Johnson Controls 22 SEER Section Xiii Flaring Work and Piping Connections, Drain Piping

Page 12

898841-UIM-B-0113

1.In order to align the drain hose and drain cap, be sure to insert securely and vertically. Incline insertion will cause water leak- age.

2.After removing drain hose, be sure not to forget mounting drain cap.

3.Be sure to fix the drain hose with tape to the bottom of piping.

4.Prevent drain water from freezing in low temperature environ- ment.

When installing indoor unit’s drain hose outdoors, necessary mea- sure for frost protection should be taken to prevent drain water freezing.

Under low temperature environment (when outdoor tempera- ture under 32 °F), after cooling operation is executed, water in the drain hose could be frozen.

Once drain water is frozen, the drain hose will be blocked and water leakage may result from indoor unit.

DRAIN PIPING

If the extension drain hose has to pass through a room, make sure it's wrapped with commercially sold insulation.

The drain hose should point downward for easy drain flow.

If the drain hose provided with the indoor unit is too short, make sure you connect it with a field-provided drain hose.

When connecting the drain hose to the hard vinyl chloride pipe, make sure it's inserted securely into the pipe.

DRAIN HOSE JUNCTION

If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end. See Figure 18.

Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to Figure 18.

Attach the Insulation (Drain hose) to the drain hose. See Figure 19.

SHIELD PIPE

 

 

EXTENSION

INSIDE THE ROOM

DRAIN HOSE

DRAIN HOSE

 

FIGURE 18: Drain Hose Extension

SECTION XIII: FLARING WORK AND PIPING CONNECTIONS

FLARING WORK

Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.

1.Measure the distance between the indoor and outdoor units.

2.Cut the copper pipe about 6 to 8 inches (15 to 20 cm) longer than the measured distance with a pipe cutter.

COPPER

90° SLANTED UNEVEN ROUGH

PIPE

 

FIGURE 20: Pipe Cutting Approved Method

3.Use a pipe reamer or file to completely remove all burrs from the cut cross section of the pipe.

a.Put the end of the copper pipe in a downward direction to avoid having burrs drop in the piping.

PIPE

REAMER

POINT DOWN

FIGURE 21: Deburring Line Set

4.Remove flare nuts attached to indoor and outdoor units then put them on pipes that have completed burrs removal (not possible to put them on after flaring work).

5.Use a flaring tool to perform flaring work at the end of the copper pipe. Use the table below as a guideline when performing flaring work.

 

HANDLE

Outside Dia.

A

 

"A"

Inch

Inch

 

 

BAR

BAR

0.24

0~0.02

 

YOKE

0.37

0~0.02

 

 

 

 

0.47

0~0.02

 

CONE

0.63

0~0.04

 

 

 

 

0.75

0.04~0.05

INSULATION (DRAIN HOSE)

COPPER PIPE CLAMP HANDLE

FIGURE 22: Flaring Tools

RED ARROW MARK

DRAIN HOSE

FIGURE 19: Drain Hose Insulation

Insert the drain hose and drain cap into the drain port, making sure that it comes in contact with the back of the drain port, and then mount it. If the drain hose is not connected properly, leaking will occur.

6.Check your flaring work and if it's found to be defective, cut off the defective flare section and redo number 5.

