Slant/Fin BOILERS dimensions Requires AIR from OUT

Page 4

4

LIBERTY II

Any oil-fired boiler must have a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney draft* is unreliable, CO2 and overfire draft* will change unpredictably.

DO NOT vent this boiler to the same chimney flue used by a fireplace or coal or wood burning furnace or boiler. The draft* produced by solid fueled devices varies tremendously between high fire and low fire:

In modern, weather stripped, energy-saving buildings or older buildings which have been modified similarly, natural infiltration may not supply enough air for combustion, particularly if other fuel burning appliances, exhaust fans or draft inducers are competing for the same air supply. Fireplaces, other solid fuel burning appliances and exhaust fans con- sume great quantities of air; if air supply is not ample, such an appliance will create a downdraft in the oil-fired boiler flue. This can create a haz- ardous condition. Flue gases can be sucked out of the chimney through

the vent regulator into the living space. DO NOT operate this boiler and a solid fuel burning appliance at the same time, unless the solid fuel burner is provided with its own outside air supply.

See Table 2, “Provisions for Combustion and Ventilation Air Supply” for determining need and method of providing air for combustion and ventilation.

If fly screen must be used over air supply openings, areas calculated should be doubled; the screen should be inspected and cleaned fre- quently to maintain free air flow.

Protect air openings against closure by snow, debris, etc. Openings such as doors or windows, if used, must be locked open.

* Draft is negative or suction pressure

TABLE 2: Provisions for Combustion and Ventilation Air Supply. See NFPA 31, latest edition for more detailed information.

 

 

 

 

 

 

 

 

 

 

Boiler Location

Air Supply

 

 

Action Required

 

 

2.1

Unconfined space

Is there sufficient air for combus-

 

 

NONE

 

 

 

 

tion by natural infiltration (see

 

 

 

 

 

 

 

NOTE (1), “Test...” below)?

 

 

 

 

 

 

 

 

 

 

 

 

 

2.2

Unconfined space

If there is NOT sufficient air for

 

 

Provide air from outdoors directly through a permanent outside

 

 

 

 

combustion by natural infiltration

 

 

wall opening or openings with a free open area of not less than

 

 

 

 

due to tight construction or other

 

 

1 sq. in. per 4000 Btu/hr of TOTAL input of ALL fuel burning

 

 

 

 

conditions, then it REQUIRES AIR

 

 

appliances in the building. See Note (1) and (3).

 

 

 

 

FROM OUTDOORS. SEE

 

 

 

 

 

 

 

“ACTION REQUIRED” column at

 

 

 

 

 

 

 

right. See Notes (1) and (2) below.

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

Confined space

If there is sufficient air for combus-

 

 

 

 

 

 

 

tion from within building but it

 

 

The confined space shall be provided with two permanent air

 

 

 

 

comes from outside of the

 

 

openings, one near the top of the enclosure and one near the

 

 

 

 

confined space. SEE “ACTION

 

 

bottom. EACH opening shall have a free air opening of not less

 

 

 

 

REQUIRED” column at right.

 

 

than 1 sq. in. per 1000 Btu/hr. of TOTAL input of ALL fuel burning

 

 

 

 

See Note (1) below.

 

 

appliances within the enclosure. The two openings shall freely

 

 

 

 

 

 

 

communicate with the interior areas of the building which in turn

 

 

 

 

 

 

 

would have to have adequate infiltration of air from outdoors.

 

 

 

 

 

 

 

See Notes (1, 3) and Figure 3a.

 

 

 

 

 

 

 

 

 

 

2.4

Confined space

If there is NOT sufficient air for

 

 

(a) Air from the outdoors shall be provided to the confined space

 

 

 

 

combustion due to tight construc-

 

 

by two permanent openings, one in or near the top of the

 

 

 

 

tion or other conditions it

 

 

enclosure space and one in or near the bottom. The open-

 

 

 

 

REQUIRES AIR FROM OUT-

 

 

ings shall communicate directly, or by means of ducts, with

 

 

 

 

DOORS. SEE “ACTION

 

 

outdoors or to such spaces (crawl or attic) that freely com-

 

 

 

 

REQUIRED” column at right.

 

 

municate with outdoors (See figures 3b, 3c

 

 

 

 

See NOTE (2) below.

 

 

and 3d).

 

 

 

 

 

 

 

(b) Where directly communicating with outdoors or by means of

 

 

 

 

 

 

 

vertical ducts, each opening shall have a free area of not

 

 

 

 

 

 

 

less than 1 sq. in. per 4,000 Btu/hr. (35 sq. in. per gal. per hr.)

