Johnson Controls J15 Outdoor Condenser Fan Assembly, Refrigerant Components, Unit Controls

Page 38

Units equipped with VFD’s shall have factory-installed man- ual bypass as an option.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider brackets and shall be dynami- cally balanced for smooth operation. The 4 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.

REFRIGERANT COMPONENTS

Compressors:

a.Shall be Scroll compressors internally protected with internal high-pressure relief and over temperature protection.

b.Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting.

Coils:

a.Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

b.Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.

Refrigerant Circuit and Refrigerant Safety Components shall include:

a.Balance-port thermostatic expansion valve with independent circuit feed system.

b.Filter drier/strainer to eliminate any moisture or for- eign matter.

c.Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.

d.The refrigeration system shall provide at least 15° F of sub-cooling at design conditions.

e.All models shall have two independent circuits.

f.Hot gas bypass option shall be factory-installed on compressor #1 discharge line to provide cooling in low-load applications. HGBP shall be a standard feature on VAV models and an optional feature on CV models.

349687-JTG-A-1007

UNIT CONTROLS

a.Unit shall be complete with self-contained low-volt- age control circuit protected by a resetable circuit breaker on the 24-volt transformer side.

b.Unit shall incorporate a lockout circuit which pro- vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.

c.Loss-of-charge/Low-pressure switch.

1.High-pressure switch.

2.Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

d.Unit shall incorporate "AUTO RESET" compressor over temperature, over current protection.

e.Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.

f.Unit control board shall have on-board diagnostics and fault code display.

g.Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 °F.

h.Control board shall monitor each refrigerant safety switch independently.

i.Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.

GAS HEATING SECTION (J**DJN MODELS)

Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redun- dant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25° F. Burners shall be of the in- shot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol- lowing minimum protection:

38

Johnson Controls Unitary Products

Image 38
Contents DESCRIPTION SERIES SINGLE PACKAGE GAS/ELECTRIC UNITSAND SINGLE PACKAGE AIR CONDITIONERS TECHNICAL GUIDELIST OF TABLES TABLE OF CONTENTSLIST OF FIGURES J15 D J N24 A 2 A AA 1 0 1 2 4 A PRODUCT NOMENCLATURE15-25Ton Series 20 Model Number Nomenclature FEATURES FACTORY-INSTALLEDOPTIONS FIGURE 1 - UNIT CUTAWAY349687-JTG-A-1007 FIELD-INSTALLEDACCESSORIES CONTROL OPTIONS349687-JTG-A-1007 TABLE 3 GAS HEAT RATIINGS TABLE 1 SOUND POWER RATING1TABLE 2 CAPACITY RATINGS - ARI TABLE 4 COOLING CAPACITIES FOR J15DJ TABLE 5 COOLING CAPACITIES FOR J18DJ TABLE 6 COOLING CAPACITIES FOR J20DJ TABLE 7 COOLING CAPACITIES FOR J25DJ TABLE 8 ALTITUDE CORRECTION FACTORS FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR Johnson Controls Unitary Products230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT ANDDRIVE 208 VOLT ANDSTANDARD 208 VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT ANDDRIVE 208 VOLT ANDSTANDARD 208 VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT AND230/460/575 208 VOLT AND STANDARD DRIVE208 VOLT AND HIGH STATIC DRIVE VOLT ANDTABLE 17 STATIC RESISTANCES1 TABLE 18 POWER EXHAUST PERFORMANCETABLE 16 BLOWER MOTOR AND DRIVE DATA COMPRESSORS NOTE 1 HACR Type per NEC Johnson Controls Unitary Products349687-JTG-A-1007 NOTE 1 HACR Type per NECNOTE 1 HACR Type per NEC Johnson Controls Unitary ProductsMODELS TABLE 21 J**DJ VOLTAGE LIMITATIONS1TABLE 22 PHYSICAL DATA J15DJTABLE 24 ELECTRIC HEAT CORRECTION FACTORS TABLE 23 SUPPLY FAN VFD WEIGHTS, IN LBSFIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAM HOLE FIGURE 4 - FRONT VIEW DIMENSIONSTABLE 25 UTILITIES ENTRY DATA USED FORField Accessories for Side FIGURE 5 - REAR VIEW DIMENSIONSDimensions listed are for side duct flange openings seeTABLE 26 MINIMUM CLEARANCES ROOF JACK INSTALLATION ROOF CURB INSTALLATION FIGURE 7 - UNIT CENTER OF GRAVITYFIGURE 8 - TYPICAL UNIT APPLICATIONS SLAB ON GROUND INSTALLATIONTotal FIGURE 9 - FOUR AND SIX POINT LOADSTABLE 27 FOUR AND SIX POINT LOADS 4 Point Loads lbsFIGURE 12 - CUT AWAY OF ROOF CURB FIGURE 10 - UNIT ROOF CURB DIMENSIONSFIGURE 11 - ROOF CURB DUCT OPENINGS DIMENSION Page DESCRIPTION GUIDE SPECIFICATIONSGENERAL UNIT CONTROLS OUTDOOR CONDENSER FAN ASSEMBLYREFRIGERANT COMPONENTS GAS HEATING SECTION J**DJN MODELSELECTRICAL REQUIREMENTS UNIT OPERATING CHARACTERISTICSELECTRIC HEATING J**DJC/E MODELS STANDARD LIMITED WARRANTIESOTHER PRE-ENGINEEREDACCESSORIES AVAILABLE