Johnson Controls 341426-BIM-A-0108 installation manual Superheat Charging Table for DYA042

Page 20

341426-BIM-A-0108

TABLE 14: SUPERHEAT CHARGING TABLE FOR DYA042

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM

 

 

 

 

 

 

INDOOR WB TEMP. (°F)

 

 

 

 

TEMP. °F

 

 

 

 

 

 

 

 

 

55

57

59

61

63

65

67

69

71

73

75

65

18.0

19.7

21.4

23.0

24.7

26.3

28.0

29.1

30.2

31.3

32.4

70

13.4

15.3

17.3

19.3

21.2

23.2

25.2

26.6

28.1

29.6

31.1

75

8.7

10.9

13.2

15.5

17.8

20.0

22.3

24.2

26.1

28.0

29.9

80

-

6.6

9.1

11.7

14.3

16.9

19.5

21.7

24.0

26.3

28.6

85

-

-

5.1

7.9

10.8

13.7

16.6

19.3

21.9

24.6

27.3

90

-

-

-

6.7

9.3

11.9

14.6

17.4

20.2

23.1

25.9

95

-

-

-

5.5

7.8

10.2

12.5

15.5

18.5

21.5

24.5

100

-

-

-

-

6.3

8.0

9.8

12.9

16.1

19.2

22.4

105

-

-

-

-

-

5.9

7.1

10.3

13.7

16.9

20.3

110

-

-

-

-

-

-

-

7.8

11.2

14.7

18.1

115

-

-

-

-

-

-

-

5.2

8.8

12.4

16.0

TABLE 15: SUPERHEAT CHARGING TABLE FOR DYA048

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM

 

 

 

 

 

 

INDOOR WB TEMP. (°F)

 

 

 

 

TEMP. °F

 

 

 

 

 

 

 

 

 

55

57

59

61

63

65

67

69

71

73

75

65

20.9

21.8

22.7

23.6

24.4

25.3

26.2

27.4

28.6

29.8

31.0

70

17.6

18.7

19.7

20.7

21.7

22.7

23.7

25.2

26.6

28.1

29.6

75

14.4

15.5

16.6

17.8

18.9

20.0

21.2

22.9

24.7

26.4

28.2

80

11.1

12.4

13.6

14.9

16.1

17.4

18.6

20.7

22.7

24.8

26.8

85

7.8

9.2

10.6

12.0

13.3

14.7

16.1

18.4

20.8

23.1

25.4

90

5.8

7.0

8.2

9.3

10.5

11.7

12.9

15.7

18.6

21.5

24.4

95

-

-

5.8

6.7

7.7

8.6

9.6

13.0

16.5

19.9

23.3

100

-

-

5.4

6.0

6.7

7.4

8.0

11.6

15.2

18.7

22.3

105

-

-

-

5.3

5.7

6.1

6.5

10.2

13.9

17.6

21.3

110

-

-

-

-

-

-

-

8.7

12.6

16.4

20.3

115

-

-

-

-

-

-

-

7.3

11.3

15.3

19.3

TABLE 16: SUPERHEAT CHARGING TABLE FOR DYA060

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM

 

 

 

 

 

 

INDOOR WB TEMP. (°F)

 

 

 

 

TEMP. °F

 

 

 

 

 

 

 

 

 

55

57

59

61

63

65

67

69

71

73

75

65

7.0

9.2

11.4

13.6

15.9

18.1

20.3

21.8

23.2

24.7

26.1

70

6.1

8.4

10.7

13.0

15.2

17.5

19.8

21.2

22.7

24.1

25.6

75

5.3

7.6

9.9

12.3

14.6

16.9

19.3

20.7

22.2

23.6

25.0

80

-

6.8

9.2

11.6

14.0

16.3

18.7

20.2

21.6

23.1

24.5

85

-

6.0

8.4

10.9

13.3

15.8

18.2

19.6

21.1

22.5

23.9

90

-

-

6.5

8.7

10.8

12.9

15.1

17.1

19.1

21.1

23.1

95

-

-

-

6.5

8.3

10.1

11.9

14.5

17.1

19.7

22.3

100

-

-

-

5.9

7.3

8.6

10.0

12.9

15.8

18.7

21.6

105

-

-

-

5.3

6.2

7.1

8.0

11.3

14.5

17.7

20.9

110

-

-

-

-

5.2

5.6

6.1

9.6

13.2

16.7

20.2

115

-

-

-

-

-

-

-

8.0

11.8

15.7

19.6

20

Johnson Controls Unitary Products

Image 20
Contents Installation Manual Table of Contents General ApprovalsInspection Renewal PartsInstallation LimitationsUnit Application Data LocationUnit Weights and Center of Gravity Service AccessDuct Work Roof CurbCompressors Power and Control WiringThermostat Natural GAS Application Data PROPANE1 LP GAS Application DataNatural GAS Pipe Sizing CHART1 Propane LP GAS Pipe Sizing CHART1GAS Piping GAS ConnectionFlue Vent Hood Flue Vent Outlet AIR HoodPhysical Data Electrical DataUnit Dimensions Front Unit Minimum CLEARANCES1Unit Dimensions Front & Bottom Sequence of Operation HeatingPost Purge START-UP Pilot Instructions Manifold GAS Pressure AdjustmentPOST-START Check List GAS Adjustment of Temperature Rise Checking GAS InputGase Rate Cubic Feet PER HOUR1 Checking Supply AIR CFMDYA Coil Delta P vs Airflow Superheat Charging Table for DYA060 Superheat Charging Table for DYA042Superheat Charging Table for DYA048 BIM-A-0108 BIM-A-0108 Typical Wiring Diagram Notes See Figures 14Typical Wiring Diagram Legend