349687-JTG-A-1007

TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSORS

 

ID

 

 

HEATER OPTION

 

MIN.

MAX.

MODEL

 

 

 

OD FAN

CONV

 

 

 

 

 

FUSE/

 

 

 

BLOWER

 

 

 

 

 

CIRCUIT

(TON-

VOLTAGE

RLA

LRA

MOTORS

OUTLET

 

 

 

 

 

BRKR1

MOTOR

MODEL

 

KW

STAGES

AMPS

AMPACITY

NAGE)

 

EACH

EACH

FLA EACH

FLA

AMPS

 

 

 

 

 

(AMPS)

SIZE

 

 

 

 

 

 

 

 

 

 

 

(AMPS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

 

0.0

~

~

84.2

100

 

 

 

 

 

 

 

E18

 

13.5

1

37.5

84.2

100

 

208

22.4

164

2.1

15.4

10.0

E36

 

27.0

2

75.1

125.4

150

 

 

 

 

 

 

 

E54

 

40.6

2

112.6

172.6

175

 

 

 

 

 

 

 

E72

 

54.1

2

150.1

181.9

200

 

 

 

 

 

 

 

None

 

0.0

~

~

83.2

100

 

 

 

 

 

 

 

E18

 

18.0

1

43.3

84.6

100

 

230

22.4

164

2.1

15.4

10.0

E36

 

36.0

2

86.6

138.8

150

 

 

 

 

 

 

 

E54

 

54.0

2

129.9

160.4

175

J15

 

 

 

 

 

 

E72

 

72.0

2

173.2

203.7

225

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

 

0.0

~

~

41.1

50

 

 

 

 

 

 

 

E18

 

18.0

1

21.7

42.3

50

 

460

10.9

100

1.1

7.2

5.0

E36

 

36.0

2

43.3

69.4

70

 

 

 

 

 

 

 

E54

 

54.0

2

65.0

80.2

90

 

 

 

 

 

 

 

E72

 

72.0

2

86.6

101.9

110

 

 

 

 

 

 

 

None

 

0.0

~

~

32.2

40

 

 

 

 

 

 

 

E18

 

18.0

1

17.3

34.0

40

 

575

8.3

78

0.9

5.9

4.0

E36

 

36.0

2

34.6

55.7

60

 

 

 

 

 

 

 

E54

 

54.0

2

52.0

64.3

70

 

 

 

 

 

 

 

E72

 

72.0

2

69.3

81.7

90

 

 

 

 

 

 

 

None

 

0.0

~

~

96.0

110

 

 

 

 

 

 

 

E18

 

13.5

1

37.5

96.0

110

 

208

25.6

190

2.1

20.0

10.0

E36

 

27.0

2

75.1

131.2

150

 

 

 

 

 

 

 

E54

 

40.6

2

112.6

178.4

200

 

 

 

 

 

 

 

E72

 

54.1

2

150.1

187.7

200

 

 

 

 

 

 

 

None

 

0.0

~

~

96.0

110

 

 

 

 

 

 

 

E18

 

18.0

1

43.3

96.0

110

 

230

25.6

190

2.1

20.0

10.0

E36

 

36.0

2

86.6

145.8

150

 

 

 

 

 

 

 

E54

 

54.0

2

129.9

167.4

175

J18

 

 

 

 

 

 

E72

 

72.0

2

173.2

210.7

225

(17 1/2)

 

 

 

 

 

 

None

 

0.0

~

~

48.2

60

 

 

 

 

 

 

 

E18

 

18.0

1

21.7

48.2

60

 

460

12.8

95

1.1

10.0

5.0

E36

 

36.0

2

43.3

72.9

80

 

 

 

 

 

 

 

E54

 

54.0

2

65.0

83.7

90

 

 

 

 

 

 

 

E72

 

72.0

2

86.6

105.4

110

 

 

 

 

 

 

 

None

 

0.0

~

~

39.0

45

 

 

 

 

 

 

 

E18

 

18.0

1

17.3

39.0

45

 

575

10.3

75

0.9

8.2

4.0

E36

 

36.0

2

34.6

58.6

60

 

 

 

 

 

 

 

E54

 

54.0

2

52.0

67.2

70

 

 

 

 

 

 

 

E72

 

72.0

2

69.3

84.5

90

NOTE 1: HACR Type per NEC.

