Raypak 302A-902A manual Direct Vent Horizontal Through- the-Wall, Material

Page 31

 

Model

Certified

 

Maximum

Combustion

Air Inlet

 

 

 

Air

Max. Length

 

 

Venting

Vent Size

Equivalent

 

 

No.

Intake Pipe

 

 

 

 

Material

 

Vent Length*

6”

8”

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

302A

 

5”

70’

 

100’

N/A

 

 

 

 

 

 

 

 

402A

 

 

 

 

 

 

6”

Room Air

Galvanized

 

 

 

 

502A

 

 

Steel,

75’

 

 

 

 

 

 

 

 

 

Category III

 

40’

PVC,

 

 

 

 

 

 

100’

 

 

652A

 

 

 

 

 

 

Ducted

ABS,

40’

 

 

752A

 

8”

Combustion

CPVC

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

902A

 

 

 

30’

80’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Subtract 10 ft per elbow. Max. 3 elbows.

Maximum combustion air duct length terminated at 100 equivalent ft.

Table M: Category III Horizontal and Direct Venting

Use only the special gas vent pipes listed for use with Category III gas burning heaters, such as the AL29-4C stainless steel vents offered by Heat Fab Inc. (800- 772-0739), Protech System, Inc. (800-766-3473) or Z- Flex (800-654-5600). Pipe joints must be positively sealed. Follow the vent manufacturer’s installation instructions carefully.

Direct Vent - Horizontal Through- the-Wall

Note: When vertical height exceeds 25 ft,

consult factory prior to installation.

Fig. 26: Direct Vent - Horizontal Through-the-Wall

Installation

These installations utilize the heater-mounted blower to draw combustion air from outdoors and vent com- bustion products to the outdoors.

The total length of the through-the-wall flue cannot exceed 40 equivalent ft in length for the flue outlet. Each elbow used is equal to 10 ft of straight pipe. This will allow installation in one of the three following arrangements:

40’ of straight flue pipe

30’ of straight flue pipe and one elbow

20’ of straight flue pipe and two elbows.

The total length of air supply pipe cannot exceed the distances listed in Table M. Each elbow used is equal to 10 ft of straight pipe. This will allow installation in any arrangement that does not exceed the lengths shown in Table M.

The flue direct vent cap is not considered in the over- all length of the venting system.

Care must be taken during assembly that all joints are sealed properly and are airtight.

The vent must be installed to prevent the potential ac- cumulation of condensate in the vent pipes. It is re- quired that:

1.The vent must be installed with a slight downward slope of not more than 1/4 inch per foot of hori- zontal run to the vent terminal.

2.The vent must be insulated through the length of the horizontal run.