 

 

 

 

 

 

 

of TOTAL input rating of ALL appliances in the enclosure. If

 

 

 

 

 

 

 

horizontal ducts are used, each opening shall have a free

 

 

 

 

 

 

 

 

 

 

 

 

area of not less than 1 sq. in. per 2,000 Btu/hr. (70 sq. in. per

 

 

 

 

 

 

 

gal. per hr.) of TOTAL input of ALL appliances in the confined

 

 

 

 

 

 

 

space. See Figures 3b, 3c and 3d.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)Test for sufficient air for combustion by infiltration by running this boiler for 30 minutes under all of the following conditions and at the same time: a) all doors, win- dows and other like openings must be closed, b) all fuel burning appliances should be FIRING, c) all exhaust fans and clothes dryers turned ON. At the above conditions the CO2, smoke and draft readings must be normal. (CO2 between 11% and 13%, smoke between ZERO and a TRACE, draft between .02” W.C. and

.04” W.C. negative pressure.)

(2)Aside from tight construction, some of the conditions that steal air for combustion from a boiler are other fuel burning appliances, exhaust fans and clothes dryers.

(3)Generally, louvers made of wood have a free open area of 20% and those made of metal have a 60% to 70% free open area. Screens also reduce the open area of the louvers.

Image 4
Contents Liberty Liberty Chimney CONNECTOR-18 Boiler LocationMinimum Clearance Chimney RequirementsRequires AIR from OUT Liberty Installing Controls Accessories on Boiler Units Cleaning Piping SystemPiping Piping for Steam BoilersWiring the Boiler Installing the BurnerOIL Supply Piping Vent Piping and Draft Regulator Cleaning and Filling a NEW Water BoilerSTART-UPCOMBUSTION Test Instruments Must be Used Blowing OFF a LOW Pressure Steam Boiler Cleaning and Filling a NEW Steam BoilerLOW Water CUT-OFF CHECK-OUT Replacement of Steam Boilers Pressure Control CHECK-OUTLiberty Basic Module Wiring Detail a Liberty Burner Data Beckett CF-375 Burners for Packaged Boilers only DelevanLiberty Turbulator Settings Riello 40 Series Burner Data RielloLiberty Liberty II. Providing Protection for Freezing IV. General MaintenanceIII. OIL Burner

BOILERS specifications

Slant/Fin is a recognized leader in the manufacturing of high-quality cast iron and stainless steel boilers, providing reliable heating solutions for residential and commercial applications. With a commitment to performance and efficiency, Slant/Fin has developed a diverse range of boiler products that cater to various heating needs and preferences.

One of the key features of Slant/Fin boilers is their exceptional fuel efficiency, which is largely achieved through advanced design and engineering. Many Slant/Fin models are designed with state-of-the-art technology to maximize heat transfer while minimizing fuel consumption. This focus on efficiency not only reduces energy costs for homeowners and businesses but also contributes to environmental sustainability by lowering carbon emissions.

Another notable characteristic is the robust construction of Slant/Fin boilers. Made from high-quality materials such as cast iron and stainless steel, these boilers are built to last with impressive durability and resilience against corrosion. This construction ensures that the boilers can withstand the rigors of heating duties for many years, providing peace of mind to users regarding long-term reliability.

Slant/Fin also stands out in terms of its range of options that cater to different heating requirements. For instance, their Mod-Con series offers high-efficiency condensing technology, which captures and reuses heat from exhaust gases. This results in maximum efficiency levels of up to 96%, making these units a top choice for energy-conscious consumers.

Furthermore, Slant/Fin boilers are designed with user-friendliness in mind. Many models come equipped with advanced control systems that allow for precise temperature management, system monitoring, and easy integration with smart home technology. This means users can maintain optimal comfort levels while also managing energy consumption more effectively.

The company also prioritizes safety features in its boiler designs. Many Slant/Fin models include built-in safety controls that protect against overheating and pressure build-up, ensuring that the unit operates safely in various conditions.

In summary, Slant/Fin boilers exemplify a combination of efficiency, durability, and user-friendliness. With a variety of models tailored to meet a wide range of heating demands and a strong emphasis on safety, Slant/Fin continues to be a trusted choice for both residential and commercial heating needs. The company's innovative approach and commitment to quality ensure that customers receive superior performance and lasting value in their heating systems.