GE SERIES B 480 user manual Specifications Ratings

Page 8

g

4.SPECIFICATIONS Ratings

GE Capacitor & Power Quality Products

Table 1

480 VAC, 60 Hz SERIES B Filter Ratings

 

THID Rating

 

8%

 

5%

 

 

 

 

 

 

 

 

 

Maximum

Efficiency

Power Dissipation

Efficiency

Power Dissipation

 

 

@ Rated Current

@ Rated Current

 

 

Output Amps

(Typical)

(Typical)

 

 

(Typical)

(Typical)

 

 

RMS

(%)

(%)

 

 

(Watts)

(Watts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

97.2

139

97.4

132

 

 

8

97.5

164

97.6

161

 

 

11

97.8

200

97.8

197

 

 

14

98.0

233

98.0

232

 

 

21

98.3

299

98.3

294

 

 

27

98.4

351

98.5

343

 

 

34

98.6

406

98.6

399

 

 

44

98.7

479

98.7

472

 

 

52

98.8

539

98.8

533

 

 

66

98.9

626

98.9

621

 

 

83

98.9

740

98.9

735

 

 

103

99.0

850

99.0

844

 

 

128

99.1

964

99.1

959

 

 

165

99.2

1143

99.2

1145

 

 

208

99.2

1355

99.2

1361

 

 

240

99.3

1493

99.2

1498

 

 

320

99.3

1829

99.3

1838

 

 

403

99.4

2110

99.4

2098

 

 

482

99.4

2393

99.4

2371

 

 

636

99.4

2978

99.4

2929

 

 

786

99.5

3432

99.5

3402

 

Service Conditions

Load: 6 pulse variable torque rectifier only

Input voltage: 480 VAC +/- 10%, 60 + 0.75 Hz, 3 phase

Input voltage line unbalance: 1% maximum

Maximum source impedance: 6.00%

Minimum source impedance: 1.5%

Service Factor: 1.00

GEH-7252

5

May 2003

Image 8
Contents Matrix Filter  Important User Information Table of Contents Important Safety Information GE Capacitor & Power Quality Products Introduction Upon Receipt of this FilterModel Number Codes Specifications Ratings Agency Approvals PerformanceVolt, 60 Hz Series B Matrix Filter Weights VAC Matrix Filters Capacitor Current at Full Load Matrix Filter Harmonic Spectrum 100% Load Unbalance Filter 30% Load Nominal ThidAltitude Derating Curve Factor Derating CurrentAltitude Feet Installation Instructions Filter InstallationInstallation Instructions Installation Instructions 34 44 Amps, 480 VAC 60Hz Outline Drawing 52 66 Amps, 480 VAC 60Hz Outline Drawing 83 128 Amps, 480 VAC 60Hz Outline Drawing 165 240 Amps, 480 VAC 60Hz Outline Drawing 320 482 Amps, 480 VAC 60Hz Vertical Mounting Outline Drawing Installation Instructions Panel Mounted Filter Input Reactor Mounting Dimensions Installation Instructions CAB-17B CAB-20B CAB-30B CAB-42B Nema Cabinet-002 Cabinet-003 Cabinet Cabinet-006 Grounding and Ground Fault Protection Input and Output Terminal Specifications Filter Input Terminals Output Terminals RatingAmpsInstallation Instructions Installation Instructions Capacitor Assembly Terminal Specifications Installation Instructions Front View TOP View Installation Instructions Front View Amps, 480 VAC 60Hz Industrial Enclosures Installation Instructions Installation Instructions Installation Instructions Installation Instructions Filter Description VAC 60Hz Block Diagram Sequence of Operation Safety PrecautionsSTART-UP GE Capacitor & Power Quality Products Troubleshooting ProblemLine voltage is not present at the filter Output terminalsHarmonic current distortion exceeds 5% on one or more Phases at full loadHarmonic current distortion exceeds 8% on one or more Filter output voltage is not within specification