Thomas & Betts LDAP 1200 Venting cont’d, Venting Requirements cont’d, Joints and Sealing cont’d

Page 28

24.Venting (cont’d)

Venting Requirements (cont’d)

4)Joints and Sealing (cont’d)

FIGURE 17C - Attaching Double-Wall (Type B) Terminal Pipe to a Single Wall or Category III Vent

Figure 17C - STEP 1

On the single-wall pipe or Category III pipe, place a continual

1/4 inch bead of silicone sealant around the circumference.

Do STEP 2 immediately after STEP 1.

Single-

Wall or

Category

III Vent

Pipe

Figure 17C - STEP 2

Insert the pipe with the sealant into the inner pipe of the double-wall pipe until the bead of sealant contacts the inner pipe creating a sealed joint.

Double-

Vent

Wall

Pipe

Pipe

with

 

Sealant

 

Pipe Run

Figure 17C - STEP 3

Spaced equally around the double-wall pipe, drill three small holes below the sealant ring. Insert 3/4 inch long sheetmetal screws to secure the joint. Do not over tighten screws.

5)Vent System Support

6)Condensation

7)Vent Terminal (Pipe and Vent Cap)

Support horizontal vent runs every six feet (1.8M). Support vertical runs of Type “B” double-wall or Category III vent pipe in accordance with the requirements of the pipe manufacturer. Support single-wall pipe in accordance with accepted indus- try practices. Do not rely on the heater for support of either horizontal or vertical vent pipe. Use non-combustible supports on vent pipe.

Any length of single-wall vent pipe exposed to cold air or run through an unheated area or an area with an ambient temperature of 45°F or less must be insulated along its entire length with a minimum of 1/2" foil-faced fiberglass, 1-1/2# density insu- lation. Where extreme conditions are anticipated, install a means of condensate disposal.

The vent terminal pipe must be either Category III vent pipe or double-wall (Type B). Heaters must be equipped with a Reznor vent cap, a Type L Breidert Air-x- hauster® vent cap or equivalent. A different style vent cap could cause nuisance problems or unsafe conditions. The vent cap must be the same diameter as the vent pipe.

See the clearance table below and FIGURE 18 for requirements of a horizontal vent terminal. See FIGURE 19 for requirements of vertical vent termination.

Horizontal Vent Terminal Clearances

A vent cap is required. Maintain a minimum clearance of 12 inches (305mm) from the wall to the vent terminal cap for stability under wind conditions.

Products of combustion can cause discolora- tion of some building finishes and deteriora- tion of masonry materials. Applying a clear silicone sealant that is normally used to pro- tect concrete driveways can protect masonry materials. If discoloration is an esthetic prob- lem, relocate the vent or install a vertical vent.

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 28

Structure

Minimum Clearances for Vent Termination

Location (all directions unless specified)

 

Forced air inlet within 10 ft (3.1M)

3 ft (0.9M) above

Combustion air inlet of another appliance

6 ft (1.8M)

Door, window, or gravity air inlet (any

4 ft (1.2M) horizontally

building opening)

4 ft (1.2M) below

 

1 ft (305mm) above

Electric meter, gas meter*, gas regulator*,

U.S. - 4 ft (1.2M) horizontally

and relief equipment

Canada - 6 ft (1.8M) horizontally)

Gas regulator *

U.S. - 3 ft (0.9M); Canada - 6 ft (1.8M)

Adjoining building or parapet

6 ft (1.8M)

Adjacent public walkways

7 ft (2.1M) above

Grade (ground level)

1 ft (305mm) above**

*Do not terminate the vent directly above a gas meter or service regulator.

