Lennox International Inc EL280DF installation instructions

Page 19

of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an exter- nal relay.

One line voltage adeterminnal is provided on the furnace integrated control. See figure 21 for integrated control configuration. This terminal is energized in the heating mode when the combustion air inducer is operat- ing. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con- nected to one of the provided neutral terminals. If a humidi- fier rated at greater than one amp is connected to this termi- nal, it is necessary to use an external relay relay.

One 24V "H" 1/4" spade terminal is provided on the furnace integrated control. See figure 21 for integrated control con- figuration. The terminal is energized in the heating mode when the combustion air inducer is operating and the pres- sure switch is closed. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the "C" terminal.

Generator Use − Voltage Requirements

The following requirements must be kept in mind when specifying a generator for use with this equipment:

SThe furnace requires 120 volts + 10% (Range: 108

volts to 132 volts).

SThe furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz).

SThe furnace integrated control requires both proper polarity and proper ground. Both polarity and proper grounding should be checked before attempting to op- erate the furnace on either permanent or temporary power.

SGenerator should have a wave form distortion of less than 5% total harmonic distortion (THC).

Thermostat

Install the room thermostat according to the instructions provided with the thermostat. See table 9 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropri- ate dual fuel thermostat instructions.

Indoor Blower Speeds

1 − When the thermostat is set to AN ON," the indoor blower will run continuously on the low heat speed when there is no cooling or heating demand.

2 − When the EL280DF is operating in the high−fire or low− fire heating mode, the indoor blower will run on the cor- responding heating speed.

3 − When the EL280DF is operating in the low cool or the high cool cooling mode, the indoor blower will run on the corresponding cooling speed.

Page 19

Image 19
Contents Table of Contents Installation Instructions EL280DFTOP View Unit Dimensions − inches mmEL280DF Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space NON−COMBUSTIBLE Floor Opening Size Downflow InstallationCombustible Floor Opening Size Setting Equipment Filters Venting Duct SystemTables for installations Mm of connector diameter as follows MIN MAX FAN + FAN FAN + NAT Carbon Monoxide Poisoning Hazard Gas PipingGas Pipe Capacity − ft3/hr m3/hr Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD Page Field Wiring Applications OFF EL280DF Schematic Wiring Diagram TWO−STAGE Integrated Control Integrated ControlUnit Start−Up For Your Safety Read Before LightingDial Gas Pressure AdjustmentGAS Meter Clocking Chart EL280DFHigh Altitude Proper CombustionHeat FAN-OFF Time in Seconds Other Unit AdjustmentsHeating Sequence of Operation Electrical SHOCK, Fire Or Explosion Hazard ServiceEL280DF BURNER, Combustion AIR Inducer Assembly Repair Parts ListHeat Exchanger Removal Start−Up & Performance Check List Drain Line Cooling ModeTemperature Rise Unit Operation