26

Johnson Controls Unitary Products

Image 26
Contents DESCRIPTION SERIES SINGLE PACKAGE GAS/ELECTRIC UNITSAND SINGLE PACKAGE AIR CONDITIONERS TECHNICAL GUIDELIST OF TABLES TABLE OF CONTENTSLIST OF FIGURES J15 D J N24 A 2 A AA 1 0 1 2 4 A PRODUCT NOMENCLATURE15-25Ton Series 20 Model Number Nomenclature FEATURES FACTORY-INSTALLEDOPTIONS FIGURE 1 - UNIT CUTAWAY349687-JTG-A-1007 FIELD-INSTALLEDACCESSORIES CONTROL OPTIONS349687-JTG-A-1007 TABLE 3 GAS HEAT RATIINGS TABLE 1 SOUND POWER RATING1TABLE 2 CAPACITY RATINGS - ARI TABLE 4 COOLING CAPACITIES FOR J15DJ TABLE 5 COOLING CAPACITIES FOR J18DJ TABLE 6 COOLING CAPACITIES FOR J20DJ TABLE 7 COOLING CAPACITIES FOR J25DJ TABLE 8 ALTITUDE CORRECTION FACTORS FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR Johnson Controls Unitary Products230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT ANDDRIVE 208 VOLT ANDSTANDARD 208 VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT ANDDRIVE 208 VOLT ANDSTANDARD 208 VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT ANDTABLE 17 STATIC RESISTANCES1 TABLE 18 POWER EXHAUST PERFORMANCETABLE 16 BLOWER MOTOR AND DRIVE DATA COMPRESSORS NOTE 1 HACR Type per NEC Johnson Controls Unitary Products349687-JTG-A-1007 NOTE 1 HACR Type per NECNOTE 1 HACR Type per NEC Johnson Controls Unitary ProductsMODELS TABLE 21 J**DJ VOLTAGE LIMITATIONS1TABLE 22 PHYSICAL DATA J15DJTABLE 24 ELECTRIC HEAT CORRECTION FACTORS TABLE 23 SUPPLY FAN VFD WEIGHTS, IN LBSFIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAM HOLE FIGURE 4 - FRONT VIEW DIMENSIONSTABLE 25 UTILITIES ENTRY DATA USED FORField Accessories for Side FIGURE 5 - REAR VIEW DIMENSIONSDimensions listed are for side duct flange openings seeTABLE 26 MINIMUM CLEARANCES ROOF JACK INSTALLATION ROOF CURB INSTALLATION FIGURE 7 - UNIT CENTER OF GRAVITYFIGURE 8 - TYPICAL UNIT APPLICATIONS SLAB ON GROUND INSTALLATIONTotal FIGURE 9 - FOUR AND SIX POINT LOADSTABLE 27 FOUR AND SIX POINT LOADS 4 Point Loads lbsFIGURE 12 - CUT AWAY OF ROOF CURB FIGURE 10 - UNIT ROOF CURB DIMENSIONSFIGURE 11 - ROOF CURB DUCT OPENINGS DIMENSION Page DESCRIPTION GUIDE SPECIFICATIONSGENERAL UNIT CONTROLS OUTDOOR CONDENSER FAN ASSEMBLYREFRIGERANT COMPONENTS GAS HEATING SECTION J**DJN MODELSELECTRICAL REQUIREMENTS UNIT OPERATING CHARACTERISTICSELECTRIC HEATING J**DJC/E MODELS STANDARD LIMITED WARRANTIESOTHER PRE-ENGINEEREDACCESSORIES AVAILABLE