** Consider local snow depth conditions. The vent must be at least 6” (152mm) higher than anticipated snow depth.

Image 28
Contents Table of Contents Reznor Model LdapWarranty General Installation CodesHazard Levels of Warnings in this Manual Switches Uncrating and Preparation High Altitude OperationTechnical Data DimensionsModel One DownflowModel LDAP800 and Model LDAP1200 Combustion Air ClearancesClearances inches/mm Mounting Height Heater Throw All Models Heater LocationThrow feet and meters Hanging or Mounting the Heater and Installing Louvers Heater Location cont’dSound Data Location RecommendationsWall Mounting Guidelines for Wall Mounting Model Ldap HeatersInstalling Heater and Louvers cont’d Installing LouversGas Piping and Pressures Sizing Gas SupplyValve Outlet or Orifice Pressure Setting Gas Connection SizeHorizontal Supply Vertical SupplyPressures GasCont’d Supply Wiring Burners Electrical Supply ConnectionsElectrical Supply and Connections cont’d Disconnect SwitchThermostat and Connections CL7 Thermostat and Connections cont’d Multiple Heater Control Option CL31 and Option CL32Connections for Model Ldap 1200 with Option CL1, CL2, CL3, CL7, or CL18Combustion Air Proving Pressure Switches Pressure Switch SettingsLimit Control High Limit ControlIgnition System Normal Heat Cycle Operating Sequence Abnormal Heat Cycle FunctionsIgnition System cont’d Fault Modes Lockout Fan Motor WiringGas Valves Fan MotorsWiring Diagrams Wiring DiagramWhite = Neutral Black = High Heat Speed Wiring Diagrams cont’d Above control wiring isAbove control wiring is Line VoltageVenting Venting RequirementsType of Vent Pipe VerticalJoints and Sealing Venting cont’d Venting Requirements cont’dJoints and Sealing cont’d Double Vent Wall Pipe With Sealant Pipe RunWall Ft 1M Minimum 305 mm Check the installation prior to startup Heater Startup Check Installation and StartupOperating Instructions Operating Sequence Check installation after startup Vent System Testing ProcedureMaintenance Schedule DimensionsWay Discharge Louvers, Option CD32 Nozzles NozzleHeat Exchanger Maintenance Burner Maintenance Location of ControlsBurner Maintenance cont’d Inspect and Clean the BurnerRe-Install the Burner Instructions to Re-Install the Burner Refer to FigureBurner Orifices Heat Section Venter Motor and WheelIgnitor Flame Sensor MeasurementHeat Section Venter Motor and Wheel cont’d Main Venter Motor and Wheel Models 800 and 1200 onlyFan Blades GuardsCombustion Air Pressure Switches Operating Gas ValvesTroubleshooting Vent SystemGeneral Troubleshooting Problem Probablecause RemedyGeneral Troubleshooting cont’d No heat Heater

LDAP 1200 specifications

The Thomas & Betts LDAP 1200 is a cutting-edge lighting control system designed specifically to enhance energy efficiency, reduce operational costs, and promote flexibility in various lighting applications. Ideal for commercial and industrial environments, the LDAP 1200 integrates advanced technologies to create a robust solution for managing lighting systems.

One of the standout features of the LDAP 1200 is its intelligent control capabilities. With occupancy sensors and daylight harvesting technology, the system can automatically adjust lighting levels based on the presence of people and the amount of natural light available. This results not only in energy savings but also in improved occupant comfort.

The LDAP 1200 is designed for easy installation and configuration. Its modular design allows for scalability, making it suitable for both small spaces and large commercial projects. The system supports a variety of lighting types, including LED, fluorescent, and incandescent, ensuring compatibility with existing infrastructure.

User-friendly interfaces are another key characteristic of the LDAP 1200. Operating through a centralized control panel or a mobile app, users can easily monitor and adjust lighting settings, schedule operations, and receive real-time feedback. This level of control empowers facility managers to respond quickly to changing needs and optimize lighting performance.

In terms of energy management, the LDAP 1200 integrates seamlessly with building management systems (BMS), enabling complex scheduling and reporting functions. The system collects data on energy usage, helping organizations to track performance and implement strategies to further reduce consumption.

Durability and reliability are paramount in industrial applications, and the LDAP 1200 does not disappoint. Constructed with high-quality materials, the system is designed to withstand everyday wear and tear. Its robust architecture ensures that it will function effectively in various environmental conditions.

In summary, the Thomas & Betts LDAP 1200 is a versatile and efficient lighting control solution that plays a critical role in enhancing energy efficiency, reducing costs, and improving user experience. With its intelligent control features, user-friendly interfaces, and compatibility with various lighting types, the LDAP 1200 represents a significant advancement in lighting technology, making it a smart choice for modern facilities seeking to optimize their lighting systems.