Raypak 302A-902A manual Vertical Venting Category, Vent Terminal Location, Condensate Management

Page 40

WARNING: Contact the vent material manufactur- er if there are any questions about the appliance cat- egory or suitability of a vent material for Category II,

IIIor IV applications. Using improper venting materi- als can result in personal injury, death or property damage.

Vent Terminal Location

NOTE: During winter months check the vent cap and make sure no blockage occurs from build-up of snow or ice.

1.Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.

2.Give special attention to the location of the vent termination to avoid possibility of property dam- age or personal injury.

3.Gases may form a white vapor plume in winter. The plume could obstruct a window view if the ter- mination is installed near windows.

4.Prevailing winds, in combination with below-freez- ing temperatures, can cause freezing of con-den- sate and water/ice build-up on building, plants or roof.

5.The bottom of the vent terminal and the air intake shall be located at least 12 in. above grade, includ- ing normal snow line.

6.Un-insulated single-wall metal vent pipe shall NOT be used outdoors in cold climates for venting gas utilization equipment.

7.Through-the-wall vents for Category II and IV appliances shall not terminate over public walk- ways or areas where condensate or vapor could create a nuisance or hazard, or be detrimental to the operation of regulators, relief valves or other equipment.

8.Locate and guard vent termination to prevent acci- dental contact by people or pets.

9.DO NOT terminate vent in window well, stairwell, alcove, courtyard or other recessed area, unless previously approved by local authority.

10.DO NOT terminate above any door, window, or gravity air intake. Condensate can freeze, causing ice formations.

11.Locate or guard vent to prevent condensate from damaging exterior finishes. Install a rust-resistant sheet metal backing plate against brick or mason- ry surfaces.

12.DO NOT extend exposed vent pipe outside of building. Condensate could freeze and block vent pipe.

Condensate Management

Condensate must be routed from the condensate trap to an appropriate container for neutralization before disposal, as required by local codes.

Vertical Venting (Category II)

Note: When vertical height exceeds 25 ft,

consult factory prior to installation.

Fig. 37: Vertical Venting (Category II)

CAUTION: A properly sized listed vent cap termi- nal must be used to evacuate the flue products from the boilers.

Common Venting System

Manifolds that connect more than one boiler to a com- mon chimney must be engineered to handle the com- bined load. Consult available guides for proper sizing of the manifold and the chimney. At no time should the area of the vent be less than the area of the largest boiler exhaust outlet.

