Johnson Controls J15 warranty Electric Heating J**Djc/E Models, Unit Operating Characteristics

Page 39

349687-JTG-A-1007

a.Primary and auxiliary high-temperature limit switches.

b.Induced draft motor speed sensor.

c.Flame roll out switch (automatic reset).

d.Flame proving controls. Unit shall have two inde- pendent stages of capacity.

ELECTRIC HEATING (J**DJC/E MODELS)

Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0° F. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER - Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring- return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi- tioned space during normal operation. During econo-

mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.

BAS-READY ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully- modulating, spring return damper actuator. The maxi- mum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG.

For units with optional VAV control, free-cooling shall be available while the outdoor dry bulb temperature (OAT) remains below a programmable set-point of the control- ler. Field-installed humidity sensors for either outdoor air or outdoor & return air streams are available to provide free-cooling based on single-enthalpy or dual-enthalpy configurations, respectively. If free-cooling is available, a call for cooling shall modulate the economizer in order to maintain a supply air temperature (SAT) programmable set-point. With the use of a field-installed indoor air qual- ity sensor, the controller shall provide Demand Ventila- tion by modulating the economizer dampers to allow more outside airflow upon detection of elevated indoor CO2 concentrations above a programmable set-point. With an additional field-installed outdoor air quality sen- sor, Differential Demand Ventilation shall be provided.

The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water elimina- tor/filters shall be provided.

Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2-position,spring-return damper actuator. The maxi- mum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi- tions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

Johnson Controls Unitary Products

39

Image 39
Contents TECHNICAL GUIDE SERIES SINGLE PACKAGE GAS/ELECTRIC UNITSAND SINGLE PACKAGE AIR CONDITIONERS DESCRIPTIONTABLE OF CONTENTS LIST OF FIGURESLIST OF TABLES PRODUCT NOMENCLATURE 15-25Ton Series 20 Model Number NomenclatureJ15 D J N24 A 2 A AA 1 0 1 2 4 A FEATURES FIGURE 1 - UNIT CUTAWAY FACTORY-INSTALLEDOPTIONS349687-JTG-A-1007 CONTROL OPTIONS FIELD-INSTALLEDACCESSORIES349687-JTG-A-1007 TABLE 1 SOUND POWER RATING1 TABLE 2 CAPACITY RATINGS - ARITABLE 3 GAS HEAT RATIINGS TABLE 4 COOLING CAPACITIES FOR J15DJ TABLE 5 COOLING CAPACITIES FOR J18DJ TABLE 6 COOLING CAPACITIES FOR J20DJ TABLE 7 COOLING CAPACITIES FOR J25DJ TABLE 8 ALTITUDE CORRECTION FACTORS Johnson Controls Unitary Products FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTORVOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575208 VOLT AND 208 VOLT ANDSTANDARD DRIVEVOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575VOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575208 VOLT AND 208 VOLT ANDSTANDARD DRIVEVOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575VOLT AND 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE 230/460/575TABLE 18 POWER EXHAUST PERFORMANCE TABLE 16 BLOWER MOTOR AND DRIVE DATATABLE 17 STATIC RESISTANCES1 COMPRESSORS Johnson Controls Unitary Products NOTE 1 HACR Type per NECNOTE 1 HACR Type per NEC 349687-JTG-A-1007Johnson Controls Unitary Products NOTE 1 HACR Type per NECJ15DJ TABLE 21 J**DJ VOLTAGE LIMITATIONS1TABLE 22 PHYSICAL DATA MODELSTABLE 23 SUPPLY FAN VFD WEIGHTS, IN LBS FIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAMTABLE 24 ELECTRIC HEAT CORRECTION FACTORS USED FOR FIGURE 4 - FRONT VIEW DIMENSIONSTABLE 25 UTILITIES ENTRY DATA HOLEduct flange openings see FIGURE 5 - REAR VIEW DIMENSIONSDimensions listed are for side Field Accessories for SideTABLE 26 MINIMUM CLEARANCES SLAB ON GROUND INSTALLATION FIGURE 7 - UNIT CENTER OF GRAVITYFIGURE 8 - TYPICAL UNIT APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION4 Point Loads lbs FIGURE 9 - FOUR AND SIX POINT LOADSTABLE 27 FOUR AND SIX POINT LOADS TotalFIGURE 10 - UNIT ROOF CURB DIMENSIONS FIGURE 11 - ROOF CURB DUCT OPENINGS DIMENSIONFIGURE 12 - CUT AWAY OF ROOF CURB Page GUIDE SPECIFICATIONS GENERALDESCRIPTION GAS HEATING SECTION J**DJN MODELS OUTDOOR CONDENSER FAN ASSEMBLYREFRIGERANT COMPONENTS UNIT CONTROLSSTANDARD LIMITED WARRANTIES UNIT OPERATING CHARACTERISTICSELECTRIC HEATING J**DJC/E MODELS ELECTRICAL REQUIREMENTSOTHER PRE-ENGINEEREDACCESSORIES AVAILABLE