Johnson Controls J15 warranty Product Nomenclature, 15-25Ton Series 20 Model Number Nomenclature

Page 3
PRODUCT NOMENCLATURE

349687-JTG-A-1007

PRODUCT NOMENCLATURE

15-25 Ton Series 20 Model Number Nomenclature

J15 D J N24 A 2 A AA 1 0 1 2 4 A

Nominal Cooling Capacity

J15 = 15 Ton

J18 = 17.5 Ton

J20 = 20 Ton

J25 = 25 Ton

Product Category

D = A/C, Single Pkg., R-22

Product Identifier

J = 11.0+ EER A/C

Heat Type and Nominal Heat Capacity

C00 = Cooling Only. No field installed electric heat

Gas Heat Options

N24 = 240 MBH Output Aluminized Steel

N32 = 320 MBH Output Aluminized Steel

S24 = 240 MBH Output Stainless Steel

S32 = 320 MBH Output Stainless Steel

Electric Heat Options

E18 = 18 KW

E36 = 36 KW

E54 = 54 KW

E72 = 72 KW

Airflow

A = Std. Drive

B = Std. Drive/Single Input Econo.

C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only)

D = Std. Drive/Motorized Damper

E = Std. Drive/Motorized Damper/Barometric Relief J = Std. Drive/Single Input Econo./Barometric Relief N = Hi Static Drive

P = Hi Static Drive/Single Input Econo.

Q = Hi Static Drive/Single Input Econo./Power Exhaust (Downflow Only)

R = Hi Static Drive/Motorized Damper

K = Hi Static Drive/Motorized Damper/Barometric Relief S = Hi Static Drive/Single Input Econo./Barometric Relief

Voltage

2 = 208/230-3-60

4 = 460-3-60

5 = 575-3-60

Product Style

A = Style A

Configuration Options (not required for all units)

These four digits will not be assigned until a quote is requested, or an order placed.

SS Drain Pan

Johnson UNT 1126 Controller (N2 protocol), DFS, APS

Johnson Light Commercial Controls System (LCCS) Rtu Controller

Hot Gas Bypass (Standard on VAV, Optional on CV)

Variable Air Volume, VFD

Variable Air Volume, VFD and Manual Bypass

Variable Air Volume, VFD (BAS ready - for customer provided VFD controller)

Variable Air Volume, VFD and Manual Bypass (BAS ready)

Variable Air Volume, VFD Ready (for customer provided, field installed drive)

 

 

 

2" Pleated filters

 

 

 

 

 

4" Pleated filters

 

 

 

 

 

BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)

 

 

 

Double Wall Construction

 

 

 

 

 

 

 

For valid combinations of the above; see the equipment price pages or

 

 

 

 

 

the Unitary Sales Tool program; all combinations are not available

 

 

 

 

 

 

 

 

 

 

 

Product Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = First Generation

 

 

 

 

 

 

2 = Second Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional Options

 

 

 

 

 

 

 

 

 

 

 

Standard Cabinet

Hinged Filter Door & Tool Free Access Cabinet

 

 

 

 

 

 

 

 

 

 

AA = None

 

 

 

BA = Hinged Filter Door & Tool Free Access Panels

 

AB = Phase Monitor

 

 

 

BB = Phase Monitor, Hinged Filter Door & Tool Free

 

AC = Coil Guard

 

 

 

Access Panels

 

AD = Dirty Filter Switch

 

 

 

BC = Coil Guard, Hinged Filter Door & Tool Free

 

AE = Phase Monitor & Coil Guard

Access Panels

 

AF = Phase Monitor & Dirty Filter Switch

BD = Dirty Filter Switch, Hinged Filter Door &

 

AG = Coil Guard & Dirty Filter Switch

Tool Free Access Panels

 

AH = Phase Monitor, Coil Guard & Dirty Filter Switch

BE = Phase Monitor & Coil Guard, Hinged Filter

 

RC = Coil Guard & American Flag

Door & Tool Free Access Panels

 

TA = Technicoat Condenser Coil

BF = Phase Monitor & Dirty Filter Switch, Hinged

 

TJ = Technicoat Evaporator Coil

Filter Door & Tool Free Access Panels

 

TS = Technicoat Evaporator & Condenser Coils

BG = Coil Guard & Dirty Filter Switch, Hinged Filter

 

 

 

 

 

 

 

 

Door & Tool Free Access Panels

 

 

 

 

 

 

 

 

BH = Phase Monitor, Coil Guard & Dirty Filter Switch,

 

 

 

 

 

 

 

 

Hinged Filter Door & Tool Free Access Panels

 

 

 

 

 

 

 

 

ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be

 

 

located in digits 15-18.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation Options

 

 

 

 

 