40

Image 40
Contents Installation and Operating Instructions Page Contents Pay Attention to These Terms Before Installation Product ReceiptModel Identification Ratings and CertificationsComponent Locations Component Locations BackModel # Burners per Stages Fire at Valve General InformationModel # Burners Valve Firing Per Valve Staging Time/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Installation Installation CodesEquipment Base StackingOutdoor Installations Indoor InstallationsClearances Installations1 Canadian Installations2 Combustion and Ventilation Air Indoor UnitsReversing Air Filter Direct VentInstallations Conventional Combustion Air SupplyTruSeal Combustion Air All Air from Inside the BuildingCanadian Installations Water PipingGeneral Reversing Water ConnectionsRelief Valve Piping Hydrostatic Test Cold Water OperationTemperature & Pressure Gauge Hydronic HeatingPump Selection Min. Flow Max Flow GpmPressure Drop in Feet of Head Feedwater Regulator PipingAir-Separation/Expansion Tank Three-Way ValvesPotable Water and Space Heating Pool HeatingAutomatic Chlorinators and Chemical Feeders Winterizing Your HeaterGas Supply Pool/Spa Water Chemistry Water HardnessPH of Water Total Dissolved SolidsReversing Gas Supply Connection Gas Supply ConnectionTable J Maximum Equivalent Pipe Length Electrical Power Connections Check the Power SourceGas Supply Pressure Field-Connected ControllersField Wiring Connection Making the Electrical ConnectionsWiring Connections Venting Appliance CategoriesSupport of Vent Stack Vent Terminal LocationDirect Venting Horizontal Through Stainless SteelCanadian Installations InstallationsChanging the Flue Outlet Venting Installation Tips Venting ConfigurationsInstallation Natural Draft Vertical Venting CategoryTermination Common Venting SystemModel Venting Vent Size Height Intake Pipe Max. Length Min MaxHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryMax. Length Venting Vent Size Equivalent Intake Pipe Direct Vent Horizontal Through- the-WallMaterial Direct Vent Vertical Controls Outdoor InstallationFreeze Protection Heater Sequence of Operation Models 302A, 402A, 502A, 652A, 752A and 902AExternal Lights Color Indication Auto Reset High Limit Red Auto reset optionInternal Lights Color Indication Ignition Module Code ConditionHigh Limit Manual Reset Flow SwitchHigh and Low Gas Pressure Switches Operating ControlHigh/Low Gas Pressure Switch 87%-Efficiency Boilers Special Instructions Water Piping Venting Appliance CategoriesModel 10F 20F 30F Min. Flow Max Flow Gpm Direct Venting Horizontal Through AL29-4CVent Terminal Location Vertical Venting CategoryCondensate Management Certified Maximum Combustion Air Air Inlet Model Venting Material Vent Length100’ Ducted 40’ 752AE Combustion Air 902AE 30’ 80’Direct Vent Horizontal Through- the-Wall Direct Vent Vertical Certified Vertical Venting Combustion Air Air Inlet302A 100’ 402A Galvanized Steel 502A 75’ Category 25’ 100’ 40’ 752A 902AWiring Diagram START-UP Pre Start-upMain Burner Adjustment Blower AdjustmentStart-Up Safety Inspection Leak Test Procedure Dual-Seat Gas ValvesFollow-Up Pilot Turn-Down TestPost Start-Up Check Leak TestLighting Instructions OperationTo Turn Off Gas To Appliance Troubleshooting StepSuggested Minimum Maintenance Schedule MaintenancePreventive Maintenance Schedule Weekly Semi-AnnuallyAnnually As RequiredAppendix Inside Air ContaminationLimited Parts Warranty HI Delta Types H and WH Limited Parts Warranty HI Delta Type P

302A-902A specifications

The Raypak 302A-902A is a highly regarded pool and spa heater, known for its efficiency and reliability in delivering warmth to residential and commercial aquatic applications. This heater stands out due to its robust design, advanced technology, and user-friendly features.

One of the key characteristics of the Raypak 302A-902A is its dual fuel capability, which means it can run on either natural gas or propane. This flexibility allows users to choose their preferred fuel type, contributing to operational efficiency and cost-effectiveness. With a BTU output ranging from 302,000 to 902,000, the Raypak heater is capable of quickly heating large volumes of water, making it ideal for pools, spas, and hot tubs.

The heater incorporates advanced technology such as a stainless steel heat exchanger, which not only ensures excellent thermal conductivity but also promotes durability against corrosion. This is especially advantageous in harsh environments, where exposure to chemicals can significantly impact the lifespan of traditional copper heat exchangers. The Raypak 302A-902A's heat exchanger is designed to withstand the rigors of constant use while maintaining high performance levels.

Another prominent feature of the Raypak 302A-902A is its digital display control system, which simplifies the operation and monitoring of the heater. Users can easily set and adjust temperatures, as well as access diagnostic information, all through an intuitive interface. This digital control not only enhances user experience but also aids in the timely maintenance of the unit.

Energy efficiency is another major selling point of the Raypak 302A-902A. The heater is designed with environmentally friendly practices in mind, utilizing a low NOx burner that minimizes harmful emissions. This not only meets environmental regulations but also makes it a greener alternative for heating needs.

In terms of installation, the compact design of the Raypak 302A-902A allows for versatile placement options, whether in a residential backyard or a commercial environment. Its user-friendly installation process ensures that homeowners and businesses alike can enjoy the benefits of heated water with minimal hassle.

Overall, the Raypak 302A-902A is an exemplary choice for anyone seeking a high-quality, efficient, and flexible pool and spa heating solution. Its combination of robust engineering, advanced technology, and user-focused features solidifies its position as a leader in the market, promising effective heating for years to come. Whether for personal enjoyment or commercial use, this heater delivers exceptional performance that meets diverse heating needs.