SMOOTH ALL ROUND

INSIDE IS SHINY WITHOUT SCRATCHES

= IMPROPER FLARING =

INCLINED SURFACE CRACKED UNEVEN

DAMAGEDTHICKNESS

EVEN LENGTH

ALL ROUND

FIGURE 23: Proper and Improper Flaring

7. When flaring is complete, align the center of the pipes and suffi- ciently tighten the flare nut by hand.

12

Johnson Controls Unitary Products

Image 12
Contents Models 22 Seer UIM-B-0113Section II Safety Section I GeneralSection III Shipping and Packaging ListSection V Selecting Installation Location Indoor Unit see for Installation DimensionsRemote Control Assembled Outdoor UnitOutdoor Unit see for Installation Dimensions Condensate Drainage Requirement Heat Pump onlySection VI Specifications Power Supply and INDOOR/OUTDOOR Wire ConnectionHeat Pump Electrical Specifications Max. Fuse Size time delay aSection VII Refrigerant Line SET Requirements Heat PumpsUIM-B-0113 Refrigerant Line Set Requirements Connection Pipe length 24.624.6 Connection Pipe Gas 32.8 Max Distance Length 49.2Section Viii Unit Dimensions Section XI Indoor Unit Wiring Installing the Wall Mounting BracketConnections Wall Hole DrillingSection XII Pipe Forming and Drain Piping Pipe FormingWhite BlueRight or Right Rear Piping Left or Left Rear PipingRear or Downward Piping Section Xiii Flaring Work and Piping Connections Drain PipingDrain Hose Junction Flaring WorkSection XIV Indoor Unit Installation Section XV Outdoor Unit InstallationSlab or Roof Mounting Ft lbSection XVI Outdoor Unit Wiring Connections Securing Outdoor Unit to Slab or Frame9K & 12K 18K & 24kRefrigerant Piping Connections Indoor Unit ConnectionOutdoor Unit Connection 208-230V Systems 30 & 36 KbtuService Valves Insulation and TapingLeak Test and Evacuation AIR Purging with Vaccum PumpAdding Refrigerant for Longer Line SET Leak TestSection XX Maintenance Section Xviii Test OperationSection XIX Emergency Operation Section Xxii Typical Unit Wiring Diagram Cleaning and Maintenance18K & 24K 115V Indoor Air Conditioners 18K & 24K Indoor Air Conditioners 18K Indoor Air Conditioners 24K Indoor Air Conditioners 09K & 12K 115V Outdoor Heat Pumps 18K & 24K 115V Heat Pumps 18K & 24K Indoor Heat Pumps 18K Indoor Heat Pumps 24K Indoor Heat Pumps 30K Indoor Heat Pumps 36K Indoor Heat Pumps Johnson Controls Unitary Products Section Xxiii Indoor and Outdoor Units Error Codes Indoor Unit Front Panel IndicatorsIndoor Unit Error Codes Error Codes 09K 12KUIM-B-0113 Error Codes 09K 12K Display Method of Indoor UnitDuring cooling and drying 150VAC, turn on the unit after IPM OFF 3S Indicator has 3 kinds of display Error Codes 18K 24K Display Method of Outdoor Display Method of Indoor UnitWill stop operation IPM Temperature Blink Indoor fan will operate UIM-B-0113 Error Codes 30K 36K While operation frequency Ductless Splits Technical Train Min Showing during min. cooling or On 0.25s Operation, compressor will Ductless Splits Technical Train AC175V During heating operation Wiring terminal 4V is loos York International Corp York Drive Norman, OK

22 SEER specifications

Johnson Controls has long been a leader in the heating, ventilation, and air conditioning (HVAC) industry, consistently pushing the boundaries of energy efficiency and comfort. One of their standout offerings is the 22 SEER (Seasonal Energy Efficiency Ratio) air conditioning system, which boasts advanced technologies designed to deliver optimal performance while minimizing energy consumption.

At the heart of the Johnson Controls 22 SEER system is its innovative compressor technology. The variable-speed compressor allows for precise temperature control by adjusting the cooling output according to the specific demands of your space. This means that instead of constantly turning on and off, the system can operate at lower speeds for longer periods, ensuring even cooling and reducing energy bills.

In addition to the compressor, the 22 SEER unit employs high-efficiency coils and a superior refrigeration system that work in tandem to enhance performance. These components are designed to maximize heat transfer, enabling the system to cool your home more effectively and efficiently.

Another notable feature of the Johnson Controls 22 SEER system is its smart technology integration. With a focus on convenience and energy management, these units often come equipped with Wi-Fi connectivity, allowing homeowners to control their HVAC systems remotely using a smartphone app. This capability enhances user experience by enabling real-time monitoring and scheduling, ultimately leading to smarter energy use.

The design of the units also reflects an emphasis on quiet operation. Noise reduction technologies, including sound-dampening features, ensure that the system operates quietly in the background, enhancing indoor comfort without disruptive sounds.

Durability is another standout characteristic of the Johnson Controls 22 SEER systems. These units are built with high-quality materials and rigorous testing standards, ensuring they can withstand harsh weather conditions and provide reliable performance over the years.

Moreover, the 22 SEER air conditioning systems contribute to environmental sustainability. By using less energy, they not only lower utility costs but also reduce the carbon footprint of homes, aligning with growing consumer preferences for eco-friendly solutions.

Overall, the Johnson Controls 22 SEER air conditioning system represents a significant leap forward in HVAC technology. Its blend of efficiency, innovative features, and user-friendly technologies makes it an ideal choice for environmentally-conscious homeowners seeking comfort without compromise. Whether upgrading an existing system or investing in a new one, the 22 SEER unit stands out as a prime example of luxury, efficiency, and sustainability in the HVAC market.