GE SERIES B 480 user manual Troubleshooting, Problem, Line voltage is not present at the filter

Page 51

g

GE Capacitor & Power Quality Products

TROUBLESHOOTING

WARNING

WARNING

When properly installed, this equipment has been designed to provide maximum safety for operating personnel. However, hazardous voltages exist within the confines of the enclosure. Servicing should therefore be performed by qualified personnel only and in accordance with OSHA Regulations.

To aid in troubleshooting, a block diagram is shown in Figure 38, and a list of potential problems and solutions are listed below.

HIGH VOLTAGE IS USED IN THE OPERATION OF THIS FILTER. USE EXTREME CAUTION TO AVOID CONTACT WITH HIGH VOLTAGE WHEN OPERATING, INSTALLING OR REPAIRING THIS FILTER. INJURY, DEATH AND/OR PROPERTY DAMAGE MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.

After removing power, allow at least five minutes to elapse and verify that the capacitors have discharged to a safe level before contacting internal components. Connect a DC voltmeter across the capacitor terminals 1, 2 and 3 on terminal block 1TB. Start with the meter on the highest scale and progressively switch to a lower scale as the indicated voltage falls below the maximum value of the scale used.

PROBLEM:

Line voltage is not present at the filter

 

output terminals.

 

 

Possible cause:

Power to the filter is turned off.

 

 

Solution:

Turn power on.

 

 

Possible cause:

One or more external line fuses are blown.

 

 

Solution:

Verify the continuity of line fuses in all

 

phases. Replace as necessary.

 

 

.

GEH-7252

48

May 2003

Image 51
Contents Matrix Filter  Important User Information Table of Contents Important Safety Information GE Capacitor & Power Quality Products Upon Receipt of this Filter IntroductionModel Number Codes Specifications Ratings Performance Agency ApprovalsVolt, 60 Hz Series B Matrix Filter Weights VAC Matrix Filters Capacitor Current at Full Load Matrix Filter Harmonic Spectrum 100% Load Filter 30% Load Nominal Thid UnbalanceFactor Derating Current Altitude FeetAltitude Derating Curve Filter Installation Installation InstructionsInstallation Instructions Installation Instructions 34 44 Amps, 480 VAC 60Hz Outline Drawing 52 66 Amps, 480 VAC 60Hz Outline Drawing 83 128 Amps, 480 VAC 60Hz Outline Drawing 165 240 Amps, 480 VAC 60Hz Outline Drawing 320 482 Amps, 480 VAC 60Hz Vertical Mounting Outline Drawing Installation Instructions Panel Mounted Filter Input Reactor Mounting Dimensions Installation Instructions CAB-17B CAB-20B CAB-30B CAB-42B Nema Cabinet-002 Cabinet-003 Cabinet Cabinet-006 Grounding and Ground Fault Protection Filter Input Terminals Output Terminals RatingAmps Input and Output Terminal SpecificationsInstallation Instructions Installation Instructions Capacitor Assembly Terminal Specifications Installation Instructions Front View TOP View Installation Instructions Front View Amps, 480 VAC 60Hz Industrial Enclosures Installation Instructions Installation Instructions Installation Instructions Installation Instructions Filter Description VAC 60Hz Block Diagram Safety Precautions START-UPSequence of Operation GE Capacitor & Power Quality Products Output terminals TroubleshootingProblem Line voltage is not present at the filterPhases at full load Harmonic current distortion exceeds 8% on one or moreHarmonic current distortion exceeds 5% on one or more Filter output voltage is not within specification