GE SERIES B 480 user manual Agency Approvals, Performance

Page 9

g

GE Capacitor & Power Quality Products

SPECIFICATIONS - continued

Ambient Temperature (Operating)

 

Enclosed Filters:

-40 to +40 degrees C

Open Panel Filters:

-40 to +50 degrees C

Storage Temperature:

-40 to +90 degrees C

Altitude: 0 to 3300 Feet above sea level. Refer to Figure 6 for altitude derating.

Relative Humidity: 0 to 95% non-condensing

Agency Approvals

UL-508C

File E191686 Component Recognized

 

(3-1000 HP, 120 VAC through 600 VAC

 

50, 50/60, 60 Hz Three Phases

CAN/CSA

C22, 2 No. 14-95

Performance

Total Harmonic Current Distortion:

 

Eight Percent Filter: 8% typical at full load

12% maximum no load to full load

Five Percent Filter: 5% typical at full load

8% maximum no load to full load

Standby Current:

 

Without Optional Capacitor Contactor: 70% of the full load capacitor current listed in Table 3

With Optional Capacitor Contactor: Refer to Drive Users Manual

8% Filter Voltage Regulation with nominal 480 volts RMS source Maximum output voltage at no load: 502 volts RMS, 710 volts peak

Maximum PCC* voltage with 6.00% source impedance at no load: 490 volts RMS, 693 volts peak

Minimum output voltage at full load: 460 volts RMS, 600 volts peak

5% Filter Voltage Regulation with nominal 480 volts RMS source Maximum output voltage at no load: 502 volts RMS, 710 volts peak

Maximum PCC voltage with 6.00% source impedance at no load: 490 volts RMS, 693 volts peak

Minimum output voltage at full load: 460 volts RMS, 600 volts peak

*Note: PCC is the point of common coupling with the power distribution system

GEH-7252

6

May 2003

Image 9
Contents Matrix Filter  Important User Information Table of Contents Important Safety Information GE Capacitor & Power Quality Products Upon Receipt of this Filter IntroductionModel Number Codes Specifications Ratings Performance Agency ApprovalsVolt, 60 Hz Series B Matrix Filter Weights VAC Matrix Filters Capacitor Current at Full Load Matrix Filter Harmonic Spectrum 100% Load Filter 30% Load Nominal Thid UnbalanceFactor Derating Current Altitude FeetAltitude Derating Curve Filter Installation Installation InstructionsInstallation Instructions Installation Instructions 34 44 Amps, 480 VAC 60Hz Outline Drawing 52 66 Amps, 480 VAC 60Hz Outline Drawing 83 128 Amps, 480 VAC 60Hz Outline Drawing 165 240 Amps, 480 VAC 60Hz Outline Drawing 320 482 Amps, 480 VAC 60Hz Vertical Mounting Outline Drawing Installation Instructions Panel Mounted Filter Input Reactor Mounting Dimensions Installation Instructions CAB-17B CAB-20B CAB-30B CAB-42B Nema Cabinet-002 Cabinet-003 Cabinet Cabinet-006 Grounding and Ground Fault Protection Filter Input Terminals Output Terminals RatingAmps Input and Output Terminal SpecificationsInstallation Instructions Installation Instructions Capacitor Assembly Terminal Specifications Installation Instructions Front View TOP View Installation Instructions Front View Amps, 480 VAC 60Hz Industrial Enclosures Installation Instructions Installation Instructions Installation Instructions Installation Instructions Filter Description VAC 60Hz Block Diagram Safety Precautions START-UPSequence of Operation GE Capacitor & Power Quality Products Problem TroubleshootingLine voltage is not present at the filter Output terminalsPhases at full load Harmonic current distortion exceeds 8% on one or moreHarmonic current distortion exceeds 5% on one or more Filter output voltage is not within specification