FORM
described above), the microprocessor control board will continue to monitor the
If the call for cooling is still present at the conclusion of the ASCD, the microprocessor control will re- energize the compressor.
Should a
Condensate Overflow Switch
A Condensate Overflow fault occurs when the Condensate Overflow switch opens for more than two line cycles. The compressor is shutdown regardless of Minimum Run Time, ASCD is initiated, and alarm is tripped. The fan continues operating in its current state. Compressor will
The microprocessor control board logs the first incident per compressor request. If the compressor request is removed, the fault occurrence counter is reset to zero. Should the Condensate Overflow switch open three within two hours of run time, the microprocessor control board will
SAFETY CONTROLS
The microprocessor control monitors the following inputs:
1.A
2.A
3.A Condensate Overflow Switch to protect against condensate overflow.
Compressor Protection
In addition to the external pressure switches, the compressor also has inherent (internal) protection. If there is an abnormal temperature rise in a compressor, the internal protection will immediately shut down the compressor. The microprocessor control incorporates features to minimize compressor wear and damage. An
is utilized to prevent short cycling of the compressor. Additionally, a minimum run time is imposed any time a compressor is energized. The ASCD is initiated on unit
Microprocessor Control Unit Flash Codes
Various flash codes are utilized by the microprocessor control to aid in troubleshooting. Flash codes are distinguished by the short on and off cycle used (approximately 200ms on and 200ms off). To show normal operation, the control boards flash a 1 second on, 1 second off “heart beat” during normal operation. This is to verify that the microprocessor is functioning correctly. Do not confuse this with an error flash code. To avoid confusion the
24 | JOHNSON CONTROLS |