Raypak B6000 manual Trouble Shooting Guide

Page 49

Trouble Shooting Guide-Continued

Symptom

Possible Cause

Corrective Action

 

 

 

Boiler # x

Boiler not powered.

Check primary power.

"Not on Line" Displayed

 

Correct as necessary.

 

 

Check communication cable,

 

 

check (surge) ground Remove /

 

 

Replace (R/R) as necessary.

 

 

Initialize system.

 

 

 

Outdoor Temp. Sensor readings

Outdoor sensor not mounted

Refer to installation manual

are high.

correctly.

mounting instructions. Possible

 

 

relocation for sensor.

 

 

 

Sensor reading 220°F.

Sensor wiring shorted

Check sensor wiring for damage.

 

 

R/R as necessary.

 

 

Initialize system.

 

 

 

Sensor reading - 35°F.

Sensor wiring open.

R/R as necessary

 

 

Initialize system.

Low water cut-off alarm.

Excessive circuit loading of pump

Check power.

 

contacts by user supplied system

Check pump contactor / relay

 

pump.

R/R as necessary.

 

Low water level in boiler

Replace F1 fusing.

 

 

Check main water supply

 

 

 

Power lamp off on Boiler Monitor.

Fuse F1 blown.

Replace F1 fusing.

 

Excessive circuit loading of pump

Remove Relay-K1 to isolate circuit

 

contacts by user supplied system

loading.

 

pump.

R/R as necessary.

 

Circuit breaker tripped.

Reset circuit breaker.

 

 

 

Pump not running.

Excessive circuit loading of pump

Replace F1 fusing.

 

contacts by user supplied system

 

 

pump.

 

 

Pump going off on thermal over-

Check pump.

 

load circuit breaker tripped

Reset circuit breaker

 

 

 

Off at flow switch.

Paddle damaged or missing.

Check paddle on flow switch.

 

Pump off on thermal overload.

Check pump, contact or relay.

 

 

Replace F1 fusing.

 

 

 

Off on High Limit.

Low limit settings.

Check and correct settings.

 

Intermittent power or pump

Meter amperage on pump.

 

failure.

R/R as needed.

 

 

 

Page 49

Image 49
Contents System Controlboiler Monitor B6000TMPage B6000 Boiler Management System BMS Contents Equipment QuantityTable of Contents System Control Module has ForewordEach Boiler Monitor Module contains Mechanical Installation Installation and MountingInstall Conduit AS Appropriate Dimensions and Weight Check Your Power SourceElectrical Characteristics Electrical Installation VAC Feeder CircuitsInstallation AIR Temperature SensorWater Temperature Sensor Installation Notes Water Temperature SensorTypical Water Sensor Simplified Diagram of Typical Piping To the System Control Module Wiring AIR and Water SensorsBelden #9842 Communication RS 485 WiringWiring Power Source to System Control and Boiler Mod- ules Power Test Switch Boiler Monitor Select SwitchBoiler Monitor Card Pictorial Boiler Monitor Communications Jumper W1 Optional Boiler Monitor Field Wiring Multiple Boilers Mechanical Installation Installation Verification ProcedureAIR Temperature Sensor Water Temperature SensorEditing B6000 Displays Location System CONTROL/DISPLAY FamiliarizationSelectable Parameters Range Value Boiler Monitor POWER-UPSystem Control Module Displays System Temperatures Indicates selectable itemInformation only Boiler Valve Firing RatesReadout Boiler StatusHigh Limit No PilotLwco Primary Control Parameters Lead LAG, Night SET BackPush Select Temperature FSet = 135F Ratio Outdoor System 140 150 160 Suggested GuidelinesSecondary Control Parameters Lead Boiler Select StepAutomatic Lead Lag Push Select Pump DelayStandard Boiler Parameters Boiler ParametersSetback Times Am or pm Setback OFF DAY Information only Boiler Valve TimingTarget MIN/MAX and HI LIM ALL Boilers ON/OFFUtility Service Standard Utility ServiceTandard Initialize InitializeStart Alternate Wiring AIR and Water SensorsAlternate Communication RS 485 Wiring Page Alternate Power Test Check Power Fig. # Fig. # System Control Board New CP10.0 90FI Replacement Parts List Boiler Monitor Control BOX Spdt Call OUT SystemDpdt Select Set Optional Temperature Scale F or C StandardUniversal Select Set OptionTroubleshooting Guide Trouble Shooting Guide Limited Warranty Design and specifications subject to change without notice
Related manuals
Manual 24 pages 53.62 Kb

B6000 specifications

The Raypak B6000 is a high-efficiency boiler designed for residential and commercial heating applications. Known for its reliability and advanced features, the B6000 exemplifies Raypak's commitment to engineering excellence and innovative technology.

One of the standout attributes of the Raypak B6000 is its robust construction. The boiler is built with high-quality materials, ensuring durability and longevity in a variety of environments. It features a compact design, which allows for easy installation even in spaces with limited room. Moreover, it has a user-friendly interface that facilitates straightforward operation and maintenance, making it accessible for both homeowners and HVAC professionals.

The B6000 is equipped with advanced heating technologies that enhance its performance and efficiency. It utilizes a modulating burner system that adjusts the heat output based on the demand, ensuring optimal energy usage. This not only leads to lower energy bills but also contributes to a reduced carbon footprint, making the B6000 an environmentally friendly choice.

Another key feature of the Raypak B6000 is its stainless steel heat exchanger, which provides superior heat transfer and contributes to the boiler's overall efficiency. The heat exchanger is designed to withstand high temperatures and pressures, ensuring safety and reliability throughout its operation. Additionally, the B6000 offers multiple venting options, including direct venting and horizontal venting, providing flexibility in installation.

The B6000 also comes with integrated controls that allow users to easily monitor and adjust settings. These controls can enhance energy efficiency by accommodating varying heating needs throughout the day. Furthermore, the boiler is compatible with smart home systems, enabling remote operation and monitoring.

In terms of safety features, the Raypak B6000 is equipped with multiple safety sensors and shutoff systems to ensure safe operation. This includes automatic shutdown in case of malfunction, preventing potential hazards.

Overall, the Raypak B6000 is a top-tier boiler that combines efficiency, reliability, and advanced technology, making it a preferred choice for those seeking a dependable heating solution. It is suitable for various applications, from residential heating to larger commercial projects, further establishing its versatility in the market. Whether for new installations or replacements, the B6000 stands out as a reliable option for efficient heating solutions.