5. INSTALLATION INSTRUCTIONS
Filter Installation
Matrix Filters are supplied in the following mechanical configurations:
Panel mounted assemblies
Floor mounted general purpose NEMA 1, 2, & 3R cabinets
Industrial style NEMA 1 cabinets with hinged doors.
Panel mounted filters are designed for mounting in the vertical plane in the customer’s enclosure. Include the power dissipation of the filter along with all the other components located in the panel to determine the internal temperature rise and cooling requirements of the enclosure. Allow a minimum side clearance of four (4) inches and a vertical clearance of six (6) inches for proper heat dissipation and access. Figure 7 through Figure 15 contain outline drawings for the various ratings and show proper mounting orientation. For 5% filters, Model numbers beginning with 37GM5, refer to Figure 15 and Table 5 for the dimensions of the separately mounted input reactor.
Select a well ventilated,
Avoid locations where the filter would be subjected to excessive vibrations.
General purpose NEMA 1, 2, and 3R enclosed filters are designed for floor mounting in the vertical plane in an environment suitable for the enclosure type. Do not install in or near a corrosive environment. Avoid locations where the filter would be subjected to excessive vibrations. Allow a minimum side and back clearance of eight (8) inches and front clearance of
GE Capacitor & Power Quality Products
Industrial style NEMA 1 enclosed filters are designed for wall and floor mounting in the vertical plane. Do not install in or near a corrosive environment. Avoid locations where the filter would be subjected to excessive vibrations. For wall mounted enclosures allow a minimum side clearance of eight (8) inches and front clearance of
Figure 20 through
Figure 24.