Lochinvar 151 - 801 Troubleshooting, Check control module fuses, Before troubleshooting

Page 24

Service Manual

3Troubleshooting

￿WARNING

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and

dangerous operation. Always disconnect power to the water heater before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.

Check control module fuses

NOTICE

ALWAYS check control module fuses before

replacing control module or any major

 

 

 

components (blower, etc.). If one of these fuses

 

is blown, it can prevent the control module or

 

other components from operating.

1. Turn OFF power to the water heater at the external line

switch.

￿WARNING Never jumper (bypass) any device except for momentary testing as

outlined in the Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.

Before troubleshooting:

1.Have the following items:

a.Voltmeter that can check 120 VAC, 24 VAC, and 12 VDC.

b.Continuity checker.

c.Contact thermometer.

2.Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to water heater.

3.Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24 VAC between thermostat wire nuts and ground.

4.Make sure all external limit controls are installed and operating.

Check the following:

1.Wire connectors to control module are securely plugged in at the module and originating control.

2.Gas pressures:

Maximum: 14 inches w.c. (natural and LP) with no flow (lockup) or with water heater on

Minimum: 4 inches w.c. (natural), 8 inches w.c. (LP) with gas flowing (verify during water heater startup)

2.

Remove top access cover.

3.

Remove the control module cover.

4.

Inspect fuses F1, F2 and F3, see FIG 3-1 below.

Figure 3-1Control Module Fuses

F3 - .80 AMP FUSE

24V DC POWER SUPPLY

F1 - 5 AMP FUSE

PUMPS

F2 - 3.15 AMP FUSE

BLOWER

5.The water heater is shipped with three (3) spare fuses in a plastic bag attached to the control module cover.

6.If necessary, replace open fuse (F3 is .80 amps, F2 is 3.15 amps, and F1 is 5 amps).

Note: Fuses F1, F2 and F3 are all slow blow fuses.

￿WARNING Do not jumper fuse or replace with any fuse except as specified. Failure to comply could

result in severe personal injury, death, or substantial property damage.

7.Install control module cover and top access cover after fuse inspection.

8.Restore power to the water heater at the external line switch and verify water heater operation (Section 10 - Start-up in the Armor Water Heater Installation and Operation Manual) after completing water heater service.

24

Image 24
Contents Models 151 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid What is in this manual? ServiceMaintenance TroubleshootingService Armor water heater displaySmart System Control Board Control inputsSmart System Control Board Control outputsAccess modes General OperationHow the water heater operates Sequence of operationOperation Display Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Parameter table GeneralModes Viewable and changeable control parameters DHW Settings Data LoggingFunctions Anti-CyclingControl modes Minimum On/Off Time Circulation pumpsService Notification Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check water heater relief valveCheck ignition ground wiring Check all water heater wiringCheck control settings Perform start-up and checksCheck flame signal Cleaning heat exchangerReview with owner Oiled bearing circulatorsTroubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No BurnerOperation Unit Does NotChecking temperature sensors Temperature F Resistance ΩWire Color R/BK and Y Wire Color G and Y Resistance TemperatureNoisy No PumpRelief Valve OpeningFault Description Corrective Action Flow SwitchAnti-cycling Flame Fail IgnNo Flame RunningAuto Reset Manual ResetFlame Sequence High LimitFan Low Fan Speed LowGV/Relay FailSensor Shorted Louver ProvingFlue Temp High Delta T HighService Blk Outlet Temp HighRem Ctrl Flt Watch Dog Error No Error StoredFatal Error Low 24 VACCombustion Analysis Procedure Gas Valve AdjustmentOr Obstruction Gas Supply PressureGas valve adjustment procedure Models 151Model 4Gas Valve Adjustment Model Models 601

151 - 801 specifications

Lochinvar 151 - 801 is a high-efficiency commercial water heater designed to meet the demanding needs of various applications in the hospitality, healthcare, and educational sectors. This advanced system provides reliable hot water with enhanced performance while promoting energy conservation and sustainability.

One of the standout features of the Lochinvar 151 - 801 is its powerful heating capability. With a robust heating input of up to 150,000 BTU per hour, it ensures a steady supply of hot water even during peak demand times. The efficient heat exchanger design optimizes thermal performance, allowing for quicker recovery rates, which is essential for facilities requiring substantial hot water usage.

This model integrates cutting-edge technologies to maximize energy efficiency. Utilized in the Lochinvar 151 - 801 is the Smart System control technology, which provides precise temperature management and diagnostics. This feature not only enhances operation efficiency but simplifies service and maintenance by providing real-time data and alerts, leading to reduced downtime.

Additionally, the Lochinvar 151 - 801 employs a stainless-steel tank construction that promotes durability and robustness. The tank is adequately insulated to minimize heat loss, thus keeping energy costs down. Its compact design also allows for easy installation in various spaces, including those with limited footprints.

Moreover, the unit features advanced combustion technology, including a modulating gas valve that adjusts the flame size according to demand, promoting even greater efficiency. This ensures that the water heater operates at optimum performance levels, reducing fuel consumption while ensuring a consistent supply of hot water.

Safety is a primary concern for Lochinvar, and the 151 - 801 model includes several integrated safety features, such as an ignition safety shutoff and a temperature/pressure relief valve. These systems work together to provide peace of mind while ensuring the unit operates safely within its designated parameters.

In conclusion, the Lochinvar 151 - 801 is an exemplary choice for commercial applications, offering powerful performance, efficient technologies, durable construction, and enhanced safety features. With its combination of high output and advanced monitoring capabilities, it stands as a reliable solution for organizations seeking an effective hot water heating solution.