Raypak B-195 installation instructions Continuation Trouble Shooting Guide

Page 17

Continuation TROUBLE SHOOTING GUIDE

3d. Excessive vent exhaust or defective air/vent switch.

3d. Excessive negative pressure exerted by the exhaust system on the vent will prevent N.O. combustion air/vent switch from closing. Provide means to relieve pressure and close the N.O. switch. If combustion air/vent switch will not close, replace switch.

3e. Ignition module or igniter may be defective.

3e. Disconnect igniter leads from ignition module. Make sure 24V is present across ignition terminals on the igni- tion module during the ignition cycle. If not, replace ignition module. Check resistance reading across igniter leads. If circuit is open, or reading is greater than 30 ohms, replace the igniter. A new igniter will measure between 1 to 6 ohms at room tem- perature.

3f. Gas valve or the ignition module may be defective.

3f. During the ignition cycle, 24V should be present at the MV1 and GND termi- nals for about 5 seconds. If no 24V is measured, replace the ignition mod- ule. If 24V is present, replace the gas valve.

4.Unit energized, pump and blower running.

Ignitor is glowing.

Burners will not stay lighted.

4a.

Improper ground

4a.

Check ground connections inside

 

 

 

control box.

4b.

Loose wiring.

4b.

Check all connections and wire nuts.

4c.

Remote sensor

4c. Check wire connection to remote sen-

 

 

 

sor.

4d.

Insufficient gas pressure.

4d.

Check gas pressure at outlet of valve

 

 

 

under load, pressure should be:

 

 

 

3.5 in. W.C.for Natural gas

 

 

 

10.5 in. W. C. for Propane gas.

5Unit does not produce suffcient hot water

5a. Supply water temperature

5a. Ensure supply water temperature is at

too low.

least 140°F.

5b. Dishwasher times not set

5b. Ensure dishwasher operates correctly.

properly.

Check rinse cycle time and inspect

 

spray nozzles for correct pressure

 

setting or damage.

5c. Operating limit set too low.

5c. Adjust operating limit to minimum tem-

 

perature that provides 180°F rinse.

 

(Do not set above 185°F).

 

-Verify booster operates correctly, if

 

not, recheck all procedures listed

 

above.

17

Image 17
Contents For Your Safety Operating Installation InstructionsSTART-UP and Operation WarrantyServicing Unit PartsSpecifications and Dimensions General SpecificationsCOMBUSTION/VENTILATION AIR B195 Combustion AIR Adjustment LEG InstallationCode Requirements Clearance RequirementsVenting Applies only to exhaust hood over cooking equipment Page Water Piping GAS PipingPage Electrical Ladder Diagram Connection Diagram Start UP and Operation Start UP Procedures Filling the SystemComponent Location Sequence of Operation Checking CIRCULATOR/PUMPHOT Surface Ignition Models with Robertshaw GAS Valve Lighting the HeaterWhat to do if YOU Smell GAS Maintenance Instructions Section Testing the Ignition Safety SHUT-OFFADJUSTMENTS/REPLACEMENTS Components Burner INSPECTION/VISUALPage Servicing Unit Continuation Trouble Shooting Guide RAYPAK, INC Replacement Parts ListPage Page Page Limited Parts Warranty Commercial Booster Heater Scope

B-195 specifications

The Raypak B-195 is a prominent model in the realm of heating solutions, specifically designed for residential and commercial applications. Known for its robust construction and high efficiency, the B-195 seamlessly combines reliability with advanced technology. This model is particularly favored in the pool and spa industry, as well as for hydronic heating systems.

One of the standout features of the Raypak B-195 is its compact design, which allows for easy installation in tight spaces. Despite its smaller footprint, the B-195 does not compromise on performance. It has a btu output of 195,000, making it suitable for both heating large pools and providing adequate heating for homes. The B-195 operates on natural gas, which is both cost-effective and environmentally friendly, promoting greener living solutions.

The unit incorporates a user-friendly digital display and control panel, enabling users to set and adjust temperatures with ease. Its advanced microprocessor control technology ensures accurate temperature regulation and efficient operation. Among the technological highlights is the patented Raypak Cupro-Nickel heat exchanger, which not only enhances the heat transfer efficiency but also extends the lifespan of the unit. This material is highly resistant to corrosion, ensuring durability and reducing maintenance needs.

The B-195 also features an exceptional flow sensing system that automatically adjusts the heater operation based on the water flow rate. This dynamic response ensures optimal performance while preventing overheating, enhancing overall safety. Additionally, the unit comes equipped with a high-efficiency ignition system, allowing for quick starts and consistent heat output.

Another significant aspect of the Raypak B-195 is its compatibility with various automation systems, facilitating smart pool management. This allows users to integrate the heater with their existing pool control systems, enabling remote monitoring and control via smart devices.

In terms of energy efficiency, the B-195 meets and often exceeds industry standards, providing a commendable energy factor. This translates to lower operating costs and reduced environmental impact, making it an ideal choice for energy-conscious consumers.

Overall, the Raypak B-195 stands as a testament to innovation in heating technology, offering a blend of efficiency, reliability, and convenience. Whether for a luxury pool or essential home heating, the B-195 delivers outstanding performance tailored to meet diverse heating needs.