Thomas & Betts LDAP 1200 warranty Check installation after startup, Vent System Testing Procedure

Page 31

FIGURE 20 - Gas Valve ON/OFF Control Knob

Top View

Gas Control

 

Knob

 

(shown in the

 

ON position)

Side View

 

Gas

Gas

Flow

Flow

NOTE: If the appliance does not operate, follow the instructions "To Turn Off Gas to Appliance" printed below (and on the Operating Label on the heater) and call your service technician.

10.Thermostat calls for heat, energizing the venter motor(s).

11.The main combustion air pressure switch (Sizes 800 and 1200) and each heat section pressure switch close, firing the heater.

12.Burner flame is sensed and in 30 seconds after the gas valve is energized, the fan motor(s) is energized.

13.If the flame is extinguished during the main burner operation, the integrated control system closes the main valve and must be reset by interrupting power to the control circuit. (See lighting instructions on the heater.).

TO TURN OFF GAS TO THE APPLIANCE

1)Set thermostat to lowest setting

2)If service is to be performed, turn off all electric power to the appliance.

3)Open the access door(s).

4)Turn the gas control knob(s) clockwise to "OFF". Do not force.

5)Close the access door(s).

Check installation after startup:

Place the "Owner's Envelope" containing the Limited Warranty, this booklet, and any control or optional information in an accessible location near the heater. Follow the instructions on the envelope.

Vent System Testing Procedure

1.Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 or CSA B149.1 and B149.2, Installation Code for Gas Burning Appliances and Equipment, and this manual. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies that could cause an unsafe condition.

3.In so far as practical, close all building doors and windows and all doors between the space where the heater is and other spaces of the building. Turn on exhaust fans so they shall operate at maximum speed. Do not operate a summer exhaust fan.

4.Light the heater following the lighting instructions. Adjust the thermostat for continued operation. Verify that combustion products are venting properly. After determining that the heater vents properly, return doors, windows, and exhaust fans to their previous conditions. If improper venting is observed, the venting system must be corrected.

With the heater in operation, measure valve outlet gas pressure. If operated at high altitude, adjust outlet gas pressure for altitude. See information and instruc- tions in Paragraph 12.

Using the thermostat, turn the heater off and on, pausing two minutes between each cycle. Observe for smooth ignition.

DANGER: The gas burner in this gas-fired equipment is designed and equipped to provide safe controlled complete combustion. However, if the installation does not permit the burner to receive the proper supply of combustion air, complete combustion may not occur. The result is incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe operation of indirect-fired gas burning equipment requires a properly operating vent system that vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH.

Always comply with the combustion air requirements in the installation codes and in Paragraph 9. Combustion air at the burner should be regulated only by manufacturer-provided equipment. NEVER RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER. Heaters installed in a confined space must be supplied with air for combustion as required by Code and in Paragraph 9 of this heater installation manual. MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPER OPERATING CONDITION.

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 31

Image 31
Contents Reznor Model Ldap Table of ContentsWarranty General Installation CodesHazard Levels of Warnings in this Manual Uncrating and Preparation High Altitude Operation SwitchesDownflow Technical DataDimensions Model OneModel LDAP800 and Model LDAP1200 Combustion Air ClearancesClearances inches/mm Mounting Height Heater Throw All Models Heater LocationThrow feet and meters Location Recommendations Hanging or Mounting the Heater and Installing LouversHeater Location cont’d Sound DataGuidelines for Wall Mounting Model Ldap Heaters Wall MountingSizing Gas Supply Installing Heater and Louvers cont’dInstalling Louvers Gas Piping and PressuresVertical Supply Valve Outlet or Orifice Pressure SettingGas Connection Size Horizontal SupplyPressures GasCont’d Burners Electrical Supply Connections Supply WiringElectrical Supply and Connections cont’d Disconnect SwitchThermostat and Connections CL7 CL1, CL2, CL3, CL7, or CL18 Thermostat and Connections cont’dMultiple Heater Control Option CL31 and Option CL32 Connections for Model Ldap 1200 with OptionHigh Limit Control Combustion Air Proving Pressure SwitchesPressure Switch Settings Limit ControlIgnition System Abnormal Heat Cycle Functions Normal Heat Cycle Operating SequenceIgnition System cont’d Fan Motors Fault Modes LockoutFan Motor Wiring Gas ValvesWiring Diagram Wiring DiagramsWhite = Neutral Black = High Heat Speed Above control wiring is Wiring Diagrams cont’dLine Voltage Above control wiring isVertical VentingVenting Requirements Type of Vent PipeJoints and Sealing Double Vent Wall Pipe With Sealant Pipe Run Venting cont’dVenting Requirements cont’d Joints and Sealing cont’dWall Ft 1M Minimum 305 mm Check the installation prior to startup Heater Startup Check Installation and StartupOperating Instructions Operating Sequence Vent System Testing Procedure Check installation after startupNozzle Maintenance ScheduleDimensions Way Discharge Louvers, Option CD32 NozzlesLocation of Controls Heat Exchanger Maintenance Burner MaintenanceInstructions to Re-Install the Burner Refer to Figure Burner Maintenance cont’dInspect and Clean the Burner Re-Install the BurnerMeasurement Burner OrificesHeat Section Venter Motor and Wheel Ignitor Flame SensorGuards Heat Section Venter Motor and Wheel cont’dMain Venter Motor and Wheel Models 800 and 1200 only Fan BladesOperating Gas Valves Combustion Air Pressure SwitchesVent System TroubleshootingProblem Probablecause Remedy General TroubleshootingNo heat Heater General Troubleshooting cont’d

LDAP 1200 specifications

The Thomas & Betts LDAP 1200 is a cutting-edge lighting control system designed specifically to enhance energy efficiency, reduce operational costs, and promote flexibility in various lighting applications. Ideal for commercial and industrial environments, the LDAP 1200 integrates advanced technologies to create a robust solution for managing lighting systems.

One of the standout features of the LDAP 1200 is its intelligent control capabilities. With occupancy sensors and daylight harvesting technology, the system can automatically adjust lighting levels based on the presence of people and the amount of natural light available. This results not only in energy savings but also in improved occupant comfort.

The LDAP 1200 is designed for easy installation and configuration. Its modular design allows for scalability, making it suitable for both small spaces and large commercial projects. The system supports a variety of lighting types, including LED, fluorescent, and incandescent, ensuring compatibility with existing infrastructure.

User-friendly interfaces are another key characteristic of the LDAP 1200. Operating through a centralized control panel or a mobile app, users can easily monitor and adjust lighting settings, schedule operations, and receive real-time feedback. This level of control empowers facility managers to respond quickly to changing needs and optimize lighting performance.

In terms of energy management, the LDAP 1200 integrates seamlessly with building management systems (BMS), enabling complex scheduling and reporting functions. The system collects data on energy usage, helping organizations to track performance and implement strategies to further reduce consumption.

Durability and reliability are paramount in industrial applications, and the LDAP 1200 does not disappoint. Constructed with high-quality materials, the system is designed to withstand everyday wear and tear. Its robust architecture ensures that it will function effectively in various environmental conditions.

In summary, the Thomas & Betts LDAP 1200 is a versatile and efficient lighting control solution that plays a critical role in enhancing energy efficiency, reducing costs, and improving user experience. With its intelligent control features, user-friendly interfaces, and compatibility with various lighting types, the LDAP 1200 represents a significant advancement in lighting technology, making it a smart choice for modern facilities seeking to optimize their lighting systems.