31

Image 31
Contents Installation and Operating Instructions Page Contents Pay Attention to These Terms Ratings and Certifications Before InstallationProduct Receipt Model IdentificationComponent Locations Back Component LocationsModel # Burners per Stages Fire at Valve General InformationModel # Burners Valve Firing Per Valve Staging Time/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Stacking InstallationInstallation Codes Equipment BaseOutdoor Installations Indoor InstallationsClearances Installations1 Canadian Installations2 Direct Vent Combustion and Ventilation AirIndoor Units Reversing Air FilterAll Air from Inside the Building InstallationsConventional Combustion Air Supply TruSeal Combustion AirReversing Water Connections Canadian InstallationsWater Piping GeneralCold Water Operation Relief Valve Piping Hydrostatic TestMin. Flow Max Flow Gpm Temperature & Pressure GaugeHydronic Heating Pump SelectionThree-Way Valves Pressure Drop in Feet of Head Feedwater RegulatorPiping Air-Separation/Expansion TankPool Heating Potable Water and Space HeatingWinterizing Your Heater Automatic Chlorinators and Chemical FeedersTotal Dissolved Solids Gas SupplyPool/Spa Water Chemistry Water Hardness PH of WaterReversing Gas Supply Connection Gas Supply ConnectionTable J Maximum Equivalent Pipe Length Field-Connected Controllers Electrical Power ConnectionsCheck the Power Source Gas Supply PressureMaking the Electrical Connections Field Wiring ConnectionWiring Connections Appliance Categories VentingStainless Steel Support of Vent StackVent Terminal Location Direct Venting Horizontal ThroughCanadian Installations InstallationsChanging the Flue Outlet Natural Draft Vertical Venting Category Venting Installation TipsVenting Configurations InstallationMin Max TerminationCommon Venting System Model Venting Vent Size Height Intake Pipe Max. LengthHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryMax. Length Venting Vent Size Equivalent Intake Pipe Direct Vent Horizontal Through- the-WallMaterial Direct Vent Vertical Controls Outdoor InstallationFreeze Protection Models 302A, 402A, 502A, 652A, 752A and 902A Heater Sequence of OperationExternal Lights Color Indication Auto Reset High Limit Red Auto reset optionInternal Lights Color Indication Code Condition Ignition ModuleOperating Control High Limit Manual ResetFlow Switch High and Low Gas Pressure SwitchesHigh/Low Gas Pressure Switch Direct Venting Horizontal Through AL29-4C 87%-Efficiency Boilers Special Instructions Water PipingVenting Appliance Categories Model 10F 20F 30F Min. Flow Max Flow GpmVent Terminal Location Vertical Venting CategoryCondensate Management 40’ 752AE Combustion Air 902AE 30’ 80’ Certified Maximum Combustion Air Air Inlet Model VentingMaterial Vent Length 100’ DuctedDirect Vent Horizontal Through- the-Wall 100’ 40’ 752A 902A Direct Vent VerticalCertified Vertical Venting Combustion Air Air Inlet 302A 100’ 402A Galvanized Steel 502A 75’ Category 25’Wiring Diagram Pre Start-up START-UPMain Burner Adjustment Blower AdjustmentStart-Up Pilot Turn-Down Test Safety InspectionLeak Test Procedure Dual-Seat Gas Valves Follow-UpLeak Test Post Start-Up CheckLighting Instructions OperationTo Turn Off Gas To Appliance Step TroubleshootingSuggested Minimum Maintenance Schedule MaintenancePreventive Maintenance Schedule As Required WeeklySemi-Annually AnnuallyInside Air Contamination AppendixLimited Parts Warranty HI Delta Types H and WH Limited Parts Warranty HI Delta Type P

302A-902A specifications

The Raypak 302A-902A is a highly regarded pool and spa heater, known for its efficiency and reliability in delivering warmth to residential and commercial aquatic applications. This heater stands out due to its robust design, advanced technology, and user-friendly features.

One of the key characteristics of the Raypak 302A-902A is its dual fuel capability, which means it can run on either natural gas or propane. This flexibility allows users to choose their preferred fuel type, contributing to operational efficiency and cost-effectiveness. With a BTU output ranging from 302,000 to 902,000, the Raypak heater is capable of quickly heating large volumes of water, making it ideal for pools, spas, and hot tubs.

The heater incorporates advanced technology such as a stainless steel heat exchanger, which not only ensures excellent thermal conductivity but also promotes durability against corrosion. This is especially advantageous in harsh environments, where exposure to chemicals can significantly impact the lifespan of traditional copper heat exchangers. The Raypak 302A-902A's heat exchanger is designed to withstand the rigors of constant use while maintaining high performance levels.

Another prominent feature of the Raypak 302A-902A is its digital display control system, which simplifies the operation and monitoring of the heater. Users can easily set and adjust temperatures, as well as access diagnostic information, all through an intuitive interface. This digital control not only enhances user experience but also aids in the timely maintenance of the unit.

Energy efficiency is another major selling point of the Raypak 302A-902A. The heater is designed with environmentally friendly practices in mind, utilizing a low NOx burner that minimizes harmful emissions. This not only meets environmental regulations but also makes it a greener alternative for heating needs.

In terms of installation, the compact design of the Raypak 302A-902A allows for versatile placement options, whether in a residential backyard or a commercial environment. Its user-friendly installation process ensures that homeowners and businesses alike can enjoy the benefits of heated water with minimal hassle.

Overall, the Raypak 302A-902A is an exemplary choice for anyone seeking a high-quality, efficient, and flexible pool and spa heating solution. Its combination of robust engineering, advanced technology, and user-focused features solidifies its position as a leader in the market, promising effective heating for years to come. Whether for personal enjoyment or commercial use, this heater delivers exceptional performance that meets diverse heating needs.