Broan HRV90HT, ERV90HCT installation instructions Balancing the Unit

Page 21

7. BALANCING THE UNIT

To avoid balancing, the difference between stale air ducts total length and fresh air ducts total length must not exceed 50 ft. However, even if the stale air ducts and fresh air ducts lengths are almost equal, your local building codes may require balancing the unit.

If the unit does not need to be balanced, shut all the pressure taps (located on the unit door) with the small plastic plugs included in the hardware kit.

7.1WHAT YOU NEED TO BALANCE THE UNIT

• A magnehelic gauge capable of measuring 0 inch to 0.5 inch of water (0 Pa to 125 Pa) and 2 plastic tubes.

• The balancing chart located on the unit door.

VP0009

7.2PRELIMINARY STAGES TO BALANCE THE UNIT

Seal all the unit ductwork with tape. Close all windows and doors.

Turn off all exhaust devices such as range hood, dryer and bathroom fans.

Make sure the integrated balancing dampers are fully open. Turn the thumb screw (A) clockwise to manually open the dampers. Both are located on the Exhaust air to outside port and on Fresh air to building port.

Make sure all filters are clean (if it is not the first time you balance the unit).

A

VJ0032

PORT WITH INTEGRATED BALANCING DAMPER - TOP VIEW

7.3BALANCING PROCEDURE

1.Set the unit to high speed.

Make sure that the furnace/air handler blower is ON if the installation is in any way connected to the ductwork of the cold air return. If not, leave furnace/air handler blower OFF. If the outside temperature is below 0°C / 32°F, make sure the unit is not running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.).

2.Place the magnehelic gauge on a level surface and adjust it to zero.

3.Connect tubing from gauge to EXHAUST air flow pressure taps (see diagram beside). Be sure to connect the tubes to their appropriate high/low fittings. If the gauge drops below zero, reverse the tubing connections.

NOTE: It is suggested to start with the exhaust air flow reading because the exhaust has typically more restriction than the fresh air, especially in cases of fully ducted installations or source point ventilation.

BALANCING

 

 

 

 

CHART

 

 

 

 

 

 

 

 

FRESH AIR FLOW

1

12

12

11

 

1

12

12

11

 

3 13 33 23

EXHAUST AIR FLOW

1

12

12

11

1

12

12

11

3 13 33 23

VP0015

 

 

 

 

Place the magnehelic gauge upright and level. Record equivalent AIR FLOW of the reading according to the balancing chart.

4.Move tubing to FRESH air flow pressure taps (see diagram). Adjust the fresh air balancing damper until the fresh air flow is approximately the same as the EXHAUST air flow. If fresh air flow is less than exhaust air flow, then go back and adjust the exhaust balancing damper to equal the fresh air flow.

5.Secure both dampers thumb screw in place with tape.

6.Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone number and business address).

NOTE: The unit is considered balanced even if there is a difference of ±10 cfm (or ± 5 l/s or 17 m³/h) between the two air flows.

- 21 -

Image 21
Contents Installation Instructions HRV90H and ERV90HC About These Units Limitation About this ManualTable of Contents 42 lb 19 kg Technical DataIT 5 127 MM Ducts 12 MMHRV Units Technical Data CONT’DHRV Typical Installations Typical Installations CONT’D Installation Make sure the unit is level Installation CONT’DStale air exhaust ductwork Fresh air distribution ductworkMethod 1 Supply side connection Method 2 Return side connectionFurnace/air handler blower operation see Section Fresh air distribution Stale air intakeDo not use screws to connect the rigid ducts to the ports Insulated flexible ductsRigid ducts 457 mm Xmas Tree PIN 457 MM 152 MM Avertissement ControlsAIN Wall Controls CONT’DFor a furnace connected to a cooling system Electrical Connection to the FurnaceDiagram 6WIRINGBalancing the Unit Connecting the Drain HRV Units only Maintenance Maintenance CONT’D HRV90HS HRV90HT ERV90HCS ERV90HCT Service PartsProblems Possible causes You should try this TroubleshootingPiezas Problemas Causas posibles Debería hacer esto Solución DE ProblemasManual DE Instalación Modelos HRV90H Y ERV90HC Acerca DE Estos Aparatos Limitación Acerca DE Este ManualAdvertancia CuidadoÍndice Ubos DE 5 127 MM Datos TécnicosRendimiento DE Ventilación Datos Técnicos ContinuaciónDimensiones Encendido Instalaciones HabitualesInstalaciones Habituales Continuación Instalación Compruebe que el aparato esté a nivel Tubos de extracción de aire viciadoTubos de distribución del aire puro Método 2 Conexión por el lado de retorno Método 1 Conexión por el lado de la alimentaciónDistribución del aire puro Admisión de aire viciadoTubos flexibles aislados 457 mm VD0087TORNILLO 18 457 MM Control Integrado ControlesControles Continuación Conexión Eléctrica CON LA Caldera Cableado de interbloqueo estándar de la calderaCableado de interbloqueo alternativo de la caldera Aparato 6DIAGRAMADE CableadosAntes de efectuar cualquier ReparaciónPonga el aparato en velocidad alta Equilibrado DEL AparatoConexión DEL Desagüe Aparatos HRV Únicamente Maintenimiento Semestral MantenimientoMantenimiento Continuación Piezas Solución DE Problemas
Related manuals
Manual 52 pages 11.89 Kb

HRV90HT, ERV90HCT specifications

The Broan ERV90HCT and HRV90HT are remarkable energy recovery ventilators designed to enhance indoor air quality while promoting energy efficiency in residential settings. Both models are built with innovative technologies that meet the demands of modern homes, ensuring a comfortable living environment.

One of the standout features of the Broan ERV90HCT and HRV90HT is their energy recovery capabilities. They efficiently exchange stale indoor air with fresh outdoor air, recovering up to 90% of the energy that would otherwise be lost. This process not only improves air quality but also helps in reducing heating and cooling costs, making them an excellent investment for energy-conscious homeowners.

Another significant characteristic of both models is their quiet operation. Equipped with advanced fan technology, the ERV90HCT and HRV90HT work at minimal noise levels, ensuring a peaceful indoor atmosphere. Whether in a bedroom, living room, or office, occupants can enjoy the benefits of fresh air without disruptive noise.

The units are designed with user-friendly controls that make operation simple and intuitive. Homeowners can easily adjust settings to optimize airflow based on current needs, whether it’s high ventilation during peak usage times or lower settings for quieter moments. Additionally, the units come with a built-in timer, allowing for customizable operation schedules.

Durability is another hallmark of the Broan ERV90HCT and HRV90HT. Constructed with high-quality materials, these ventilators are designed for long-lasting performance. Furthermore, their compact design allows for flexible installation options, making them suitable for various home layouts and sizes.

The ERV90HCT features a heat recovery system, making it ideal for climates that experience significant temperature fluctuations, while the HRV90HT is tailored for those residing in colder regions. Both units utilize an efficient balanced ventilation system, ensuring that airflow is evenly distributed throughout the home.

In summary, the Broan ERV90HCT and HRV90HT are top-tier energy recovery ventilators that prioritize comfort, efficiency, and air quality. With their energy recovery capabilities, quiet operation, user-friendly controls, durability, and flexible installation options, they stand out in the market as excellent solutions for maintaining a healthy home environment. Whether seeking to reduce energy costs or improve indoor air quality, these models deliver on all fronts, making them a worthy addition to any household.