GENERAL INFORMATION
All models are shipped as
The 5 ton unit utilizes a single compressor. All 8 ~ 20 ton models are dual compressor units with two independent refrigerant circuits. All units come standard with a microprocessor control board (refer to ‘Microprocessor’ section).
ONLY QUALIFIED PERSONNEL SHOULD PERFORM INSTALLATION AND SERVICE OF THIS EQUIPMENT.
All units are factory tested to ensure safe operation and quality assembly. Units are packaged and sealed on shipping skids and shipped in first class condition. Torn and broken packaging, scratched or dented panels should be reported to carrier immediately. Internal inspection of all units should be performed prior to installation. Remove all access doors and check for visual defects that can occur during transport. Any problems found internally should be reported to carrier and manufacturer immediately. Refrigerant circuit should be checked to ensure no leaks have occurred during shipment. Install gauge set to high and low pressure ports to confirm pressure has been maintained and no leaks have occurred during shipment. Repair any damage prior to installation to ensure safe operation.
Record any unit damage on the Bill of Lading and report to carrier and factory immediately. Shipping and handling damages are not warranty items.
RIGGING
PRIOR TO MOUNTING UNIT, CHECK INDIVIDUAL UNIT WEIGHTS (PAGE 10) AND VERIFY LIFTING CAPACITY OF LIFTING EQUIPMENT EXCEEDS WEIGHT OF UNITS BY SAFE MARGINS. FAILURE TO DO SO MAY RESULT IN UNIT DAMAGE, PERSONAL INJURY OR EVEN DEATH.
To ensure safe installation of the unit when ceiling mount application is specified, estimate the approximate center of gravity of the unit. The configuration of internal components for each unit is different and weight is unevenly distributed.
DETERMINE THE ACTUAL CENTER OF GRAVITY OF THE UNIT BY PERFORM- ING A TEST LIFT. LIFTING AN UNBAL- ANCED UNIT CAN CAUSE PERSONAL INJURY OR EVEN DEATH.
INSTALLATION SITE
LOCK ALL ELECTRICAL POWER SUP- PLY SWITCHES IN THE OFF POSITION BEFORE INSTALLING THE UNIT. FAIL- URE TO DISCONNECT POWER SUPPLY MAY RESULT IN ELECTRICAL SHOCK OR EVEN DEATH.
Location - To ensure unit operates at maximum efficiencies, choose a dry indoor area where the temperature is controlled between 50°F and 115°F. Consideration of surrounding areas should be taken when choosing a location to install the unit. Common vibration and sound levels associated with commercial equipment may be objectionable to people or equipment.
Failure to allow adequate space between units may result in poor unit perfor- mance and possible unit failure.
Install thermostats, air supplies and returns so that each unit will operate only on individual unit control. To assure fast drainage of condensate
CSV Operating Weight
Unit | Operating | Shipping | |
Weight (Lbs) | Weight (Lbs) | ||
| |||
|
|
| |
CSV060B | 590 | 635 | |
CSV096B | 795 | 835 | |
CSV120B | 955 | 995 | |
CSV180B | 1310 | 1365 | |
CSV240B | 1465 | 1525 |