 

 

 

 

 

A = No Options Installed

 

N = Options 2 & 3

 

 

 

B = Option 1

 

P = Options 2 & 4

 

 

 

C = Option 2

 

Q = Options 2, 3, & 4

 

 

 

D = Options 1 & 2

 

R = Options 3 & 4

 

 

 

E = Option 3

 

S = Option 5

 

 

 

F = Option 4

 

T = Options 1 & 5

 

 

 

G = Options 1 & 3

 

U = Options 1, 3, & 5

 

 

 

H = Options 1 & 4

 

V = Options 1, 4, & 5

 

 

 

J = Options 1, 2 & 3

 

W = Options 1, 3, 4, & 5

 

 

 

K = Options 1, 2, & 4

 

X = Options 3 & 5

 

 

 

L = Options 1,3 & 4

 

Y = Options 4 & 5

 

 

 

M = Options 1, 2, 3, & 4

 

Z = Options 3, 4 & 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

1 = Disconnect

 

4 = Smoke Detector R.A.

 

 

 

2 = Non-Pwr'd Conv. Outlet

 

5 = Pwr'd Conv. Outlet

 

 

 

3 = Smoke Detector S.A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Johnson Controls Unitary Products

3

Image 3
Contents TECHNICAL GUIDE SERIES SINGLE PACKAGE GAS/ELECTRIC UNITSAND SINGLE PACKAGE AIR CONDITIONERS DESCRIPTIONTABLE OF CONTENTS LIST OF FIGURESLIST OF TABLES PRODUCT NOMENCLATURE 15-25Ton Series 20 Model Number NomenclatureJ15 D J N24 A 2 A AA 1 0 1 2 4 A FEATURES FIGURE 1 - UNIT CUTAWAY FACTORY-INSTALLEDOPTIONS349687-JTG-A-1007 CONTROL OPTIONS FIELD-INSTALLEDACCESSORIES349687-JTG-A-1007 TABLE 1 SOUND POWER RATING1 TABLE 2 CAPACITY RATINGS - ARITABLE 3 GAS HEAT RATIINGS TABLE 4 COOLING CAPACITIES FOR J15DJ TABLE 5 COOLING CAPACITIES FOR J18DJ TABLE 6 COOLING CAPACITIES FOR J20DJ TABLE 7 COOLING CAPACITIES FOR J25DJ TABLE 8 ALTITUDE CORRECTION FACTORS Johnson Controls Unitary Products FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTORVOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575208 VOLT AND 208 VOLT ANDSTANDARD DRIVEVOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575VOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575208 VOLT AND 208 VOLT ANDSTANDARD DRIVEVOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575VOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575TABLE 18 POWER EXHAUST PERFORMANCE TABLE 16 BLOWER MOTOR AND DRIVE DATATABLE 17 STATIC RESISTANCES1 COMPRESSORS Johnson Controls Unitary Products NOTE 1 HACR Type per NECNOTE 1 HACR Type per NEC 349687-JTG-A-1007Johnson Controls Unitary Products NOTE 1 HACR Type per NECJ15DJ TABLE 21 J**DJ VOLTAGE LIMITATIONS1TABLE 22 PHYSICAL DATA MODELSTABLE 23 SUPPLY FAN VFD WEIGHTS, IN LBS FIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAMTABLE 24 ELECTRIC HEAT CORRECTION FACTORS USED FOR FIGURE 4 - FRONT VIEW DIMENSIONSTABLE 25 UTILITIES ENTRY DATA HOLEduct flange openings see FIGURE 5 - REAR VIEW DIMENSIONSDimensions listed are for side Field Accessories for SideTABLE 26 MINIMUM CLEARANCES SLAB ON GROUND INSTALLATION FIGURE 7 - UNIT CENTER OF GRAVITYFIGURE 8 - TYPICAL UNIT APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION4 Point Loads lbs FIGURE 9 - FOUR AND SIX POINT LOADSTABLE 27 FOUR AND SIX POINT LOADS TotalFIGURE 10 - UNIT ROOF CURB DIMENSIONS FIGURE 11 - ROOF CURB DUCT OPENINGS DIMENSIONFIGURE 12 - CUT AWAY OF ROOF CURB Page GUIDE SPECIFICATIONS GENERALDESCRIPTION GAS HEATING SECTION J**DJN MODELS OUTDOOR CONDENSER FAN ASSEMBLYREFRIGERANT COMPONENTS UNIT CONTROLSSTANDARD LIMITED WARRANTIES UNIT OPERATING CHARACTERISTICSELECTRIC HEATING J**DJC/E MODELS ELECTRICAL REQUIREMENTSOTHER PRE-ENGINEEREDACCESSORIES AVAILABLE