Performing the gas leak tests

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

Make sure to check for gas leaks before completing the installation process (connecting the assembly pipe and hose between indoor unit and outdoor unit, insulating the cables, hose and pipe, and fixing the indoor unit to the installation plate).

A

B

Test part for outdoor unit

Tightening torque for body cap (Refer to the table)

Spindle

Charging

core

R-22: Diameter of the screw - 7/16-20UNF

R-410A: Diameter of the screw - 1/2-20UNF

Tightening torque for charging port cap (Refer to the table)

To check for gas leaks on the outdoor unit,

Check the valve A and B using a leak detector.

To check for gas leaks on the indoor unit,

Check the flare nut C and D using a leak detector.

C D

Test part for indoor unit

Before inspecting the leakage, use a torque wrench to close the cap for the service valve. (Comply with a tightening torque for each size of the diameter,and tighten the cap firmly to prevent any leakage.).

To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the connection part of the indoor/outdoor units with soap lather or liquid for leakage test.

Outer

Tightening torque

Diameter

Body cap (N•m)

Charging port cap

(mm)

(N•m)

 

ø 6.35

20 ~ 25

 

ø 9.52

20 ~ 25

 

ø12.70

25 ~ 30

10 ~ 12

ø15.88

30 ~ 35

 

ø19.05

35 ~ 40

 

( 1 N•m = 10 kgf•cm )

Leak test with nitrogen (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A, it’s responsible of installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar (gauge).

Leak test with R-410A (after opening valves)

Before opening valves, discharge all the nitrogen from the system and create vacuum according to page 41~43. After opening valves, check leaks using a leak detector for refrigerant.

Pump down (before disconnecting the refrigerant connections for unit repair, removal or disposal) Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.

This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

Shut off the liquid valve with the Allen wrench.

Turn the system on in cooling with fan operating at high velocity.

(Compressor will immediately start, provided 3 minutes have elapsed since the last stop).

After 2 minutes of operation, shut the suction valve with the same wrench.

Turn the system off and switch mains supply off.

Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

Compressor damage may occur if run at a negative suction pressure.

English-44

Maldives ET IB&IM_DB68-06219A-00_EN.indd 44

2016/5/16 10:26:52

Image 44 Contents
Air conditioner Features of your new air conditioner Contents Safety precautions English-4English-5 01epaPr n atioFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9Checking before use Operation rangesModel AJ English-10Checking the name of the parts Main partsDisplay English-11English-12 Checking the remote controllerRemote controller buttons Remote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Button to adjust the temperature PressEnglish-15 Basic fun n iotAdjusting the air flow direction Press the Air swing button on the remote controllerVertical air flow Horizontal air flowUsing the Smart Saver function Using the turbo functionEnglish-17 24C~30CUsing the Quiet function Using the Auto Clean functionWhen the air conditioner is turned on English-18English-19 When the air conditioner is on and in cool/heat modeMode Setting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode English-20From the moment you have set the timer English-21If the air conditioner is on If the air conditioner is off Turn off automaticallyCleaning the air conditioner English-23 Cleaning the air filterRemoving the Air filter Maintaining the air conditioner English-24Troubleshooting Adjustment is notConditioner does English-25These modes, desired temperature is set to auto and you Check if you press the Set button on the remote controllerRoom or operate the air conditioner in Fan mode for When an indoor unit indicator blinks, contact the nearestInstalling the unit General informationEnglish-27 T05s In llan atioChoosing the installation location Power supply line, fuse or circuit breaker a place where the air filter can be replaced easily Indoor unitWhere sulfide gas exists Outdoor UnitEnglish-29 ModelWhen installing 1 outdoor unit When installing more than 1 outdoor unitSpace Requirements for Outdoor Unit English-30Accessories Accessories in the indoor unit caseEnglish-31 Unit mmAccessories in the outdoor unit case Optional accessoriesTools required for installation General Tools Tools for test operationsFixing the installation plate English-33Fix the indoor unit If you fix the indoor unit on a wall If you fix the indoor unit on a window frameConnecting the assembly cable Cable specificationConnecting the cable English-34English-35 Each wire is labeled with the corresponding terminal numberInStAllAtIOn English-36 Smooth the cut edgesCut off the remaining foam insulation TorqueEvacuating the indoor unit Cutting or extending the pipeEnglish-37 Unscrew the caps at the end of each pipeDepth a English-38Put a flare nut slightly into the pipe and modify the flare Drain hose installation English-39Wall Indoor unit Drain hose Drain hose must not Be bentEnglish-40 Check for leakage on both side of the drain outletEvacuating the connected pipes English-41Connect a drain hose to the drain plug Drain hole Drain plugAdding Refrigerant English-42Outer Torque If you use a pipe longer than 5 mEnglish-43 Performing the gas leak tests English-44Outdoor unit installed on the wall by rack Fixing the indoor unit in placeFixing the outdoor unit in place English-45English-46 Pump down procedure when removing the productFinal check and trial operation How to connect your extended power cables English-47Sub PCB installationoptional Wried remote controller, central remote controller etcEnglish-48 Only for multi systemEnglish-49 Questions or COMMENTS? Country
Related manuals
Manual 28 pages 39.02 Kb Manual 50 pages 48.99 Kb Manual 1 pages 46.73 Kb Manual 51 pages 18.39 Kb Manual 28 pages 11.1 Kb Manual 28 pages 7.21 Kb Manual 28 pages 12.32 Kb Manual 28 pages 13.27 Kb Manual 28 pages 21.38 Kb Manual 28 pages 20.36 Kb Manual 28 pages 35.95 Kb Manual 49 pages 54.48 Kb Manual 29 pages 21.43 Kb