11. TROUBLESHOOTING

If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on the unit the problem occurs.

LED flashes GREEN. LED flashes AMBER. LED flashes RED.

• Thermistor error.

Replace the entire port assembly (fresh air from outside port).

• Damper error.

Go to Point 6.

The door is open and the unit is not unplugged. Close the door and press once on the integrated control push button to reset the unit.

• Exhaust motor error.

Go to Point 5.

Problems

Possible causes

You should try this

1. Unit does not work.

•The circuit board may be defective.

•Unplug the unit. Disconnect the main control and the auxiliary control(s) (if need be). Jump G and B terminals. Plug the unit back and wait about 10 seconds. If the motors run on high speed and the damper opens, the circuit board is not defective.

NO C NC I OC OL Y R G B

VE0097

2. The damper actuator

•The damper actuator or the integrated

does not work.

damper port mechanism may be defective.

•The circuit board may be defective.

•Unplug the unit. Disconnect the main control and the optional control(s) (if need be). Wait 10 seconds and plug the unit back. Check if the damper opens. If not, use a multimeter and check for 24V AC on J12-1 and J12-2 (in electrical compartment). If there is 24V AC, replace the entire port assembly. NOTE: It is normal to experience a small delay (7-8 seconds) before

detecting the 24V AC signal at starting-up. This signal will stay during 17-18 seconds before disappearing.

•If there is no 24V AC, replace the circuit board.

3.The wall control does not work OR the indicators flash.

•The wires may be in reverse position.

•The wires may be broken. •The wire in the wall OR the wall control may be defective.

•Ensure that the color coded wires have been connected to their appropriate places.

•Inspect every wire and replace any that are damaged.

•Remove the wall control and test it right beside the unit using another shorter wire. If the wall control works there, change the wire. If it does not, change the wall control.

4.The Humidity Control does not work OR the 20-minute push-button timer does not work OR its indicator light does not stay on.

•The wires may be in reverse position.

•The Humidity Control or push button may be defective.

•Ensure that the color coded wires have been connected to their appropriate places.

•Jump the OL and OC terminals. If

NO

C

NC

I

OC

OL

Y

R

G

B

the unit switches to high speed, remove

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the Humidity Control or push button

 

 

 

 

 

 

 

 

 

 

and test it right beside the unit using

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

beside the unit using another VE0098

shorter wire. If it works here, change the wire. If it doesn’t, change the Humidity Control or the push button.

5.The supply and/or exhaust motor do not work.

•The circuit board may be defective.

•The motor(s) may be defective.

•Press on the integrated control push button until the unit turn on low speed (the LED will light AMBER). Using a multimeter, check the voltage on J4-1 and J4-2 (for supply motor), and on J5-1 and J5-2 (for exhaust motor). The reading must be ± 68 V AC. Then set the unit on high speed by pressing on the integrated control 1 more time (the LED will light GREEN). Using a multimeter, check the voltage on J4-1 and J4-2 (for supply motor), and on J5-1 and J5-2 (for exhaust motor). The reading must be ± 120 V AC if the fan motor speed setting is Low-High, or ± 90 V AC if the fan motor speed setting is Low-Medium. If all the readings correspond to the right voltage values, the circuit board is not defective. If one or both readings are different, change the circuit board.

•Using a multimeter, check the ohms value on each motor connectors. For BLUE and BLACK motor wires, the right value is ± 52 ohms. For BLUE and BROWN motor wires, the right value is ± 72 ohms. For BROWN and BLACK motor wires, the right value is ± 124 ohms. If the ohm values are the same, the motor is not defective. Replace the motor capacitor.

6.

The defrost cycle does not work •Ice deposits may be hindering

•Remove the ice.

 

(the fresh air duct is frozen OR

the damper operation.

 

 

the fresh air distributed

 

 

 

is very cold.

•The damper rod or the port

•Inspect these parts and replace if necessary.

 

 

damper itself may be broken.

 

 

 

•The damper actuator or circuit board

•See point 2.

 

 

may be defective.

 

 

 

 

 

7.

The integrated control

•The 30-second boot sequence

•See Section 4.1.1 Boot Sequence

 

push button does not work.

is not completed.

