Lennox International Inc EL280DF Gas Piping, Carbon Monoxide Poisoning Hazard

Page 16

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a venting system commonly run with separate gas ap- pliances, the venting system is likely to be too large to properly vent the remaining attached appliances.

Conduct the following test while each appliance is operat- ing and the other appliances (which are not operating) re- main connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting re- quirements section.

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon mon- oxide poisoning or death.

The following steps shall be followed for each ap- pliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1 − Seal any unused openings in the common venting sys- tem.

2 − Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

3 − Close all building doors and windows and all doors be- tween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dry- ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper- ate at maximum speed. Do not operate a summer ex- haust fan. Close fireplace dampers.

4 − Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.

5 − After the main burner has operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.

6 − After determining that each appliance connected to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace damp- ers, and any other gas−burning appliances to their pre- vious mode of operation.

7 − If a venting problem is found during any of the preced- ing tests, the common venting system must be modi- fied to correct the problem.

Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan- dards of the National Fuel Gas Code ANSI Z223.1.

Gas Piping

Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.

CAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

Gas Supply

1 − This unit is shipped standard for left or right side instal- lation of gas piping. Connect the gas supply to the pip- ing assembly.

2 − When connecting the gas supply piping, consider fac- tors such as length of run, number of fittings, and fur- nace rating to avoid excessive pressure drop. Table 8 lists recommended pipe sizes for typical applications.

3 − The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.

4 − The piping should be sloped 1/4 inch (6.4 mm) per 15 feet (4.57 m) upward toward the meter from the fur- nace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang- ers or straps. Install a drip leg inside vertical pipe runs to the unit.

5 − A 1/8" N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See figure NO TAG.

6 − In some localities, codes may require the installation of a manual main shut-off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.

IMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro- leum gases.

NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect main power to the fur- nace. The installer should properly label these devices.

Page 16

Image 16
Contents Installation Instructions EL280DF Table of ContentsUnit Dimensions − inches mm TOP ViewEL280DF Gas Furnace Safety InformationShipping and Packing List Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space NON−COMBUSTIBLE Floor Opening Size Downflow InstallationCombustible Floor Opening Size Setting Equipment Filters Duct System VentingTables for installations Mm of connector diameter as follows MIN MAX FAN + FAN FAN + NAT Gas Piping Carbon Monoxide Poisoning HazardGas Pipe Capacity − ft3/hr m3/hr Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD Page Field Wiring Applications OFF EL280DF Schematic Wiring Diagram Integrated Control TWO−STAGE Integrated ControlFor Your Safety Read Before Lighting Unit Start−UpGas Pressure Adjustment GAS Meter Clocking ChartEL280DF DialProper Combustion High AltitudeOther Unit Adjustments Heat FAN-OFF Time in SecondsHeating Sequence of Operation Service Electrical SHOCK, Fire Or Explosion HazardEL280DF BURNER, Combustion AIR Inducer Assembly Repair Parts ListHeat Exchanger Removal Start−Up & Performance Check List Cooling Mode Temperature RiseUnit Operation Drain Line
Related manuals
Manual 7 pages 17.85 Kb