameter (H2) is set by parameter H6. The minimum value is 32°F (0°C) and the maximum is the Set Point at Maximum Volts setting H7. The default value is 70°F (21°C).

17

Image 17
Contents Models 151 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials Service What is in this manual?Maintenance TroubleshootingArmor water heater display ServiceControl inputs Smart System Control BoardControl outputs Smart System Control BoardGeneral Operation Access modesHow the water heater operates Sequence of operationOperation Display Button Screen Operation Display Status Display panel menu accessDisplay panel parameter access General Parameter tableModes Viewable and changeable control parameters Data Logging DHW SettingsFunctions Anti-CyclingControl modes Circulation pumps Minimum On/Off TimeService Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check water heater relief valveCheck all water heater wiring Check ignition ground wiringCheck control settings Perform start-up and checksCleaning heat exchanger Check flame signalReview with owner Oiled bearing circulatorsBefore troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does NotTemperature F Resistance Ω Checking temperature sensorsWire Color R/BK and Y Wire Color G and Y Resistance TemperatureNo Pump NoisyRelief Valve OpeningFlow Switch Fault Description Corrective ActionFlame Fail Ign Anti-cyclingRunning No FlameManual Reset Auto ResetFlame Sequence High LimitFan Speed Low Fan LowGV/Relay FailLouver Proving Sensor ShortedFlue Temp High Delta T HighRem Ctrl Flt Service BlkOutlet Temp High No Error Stored Watch Dog ErrorFatal Error Low 24 VACGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply PressureModel Gas valve adjustment procedureModels 151 Models 601 4Gas Valve Adjustment Model

151 - 801 specifications

Lochinvar 151 - 801 is a high-efficiency commercial water heater designed to meet the demanding needs of various applications in the hospitality, healthcare, and educational sectors. This advanced system provides reliable hot water with enhanced performance while promoting energy conservation and sustainability.

One of the standout features of the Lochinvar 151 - 801 is its powerful heating capability. With a robust heating input of up to 150,000 BTU per hour, it ensures a steady supply of hot water even during peak demand times. The efficient heat exchanger design optimizes thermal performance, allowing for quicker recovery rates, which is essential for facilities requiring substantial hot water usage.

This model integrates cutting-edge technologies to maximize energy efficiency. Utilized in the Lochinvar 151 - 801 is the Smart System control technology, which provides precise temperature management and diagnostics. This feature not only enhances operation efficiency but simplifies service and maintenance by providing real-time data and alerts, leading to reduced downtime.

Additionally, the Lochinvar 151 - 801 employs a stainless-steel tank construction that promotes durability and robustness. The tank is adequately insulated to minimize heat loss, thus keeping energy costs down. Its compact design also allows for easy installation in various spaces, including those with limited footprints.

Moreover, the unit features advanced combustion technology, including a modulating gas valve that adjusts the flame size according to demand, promoting even greater efficiency. This ensures that the water heater operates at optimum performance levels, reducing fuel consumption while ensuring a consistent supply of hot water.

Safety is a primary concern for Lochinvar, and the 151 - 801 model includes several integrated safety features, such as an ignition safety shutoff and a temperature/pressure relief valve. These systems work together to provide peace of mind while ensuring the unit operates safely within its designated parameters.

In conclusion, the Lochinvar 151 - 801 is an exemplary choice for commercial applications, offering powerful performance, efficient technologies, durable construction, and enhanced safety features. With its combination of high output and advanced monitoring capabilities, it stands as a reliable solution for organizations seeking an effective hot water heating solution.