 

- 26 -

Image 26
Contents Installation Instructions HRV90H and ERV90HC About this Manual About These Units LimitationTable of Contents Technical Data HRV ERVTechnical Data CONT’D Ventilation PerformanceHRV Typical Installations Typical Installations CONT’D Installation Stale air exhaust ductwork Installation CONT’DMake sure the unit is level Fresh air distribution ductworkMethod 2 Return side connection Method 1 Supply side connectionDuct, see figure beside Stale air intake Fresh air distributionDo not use screws to connect the rigid ducts to the ports Insulated flexible ductsRigid ducts 457 mm Xmas tree pin ’’ Ø Controls AvertissementControls CONT’D No C NC I OC OL Y R G BElectrical Connection to the Furnace OC OL Y R G6WIRINGDIAGRAM Balancing the Unit Connecting the Drain HRV Units only To drainMaintenance Maintenance CONT’D Service Parts HRV90HS HRV90HT ERV90HCS ERV90HCTTroubleshooting Problems Possible causes You should try thisManual DE Instalación Modelos HRV90H Y ERV90HC Advertancia Acerca DE Este ManualAcerca DE Estos Aparatos Limitación CuidadoÍndice Datos Técnicos Temperatura exterior Ciclos DE Deshielo DEL HRV y ERVRendimiento de ventilación Datos Técnicos ContinuaciónDimensiones Instalaciones Habituales Sistema Totalmente EntubadoInstalaciones Habituales Continuación Instalación Tubos de distribución del aire puro Compruebe que el aparato esté a nivelTubos de extracción de aire viciado Método 1 Conexión por el lado de la alimentación Método 2 Conexión por el lado de retornoAdmisión de aire viciado Distribución del aire puroTubos flexibles aislados Tubos rígidosTubo de aire de salida hacia el exterior Pasador de Instalación DE 2 Bocas Exteriores Controles Control IntegradoControles Continuación Conexión Eléctrica CON LA Caldera No C NCDiagrama DE Cableados Diagrama DE Cableados Diagrama LógicoEquilibrado DEL Aparato Ponga el aparato en velocidad altaConexión DEL Desagüe Aparatos HRV Únicamente Al desagüeMantenimiento Mantenimiento Continuación Piezas Solución DE Problemas Problemas Causas posibles Debería hacer esto
Related manuals
Manual 54 pages 23.2 Kb

ERV90HCT specifications

The Broan ERV90HCT and HRV90HT are remarkable energy recovery ventilators designed to enhance indoor air quality while promoting energy efficiency in residential settings. Both models are built with innovative technologies that meet the demands of modern homes, ensuring a comfortable living environment.

One of the standout features of the Broan ERV90HCT and HRV90HT is their energy recovery capabilities. They efficiently exchange stale indoor air with fresh outdoor air, recovering up to 90% of the energy that would otherwise be lost. This process not only improves air quality but also helps in reducing heating and cooling costs, making them an excellent investment for energy-conscious homeowners.

Another significant characteristic of both models is their quiet operation. Equipped with advanced fan technology, the ERV90HCT and HRV90HT work at minimal noise levels, ensuring a peaceful indoor atmosphere. Whether in a bedroom, living room, or office, occupants can enjoy the benefits of fresh air without disruptive noise.

The units are designed with user-friendly controls that make operation simple and intuitive. Homeowners can easily adjust settings to optimize airflow based on current needs, whether it’s high ventilation during peak usage times or lower settings for quieter moments. Additionally, the units come with a built-in timer, allowing for customizable operation schedules.

Durability is another hallmark of the Broan ERV90HCT and HRV90HT. Constructed with high-quality materials, these ventilators are designed for long-lasting performance. Furthermore, their compact design allows for flexible installation options, making them suitable for various home layouts and sizes.

The ERV90HCT features a heat recovery system, making it ideal for climates that experience significant temperature fluctuations, while the HRV90HT is tailored for those residing in colder regions. Both units utilize an efficient balanced ventilation system, ensuring that airflow is evenly distributed throughout the home.

In summary, the Broan ERV90HCT and HRV90HT are top-tier energy recovery ventilators that prioritize comfort, efficiency, and air quality. With their energy recovery capabilities, quiet operation, user-friendly controls, durability, and flexible installation options, they stand out in the market as excellent solutions for maintaining a healthy home environment. Whether seeking to reduce energy costs or improve indoor air quality, these models deliver on all fronts, making them a worthy addition to any household.